| 2019-04-01 12:37:38 | 3RD REVIEW FBC-2017 MECHANICAL |
| | PERMIT #18090469 |
| | 360 S. ROSEMARY |
| | 4/1/19 |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | 1) THE REQUEST BY TLC ENGINEERING TO ADD THE FOLLOWING |
| | ITEMS TO THE DEFERRED SUBMITTAL IS ACCEPTED: |
| | A) AC COOLING AND HEATING CALCULATIONS. |
| | B) MINIMUM VENTILATION CALCULATIONS FOR ALL ROOMS AND |
| | SPACES. |
| | C) COMMISSIONING PLAN: THE PLAN IS THE FIRST STEP IN |
| | THE PROCESS WHICH CULMINATES WITH SUBMITTAL OF A FINAL |
| | COMMISSIONING REPORT. |
| | |
| | 2) REVISED M1.01 PLAN ERRORS AND OMISSIONS: |
| | A) KEYNOTE #3 IS BEING USED TO INDICATE BOTH EXHAUST AT |
| | THE GENERATOR ROOM AND AIR INTAKE OPENING FOR THE LOBBY |
| | AND CORE ROOMS AND SPACES. THE REQUESTED DAMPER AT THE |
| | INLET NOT SHOWN- SECTION C403.2.4.3 FBC EC. |
| | B) AH-DX-1-1 AND AH-DX-1-2 NOT IDENTIFIED- SECTION |
| | 107.2.1 WPB. |
| | C) AH-DX-1-7 IN THE POWER ROOM NOT SHOWN- SECTION |
| | 107.2.1 WPB. |
| | D) NOTE #5 INDICATES A FIRE-RATED ENCLOSURE FOR THE |
| | TANK ROOM MAKE UP AIR DUCT WHICH IS NOT REQUIRED, |
| | HOWEVER FIRE DAMPERS ARE REQUIRED AT THE DUCT |
| | PENETRATIONS OF FIRE-RATED WALLS- SECTION 607.5.2 FBC |
| | M. |
| | E) THE EXHAUST DUCT RUN FROM THE TANK ROOM TO THE |
| | EXTERIOR OF THE BUILDING IS NOT SHOWN, AND NO DUCT |
| | SPECIFICATIONS HAVE BEEN PROVIDED- TYPE AND SIZE OF |
| | DUCT, TERMINATION LOCATION AND CLEARANCES ETC- SECTION |
| | 510 FBC M. |
| | F) CONSTRUCTION DETAILS FOR THE FIRE-RATED EXHAUST DUCT |
| | ENCLOSURE NOT PROVIDED. THE RESPONSE NARRATIVE FROM TLC |
| | IS CALLING THIS OUT AS AN "INTERSTITIAL WALL". NO NOTES |
| | ON THE PLAN PROVIDED- SECTION 713.2 FBC B. |
| | G) THE LETTER DAIKIN CERTIFYING THE INSTALLATIONS OF |
| | THE OUTDOOR CONDENSERS IN THE ENCLOSED GARAGES IS NOT |
| | ACCEPTED: 1) IT IS INDICATING THE UNITS ARE TO BE |
| | INSTALLED IN AN "OPEN GARAGE" AND NOT AN ENCLOSED |
| | GARAGE. 2) THE LETTER IS FROM BECAUSE A SALES MANAGER, |
| | AND ALTERNATE DESIGNS AND METHODS MUST BE SUBMITTED BY |
| | A LICENSED DESIGN PROFESSIONAL. THE MANUFACTURER'S |
| | TECHNICAL DEPARTMENT CAN PROVIDE INSTALLATION DETAILS |
| | FOR INDOOR INSTALLATIONS THAT WOULD BE ACCEPTABLE IF |
| | THE DETAILS BEAR A SHOP DRAWING STAMP OF APPROVAL BY |
| | THE ENGINEER OF RECORD FOR THE PROJECT. PLEASE NOTE |
| | THAT THE LETTER MUST ADDRESS ALL THE CONDENSERS ON ALL |
| | FLOORS THAT ARE BEING INSTALLED IN THE ENCLOSED |
| | GARAGES- SECTION 304.1 FBC M. |
| | H) RETURN AIR MISSING FROM THE ENGINEERING ROOM- |
| | SECTION 601.6 FBC M. |
| | |
| | 3) REVISED M1.02 PLAN ERRORS AND OMISSIONS: |
| | A) NO O/A PRESSURIZATION PROVIDED FOR THE FIRE RESCUE |
| | ROOM- SECTION 404.3 FBC M. |
| | |
| | 4) REVISED M1.03 PLAN ERRORS AND OMISSIONS: |
| | A) NO O/A PRESSURIZATION PROVIDED FOR THE FIRE RESCUE |
| | ROOM- SECTION 404.3 FBC M. |
| | B) THE PLAN APPEARS TO SHOW A 4" ROUND DUCT SUPPLYING |
| | 660 CFMS OF CONDITIONED SUPPLY AIR TO THE FUTURE |
| | OFFICE, HOWEVER THE AIRFLOW ARROW SHOWN BY THE 12X10 |
| | OPENING IS IS MOST LIKELY REVERSED. I'M ASSUMING THIS |
| | IS SUPPOSED TO INDICATE THE O/A SUPPLY. PLEASE CORRECT |
| | AND PROVIDE NOTES TO CLARIFY- SECTION 107.2.1 WPB. |
| | C) NO TEXT HAS BEEN PROVIDED AT KEYED NOTE #6. |
| | |
| | 5) REVISED M1.04: |
| | A) NO O/A PRESSURIZATION PROVIDED FOR THE FIRE RESCUE |
| | ROOM- SECTION 404.3 FBC M. |
| | B) IT APPEARS THE O/A SUPPLY DUCT LAYOUT IS INCOMPLETE. |
| | NO INLET LOCATION IS SHOWN, NO NOTES- SECTION 107.2.1 |
| | WPB. |
| | |
| | 6) REVISED M1.05: |
| | A) NO O/A PRESSURIZATION PROVIDED FOR THE FIRE RESCUE |
| | ROOM- SECTION 404.3 FBC M. |
| | B) SEE COMMENT #4B ABOVE FOR SIMILAR DEFICIENCY. |
| | |
| | 7) REVISED M1.06: |
| | A) NO O/A PRESSURIZATION PROVIDED FOR THE FIRE RESCUE |
| | ROOM- SECTION 404.3 FBC M. |
| | B) NO TEXT PROVIDED FOR NOTES #4 & 5- SECTION 107.2.1 |
| | WPB. |
| | |
| | 8) REVISED M1.07: |
| | A) NO O/A PRESSURIZATION PROVIDED FOR THE FIRE RESCUE |
| | ROOM- SECTION 404.3 FBC M. |
| | B) NO TEXT PROVIDED FOR NOTES #4 & 5- SECTION 107.2.1 |
| | WPB. |
| | |
| | 9) REVISED M1.08: |
| | A) NO O/A PRESSURIZATION PROVIDED FOR THE FIRE RESCUE |
| | ROOM- SECTION 404.3 FBC M. |
| | B) NO TEXT PROVIDED FOR NOTES #4 & 5- SECTION 107.2.1 |
| | WPB. |
| | |
| | 10) M1.09: PLACE NOTES ON THE PLAN TO SHOW THE |
| | LOCATIONS OF THE O/A, THE TOILET EXHAUST, AND THE SMOKE |
| | EXHAUST SMOKE SHAFTS- |
| | A) PROVIDE MOTORIZED FIRE/SMOKE DAMPERS AT THE EXHAUST |
| | AND AIR INLET OPENINGS AT THE SHAFTS- SECTION 607.5.5 |
| | FBC M. |
| | |
| | PLEASE NOTE THE FOLLOWING: |
| | 1) SEPARATE PERMITS ARE REQUIRED FOR THE FUTURE |
| | RESTAURANT AND OFFICES, KITCHEN EXHAUST HOODS AND FIRE |
| | SUPPRESSION SYSTEM, WALK IN COOLERS AND FREEZERS. |
| | 2) DEFERRED SUBMITTALS |
| | REQUIRED SUBMITTALS LISTED BELOW SHALL HAVE SHOP |
| | DRAWING STAMPS BY THE EOR AND BE IN THE FIELD AT TIME |
| | OF INSPECTION. |
| | 1) SMOKE CONTROL FANS INCLUDING SMOKE EXHAUST FANS, AND |
| | STAIRWELL AND ELEVATOR PRESSURIZATION FANS. |
| | 2) FIRE DAMPERS AND FIRE/SMOKE DAMPERS. |
| | 3) MOTORIZED AND BAROMETRIC DAMPERS |
| | 4) DUCT SMOKE DETECTORS |
| | 5) LOUVERS FOR EXHAUST AND OUTSIDE AIR INTAKES |
| | INCLUDING MANUFACTURER'S SPECIFICATIONS AND FL. PRODUCT |
| | APPROVALS AND/OR MIAMI-DADE NOA'S |
| | 6) AC STAND NOA'S OR FL. PRODUCT APPROVALS |
| | 7) C0, N02, & CO2 SENSORS, AND REFRIGERANT LEAK |
| | DETECTORS. |
| | 8) COOLING TOWERS |
| | 9) FACTORY BUILT DUCTWORK |
| | 10) DUCT FIRE WRAPPING |
| | 11) CLOTHES DRYERS |
| | 12) COOKING APPLIANCES |
| | 13) TEST AND BALANCE REPORTS |
| | 14) SMOKE CONTROL TEST REPORTS. |
| | |
| | SUBMITTALS TO BE PROVIDED TO THE BUILDING DEPARTMENT |
| | FOR REVIEW. |
| | 1) SIGNED AND SEALED STRUCTURAL ENGINEERING FOR |
| | INSTALLATION OF ALL EXTERIOR MECHANICAL EQUIPMENT AND |
| | APPLIANCES. ALTERNATELY, SIGNED AND SEALED, OR |
| | DELEGATED ENGINEERING MAY BE AVAILABLE ONSITE AT THE |
| | TIME OF INSPECTION. PLEASE NOTE THAT DELEGATED |
| | ENGINEERING SHALL BEAR THE SHOP DRAWING STAMP OF THE |
| | STRUCTURAL ENGINEER RECORD. |
| | 2) GENERATORS AND FUEL TANKS AND ALL ASSOCIATED |
| | EQUIPMENT, VENT FLUES, AND FUEL OIL PIPING. |
| | 3) BOILERS AND WATER HEATERS INCLUDING COMBUSTION AIR |
| | DUCTS AND VENT FLUES. |
| | 4) COMMISSIONING REPORTS |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL PLANS EXAMINER |