| Plan Review Notes For Permit 18090469 |
| Permit Number |
18090469 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2019-02-12 15:46:30 | FLORIDA BUILDING CODE 2017 6TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED | | | NFPA 70 2014 EDITION | | | | | | JAKE LEAHY | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | PAGE 446 T5.03 | | | | | | RISER FOR FIBER OPTIC CABLE IS USING THE STAIRWELL TO | | | GET TO THE UPPER FLOORS. STAIRWELL CAN NOT BE USED AS | | | AMEANS TO RUN CABLE THROUGH A BUILDING | | | | | | FIREMAN'S COMMUNICATION SYSTEM PENETRATES THE STAIRWELL | | | MORE THAN ONE TIME. | | | | | | | | | PER FBC B1023.5 (6TH EDITION 2017) PENETRATIONS IN THE | | | STAIRWELLS ARE FORBIDDEN. PLEASE VERIFY RISER WILL NOT | | | BE USING STAIRWELLS AS A RACEWAY. | | | | | | | | | |
|