| 2018-12-10 11:37:37 | 1ST REVIEW: |
| | 2017 FLORIDA BUILDING CODE 6TH EDITION |
| | 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH |
| | EDITION |
| | 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH |
| | EDITION |
| | 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH |
| | EDITION |
| | |
| | PLUMBING COMMENTS: |
| | |
| | 1. PLEASE SHOW COMPLIANCE WITH THE FOLLOWING FBC ACC |
| | 2017 6TH EDITION. |
| | A) 604.2 LOCATION.THE WATER CLOSET SHALL BE POSITIONED |
| | WITH A WALL OR PARTITION TO THE REAR AND TO ONE SIDE. |
| | THE CENTERLINE OF THE WATER CLOSET SHALL BE 16 INCHES |
| | MINIMUM TO 18 INCHES MAXIMUM FROM THE SIDE WALL OR |
| | PARTITION. |
| | B) 604.3.1 SIZE.CLEARANCE AROUND A WATER CLOSET SHALL |
| | BE 60 INCHES MINIMUM MEASURED PERPENDICULAR FROM THE |
| | SIDE WALL AND 56 INCHES MINIMUM MEASURED PERPENDICULAR |
| | FROM THE REAR WALL. SHOW DIMENSIONS ON CLEAR FLOOR |
| | SPACE. |
| | C) 604.4 SEATS.THE SEAT HEIGHT OF A WATER CLOSET ABOVE |
| | THE FINISH FLOOR SHALL BE 17 INCHES MINIMUM AND 19 |
| | INCHES MAXIMUM MEASURED TO THE TOP OF THE SEAT. SEATS |
| | SHALL NOT BE SPRUNG TO RETURN TO A LIFTED POSITION. |
| | D) 604.5.1 SIDE WALL.THE SIDE WALL GRAB BAR SHALL BE 42 |
| | INCHES LONG MINIMUM, LOCATED 12 INCHES (305 MM) MAXIMUM |
| | FROM THE REAR WALL AND EXTENDING 54 INCHES MINIMUM FROM |
| | THE REAR WALL. |
| | E) 604.5.2 REAR WALL.THE REAR WALL GRAB BAR SHALL BE 36 |
| | INCHES LONG MINIMUM AND EXTEND FROM THE CENTERLINE OF |
| | THE WATER CLOSET 12 INCHES MINIMUM ON ONE SIDE AND 24 |
| | INCHES MINIMUM ON THE OTHER SIDE. |
| | F) 609.4 POSITION OF GRAB BARS.GRAB BARS SHALL BE |
| | INSTALLED IN A HORIZONTAL POSITION, 33 INCHES (840 MM) |
| | MINIMUM AND 36 INCHES (915 MM) MAXIMUM ABOVE THE FINISH |
| | FLOOR MEASURED TO THE TOP OF THE GRIPPING SURFACE. |
| | G) 604.7 DISPENSERS.TOILET PAPER DISPENSERS SHALL |
| | COMPLY WITH 309.4 AND SHALL BE 7 INCHES MINIMUM AND 9 |
| | INCHES MAXIMUM IN FRONT OF THE WATER CLOSET MEASURED TO |
| | THE CENTERLINE OF THE DISPENSER. THE OUTLET OF THE |
| | DISPENSER SHALL BE 15 INCHES MINIMUM AND 48 INCHES |
| | MAXIMUM ABOVE THE FINISH FLOOR. |
| | H) 603.3 MIRRORS.MIRRORS LOCATED ABOVE LAVATORIES OR |
| | COUNTERTOPS SHALL BE INSTALLED WITH THE BOTTOM EDGE OF |
| | THE REFLECTING SURFACE 40 INCHES MAXIMUM ABOVE THE |
| | FINISH FLOOR OR GROUND. |
| | I) 606.2 CLEAR FLOOR SPACE.A CLEAR FLOOR SPACE |
| | COMPLYING WITH 305, POSITIONED FOR A FORWARD APPROACH, |
| | AND KNEE AND TOE CLEARANCE COMPLYING WITH 306 SHALL BE |
| | PROVIDED. |
| | J) 606.3 HEIGHT.LAVATORIES AND SINKS SHALL BE INSTALLED |
| | WITH THE FRONT OF THE HIGHER OF THE RIM OR COUNTER |
| | SURFACE 34 INCHES MAXIMUM ABOVE THE FINISH FLOOR OR |
| | GROUND. |
| | K) THE SHOWER IN THE MANAGERS BATHROOM ON THE 1ST FLOOR |
| | SHALL COMPLY WITH ONE OF THE FOLLOWING. |
| | 608.2.1 TRANSFER TYPE SHOWER COMPARTMENTS.TRANSFER TYPE |
| | SHOWER COMPARTMENTS SHALL BE 36 INCHES BY 36 INCHES |
| | CLEAR INSIDE DIMENSIONS MEASURED AT THE CENTER POINTS |
| | OF OPPOSING SIDES AND SHALL HAVE A 36 INCH WIDE MINIMUM |
| | ENTRY ON THE FACE OF THE SHOWER COMPARTMENT. CLEARANCE |
| | OF 36 INCHES WIDE MINIMUM BY 48 INCHES LONG MINIMUM |
| | MEASURED FROM THE CONTROL WALL SHALL BE PROVIDED. |
| | 608.2.2 STANDARD ROLL-IN TYPE SHOWER |
| | COMPARTMENTS.STANDARD ROLL-IN TYPE SHOWER COMPARTMENTS |
| | SHALL BE 30 INCHES WIDE MINIMUM BY 60 INCHES DEEP |
| | MINIMUM CLEAR INSIDE DIMENSIONS MEASURED AT CENTER |
| | POINTS OF OPPOSING SIDES AND SHALL HAVE A 60 INCHES |
| | WIDE MINIMUM ENTRY ON THE FACE OF THE SHOWER |
| | COMPARTMENT. |
| | 608.2.3 ALTERNATE ROLL-IN TYPE SHOWER |
| | COMPARTMENTS.ALTERNATE ROLL-IN TYPE SHOWER COMPARTMENTS |
| | SHALL BE 36 INCHES WIDE AND 60 INCHES DEEP MINIMUM |
| | CLEAR INSIDE DIMENSIONS MEASURED AT CENTER POINTS OF |
| | OPPOSING SIDES.A 36 INCH WIDE MINIMUM ENTRY SHALL BE |
| | PROVIDED AT ONE END OF THE LONG SIDE OF THE |
| | COMPARTMENT. |
| | |
| | 2. PROVIDE MANUFACTURE SPECIFICATIONS FOR THE FUEL OIL |
| | FILL STATION, AUTOMATIC FUEL POLISHER, WATER HEATER, |
| | ELEVATOR SUMP PUMP, GREASE INTERCEPTOR AND DOMESTIC |
| | WATER BOOSTER PUMP. |
| | |
| | 3. SHT. P1.01 THE BACK PREVENTER'S ON THE DOMESTIC |
| | WATER MAIN AND FIRE LINE MAINS SHALL BE INSTALLED AS |
| | CLOSE AS POSSIBLE TO THE WATER METERS. PLEASE CONTACT |
| | DAVE PEARSON 822-2242 WPB UTILITIES DEPT. |
| | |
| | 4. PLEASE PLACE NOTES ON THE PLAN SEPARATE PERMITS ARE |
| | REQUIRED FOR BACKFLOWS, GREASE INTERCEPTORS. PER WPB |
| | AMEND TO FBC 107.2.1 |
| | |
| | 5. THE PLAN SHOWS 3000 GAL. GREASE INTERCEPTOR THE |
| | MAXIMUM SIZE ALLOWED IN WPB IS 1250 GAL. PLEASE CONTACT |
| | JEFFERY ODOMS 822-2172 WPB UTILITIES DEPT. |
| | |
| | 6. PROVIDE SIZING CALCULATIONS FOR THE GREASE |
| | INTERCEPTORS. PER WPB AMEND TO FBC 107.2.1 |
| | |
| | 7. SANITARY FACILITY'S WILL BE REQUIRED FOR THE RETAIL |
| | SPACE ON FST FLOOR WILL THERE BE ANY ROUGH PIPING |
| | INSTALLED ON THIS PROJECT. PER FBC PL 403.1 |
| | |
| | 8. PLEASE LABEL ALL STACKS AND RISERS ON THE FLOOR |
| | PLANS AND ISOMETRIC DRAWINGS FOR THE SANITARY, WATER |
| | AND STORM DRAIN. WPB AMEND TO FBC 107.2.1 |
| | |
| | 9. WHAT IS THE CONDENSATE RECYCLED WATER BEING USED FOR |
| | PLEASE PROVIDE PIPING DIAGRAM AND SHOW PIPING ON FLOOR |
| | PLAN. WPB AMEND TO FBC 107.2.1 |
| | |
| | 10. SHTS. P-1.02 THRU P-1.10 SHOW PIPING SIZES AND |
| | LABEL STACKS. WPB AMEND TO FBC 107.2.1 |
| | |
| | 11. SHT P-1.10 SHOWS A NOTE THAT STATES 4" |
| | STORM/OVERFLOW FROM ABOVE BUT NO PIPING IS SHOWN PLEASE |
| | CLARIFY. WPB AMEND TO FBC 107.2.1 |
| | |
| | 12. SHT. SHT. P4.01 PLEASE CLARIFY WHAT G.C.O. STANDS |
| | FOR. LOCATED BETWEEN LINE F AND G. WPB AMEND TO FBC |
| | 107.2.1 |
| | |
| | 13. PROVIDE PLUMBING FIXTURE BREAKDOWN PER FLOOR. WPB |
| | AMEND TO FBC 107.2.1 |
| | |
| | 14. SHT. P-4.02B A WATER FOUNTAIN IS REQUIRED FOR |
| | OFFICE SPACE. PER FBC PL TABLE 403.1 |
| | |
| | 15. THE THERMOSTATIC MIXING VALVE FOR THE TEMPERED |
| | WATER TO THE LAVATORY'S SHALL COMPLY WITH ASSE 1070 |
| | PLEASE PROVIDE MANUFACTURES SPECIFICATIONS TO VERIFY |
| | COMPLIANCE. PER FBC PL 416.5 |
| | |
| | 16. SHT. P5.02 THE POLISHING SYSTEM FOR THE FUEL OILS |
| | NOT SHOWN AS BEING PIPED INTO THE REST OF THE SYSTEM |
| | PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1 |
| | |
| | 17. PROVIDE THE MSDS SHEETS FOR THE FUEL OIL USED BY |
| | GENERATOR. . PER WPB AMEND TO FBC 107.2.1 |
| | |
| | 18. SHT. P-9.02 SHOW ON THE PLAN THE PIPE SLOPE AND ON |
| | THE PIPE ITSELF SHOW THE SQFT AND OR GPM. . PER WPB |
| | AMEND TO FBC 107.2.1 |
| | |
| | 19. PROVIDE A SANITARY COLLECTION ISOMETRIC DRAWING. . |
| | PER WPB AMEND TO FBC 107.2.1 |
| | |
| | 20. PROVIDE A COMPLETE WATER ISOMETRIC DRAWING. . PER |
| | WPB AMEND TO FBC 107.2.1 |
| | |
| | 21. PROVIDE DETAIL TO SHOW COMPLIANCE WITH FBC PL |
| | 308.6 SWAY BRACING.RIGID SUPPORT SWAY BRACING SHALL BE |
| | PROVIDED AT CHANGES IN DIRECTION GREATER THAN 45 |
| | DEGREES (0.79 RAD) FOR PIPE SIZES 4 INCHES AND LARGER. |
| | 308.7 ANCHORAGE. ANCHORAGE SHALL BE PROVIDED TO |
| | RESTRAIN DRAINAGE PIPING FROM AXIAL MOVEMENT. |
| | 308.7.1 LOCATION. FOR PIPE SIZES GREATER THAN 4 INCHES |
| | , RESTRAINTS SHALL BE PROVIDED FOR DRAIN PIPES AT ALL |
| | CHANGES IN DIRECTION AND AT ALL CHANGES IN DIAMETER |
| | GREATER THAN TWO PIPE SIZES. BRACES, BLOCKS, RODDING |
| | AND OTHER SUITABLE METHODS AS SPECIFIED BY THE COUPLING |
| | MANUFACTURER SHALL BE UTILIZED. |
| | PER WPB AMEND TO FBC 107.2.1 |
| | |
| | 22. SHT. P-4.09 SHOW DISTANCE OF SANITARY VENTS FROM |
| | AIR INTAKES MUST BE MIN. OF 10'. PER FBC PL 903.5 |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | |
| | GEORGE JOHNSON |
| | PLUMBING PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | 561-805-6711 |
| | [email protected] |
| | |