| 2018-10-15 10:26:01 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | 1) SHEET LS 1.01 - THERE IS NO INDICATIONS WHETHER THIS |
| | IS A MIXED OR SEPARATED OCCUPANCY. THERE DOES NOT |
| | APPEAR TO ANY RATED WALL ASSEMBLIES FOR THE CORRIDORS |
| | FROM THE RETAIL SPACES. |
| | |
| | PLEASE REVIEW AND CORRECT OF JUSTIFY WITH SPECIFIC CODE |
| | REFERNECES. |
| | |
| | |
| | |
| | 2) SHEET LS 0.01 - THERE IS AN INDICATION OF SMOKE |
| | CONTROL HOWEVER, THERE ARE NO CLEAR INDICATIONS OF TYPE |
| | AND NO RATIONAL ANALYSIS SUBMITTED. |
| | |
| | PER NFPA 1, CHAPTER 10 , GENERAL SAFETY REQUIREMENTS |
| | |
| | 10.14.3.4.4 ENGINEERING ANALYSIS AND CALCULATIONS. AN |
| | ENGINEERING ANALYSIS AND CALCULATIONS SHALL BE PROVIDED |
| | WITH THE |
| | FOLLOWING: |
| | (1) SMOKE PROTECTION CALCULATIONS AS FOLLOWS: |
| | (A) SMOKE EXHAUST AND FRESH AIR REQUIREMENTS PER NFPA |
| | 92, STANDARD FOR SMOKE CONTROL SYSTEMS |
| | (B) SMOKE MAINTAINED AT A LEVEL SIX FT ABOVE THE FLOOR |
| | OF THE |
| | MEANS OF EGRESS |
| | (C) PROPOSED TESTING PROTOCOL FOR SMOKE SYSTEM AND |
| | PASS/FAIL CRITERIA |
| | (D) CALCULATIONS FOR PERFORMANCE-BASED DESIGN METHODS |
| | ACCEPTED BY THE AHJ |
| | (E) SMOKE AND FIRE MODELING |
| | (F) TIMED EGRESS ANALYSIS |
| | (G) ASSUMED FLOW RATES AND TRAVEL SPEED |
| | |
| | PLEASE REVIEW AND PROVIDE. |
| | |
| | |
| | |
| | 3) LS 0.01 - THERE IS A COMMAND ROMM INDICATED. PLEASE |
| | ENSURE A GENEREATOR SWITCH AND FIRE SPRINKLER VALVE AND |
| | WATER FLOW PANEL ARE PROVIDED. |
| | |
| | PER NFPA 1, CHAPTER 11, BUILDING SERVICES |
| | |
| | 11.9 EMERGENCY COMMAND CENTER. WHERE REQUIRED, |
| | EMERGENCY |
| | COMMAND CENTERS SHALL COMPLY WITH SECTION 11.9. |
| | |
| | 11.9.4 THE FOLLOWING SHALL BE PROVIDED IN THE EMERGENCY |
| | COMMAND |
| | CENTER: |
| | (1) THE FIRE DEPARTMENT COMMUNICATION UNIT |
| | (2) A TELEPHONE FOR FIRE DEPARTMENT USE WITH CONTROLLED |
| | ACCESS TO THE |
| | PUBLIC TELEPHONE SYSTEM |
| | (3) SCHEMATIC BUILDING PLANS INDICATING THE TYPICAL |
| | FLOOR PLAN AND |
| | DETAILING THE BUILDING CORE MEANS OF EGRESS, FIRE |
| | PROTECTION |
| | SYSTEMS, FIRE-FIGHTING EQUIPMENT, AND FIRE DEPARTMENT |
| | ACCESS |
| | (4) WORK TABLE |
| | (5) IF APPLICABLE, HAZARDOUS MATERIAL MANAGEMENT PLANS |
| | FOR THE |
| | BUILDING |
| | 11.9.5 WHERE OTHERWISE REQUIRED, THE FOLLOWING DEVICES |
| | OR FUNCTIONS |
| | SHALL BE PROVIDED WITHIN THE EMERGENCY COMMAND CENTER: |
| | (1) THE EMERGENCY VOICE/ALARM COMMUNICATION SYSTEM UNIT |
| | (2) FIRE DETECTION AND ALARM SYSTEM ANNUNCIATOR UNIT |
| | (3) ANNUNCIATOR VISUALLY INDICATING THE LOCATION OF THE |
| | ELEVATORS AND |
| | WHETHER THEY ARE OPERATIONAL |
| | (4) STATUS INDICATORS AND CONTROLS FOR AIR-HANDLING |
| | SYSTEMS |
| | (5) CONTROLS FOR UNLOCKING STAIRWAY DOORS |
| | SIMULTANEOUSLY |
| | (6) SPRINKLER VALVE AND WATERFLOW DETECTOR DISPLAY |
| | PANELS |
| | (7) EMERGENCY AND STANDBY POWER STATUS INDICATORS |
| | (8) FIRE PUMP STATUS INDICATORS |
| | (9) GENERATOR SUPERVISION DEVICES AND MANUAL START AND |
| | TRANSFER |
| | FEATURES |
| | (10) PUBLIC ADDRESS SYSTEM, WHERE SPECIFICALLY REQUIRED |
| | BY OTHER |
| | SECTIONS OF THIS CODE |
| | (11) CONTROLS REQUIRED FOR SMOKE CONTROL |
| | |
| | AND |
| | |
| | PER NFPA 101, CHAPTER 11, SPECIAL STRUCTURES AND HIGH |
| | RISE BUILDINGS |
| | |
| | 11.8.6* EMERGENCY COMMAND CENTER. |
| | 11.8.6.1 AN EMERGENCY COMMAND CENTER SHALL BE PROVIDED |
| | IN A |
| | LOCATION APPROVED BY THE FIRE DEPARTMENT. |
| | 11.8.6.2 THE EMERGENCY COMMAND CENTER SHALL CONTAIN THE |
| | FOLLOWING: |
| | (1) VOICE FIRE ALARM SYSTEM PANELS AND CONTROLS |
| | (2) FIRE DEPARTMENT TWO-WAY TELEPHONE COMMUNICATION |
| | SERVICE |
| | PANELS AND CONTROLS WHERE REQUIRED BY ANOTHER SECTION |
| | OF THIS |
| | CODE |
| | (3) FIRE DETECTION AND FIRE ALARM SYSTEM ANNUNCIATION |
| | PANELS |
| | (4) ELEVATOR FLOOR LOCATION AND OPERATION ANNUNCIATORS |
| | (5) ELEVATOR FIRE RECALL SWITCH IN ACCORDANCE WITH ASME |
| | A17.1/CSA B44, SAFETY CODE FOR ELEVATORS AND ESCALATORS |
| | (6) ELEVATOR EMERGENCY POWER SELECTOR SWITCH(ES) WHERE |
| | PROVIDED |
| | IN ACCORDANCE WITH ASME A17.1/CSA B44 |
| | (7) SPRINKLER VALVE AND WATERFLOW ANNUNCIATORS |
| | (8) EMERGENCY GENERATOR STATUS INDICATORS |
| | (9) CONTROLS FOR ANY AUTOMATIC STAIRWAY DOOR UNLOCKING |
| | SYSTEM |
| | (10) FIRE PUMP STATUS INDICATORS |
| | (11) TELEPHONE FOR FIRE DEPARTMENT USE WITH CONTROLLED |
| | ACCESS TO THE |
| | PUBLIC TELEPHONE SYSTEM |
| | (12) STAIRWAY VIDEO MONITORING EQUIPMENT AS REQUIRED BY |
| | 11.8.8 |
| | |
| | |
| | PLEASE REVIEW, ENSURE COMPLIANCE AND PROVIDE AN |
| | APPLICABLE NOTE OF ACKNOWLEDGEMENT. |
| | |
| | |
| | |
| | 4 A) SHEET LS 1.09 - TWO EXITS ARE INDICATED FROM THE |
| | OUTSIDE SPACE INTO THE BUSINESS AREA. THESE EXITS DO |
| | NOT APPEAR TO HAVE THE MINIMUM EXIT SEPARATION |
| | REQUIRED. |
| | |
| | PER NFPA 101, CHAPTER 12 NEW ASSEMBLY OCCUPANCIES |
| | |
| | 12.2.5 ARRANGEMENT OF MEANS OF EGRESS. |
| | 12.2.5.1 GENERAL. |
| | 12.2.5.1.1 MEANS OF EGRESS SHALL BE ARRANGED IN |
| | ACCORDANCE WITH |
| | SECTION 7.5. |
| | |
| | |
| | 7.5.1.3 REMOTENESS SHALL BE PROVIDED IN ACCORDANCE WITH |
| | 7.5.1.3.1 |
| | THROUGH 7.5.1.3.7. |
| | 7.5.1.3.1 WHERE MORE THAN ONE EXIT, EXIT ACCESS, OR |
| | EXIT DISCHARGE IS |
| | REQUIRED FROM A BUILDING OR PORTION THEREOF, SUCH |
| | EXITS, EXIT ACCESSES, |
| | OR EXIT DISCHARGES SHALL BE REMOTELY LOCATED FROM EACH |
| | OTHER AND BE |
| | ARRANGED TO MINIMIZE THE POSSIBILITY THAT MORE THAN ONE |
| | HAS THE |
| | POTENTIAL TO BE BLOCKED BY ANY ONE FIRE OR OTHER |
| | EMERGENCY |
| | CONDITION. |
| | |
| | 7.5.1.3.2* WHERE TWO EXITS, EXIT ACCESSES, OR EXIT |
| | DISCHARGES ARE |
| | REQUIRED, THEY SHALL BE LOCATED AT A DISTANCE FROM ONE |
| | ANOTHER NOT |
| | LESS THAN ONE-HALF THE LENGTH OF THE MAXIMUM OVERALL |
| | DIAGONAL |
| | DIMENSION OF THE BUILDING OR AREA TO BE SERVED, |
| | MEASURED IN A |
| | STRAIGHT LINE BETWEEN THE NEAREST EDGE OF THE EXITS, |
| | EXIT ACCESSES, OR |
| | EXIT DISCHARGES, UNLESS OTHERWISE PROVIDED IN 7.5.1.3.3 |
| | THROUGH |
| | 7.5.1.3.5. |
| | |
| | PLEASE REVIEW AND CORRECT OR JUSTIFY WITH SPECIFIC CODE |
| | REFERENCES |
| | |
| | |
| | |
| | |
| | 4 B) SHEET LS 1.09 - TWO EXITS ARE INDICATED FROM THE |
| | OUTSIDE SPACE INTO THE BUSINESS AREA. THESE EXITS DO |
| | NOT APPEAR TO HAVE THE MINIMUM EXIT SEPARATION |
| | REQUIRED. |
| | |
| | PER NFPA 101, CHAPTER 12 NEW ASSEMBLY OCCUPANCIES |
| | |
| | 12.2.5 ARRANGEMENT OF MEANS OF EGRESS. |
| | 12.2.5.1 GENERAL. |
| | 12.2.5.1.1 MEANS OF EGRESS SHALL BE ARRANGED IN |
| | ACCORDANCE WITH |
| | SECTION 7.5. |
| | |
| | |
| | 7.5.1.3 REMOTENESS SHALL BE PROVIDED IN ACCORDANCE WITH |
| | 7.5.1.3.1 |
| | THROUGH 7.5.1.3.7. |
| | 7.5.1.3.1 WHERE MORE THAN ONE EXIT, EXIT ACCESS, OR |
| | EXIT DISCHARGE IS |
| | REQUIRED FROM A BUILDING OR PORTION THEREOF, SUCH |
| | EXITS, EXIT ACCESSES, |
| | OR EXIT DISCHARGES SHALL BE REMOTELY LOCATED FROM EACH |
| | OTHER AND BE |
| | ARRANGED TO MINIMIZE THE POSSIBILITY THAT MORE THAN ONE |
| | HAS THE |
| | POTENTIAL TO BE BLOCKED BY ANY ONE FIRE OR OTHER |
| | EMERGENCY |
| | CONDITION. |
| | |
| | 7.5.1.3.2* WHERE TWO EXITS, EXIT ACCESSES, OR EXIT |
| | DISCHARGES ARE |
| | REQUIRED, THEY SHALL BE LOCATED AT A DISTANCE FROM ONE |
| | ANOTHER NOT |
| | LESS THAN ONE-HALF THE LENGTH OF THE MAXIMUM OVERALL |
| | DIAGONAL |
| | DIMENSION OF THE BUILDING OR AREA TO BE SERVED, |
| | MEASURED IN A |
| | STRAIGHT LINE BETWEEN THE NEAREST EDGE OF THE EXITS, |
| | EXIT ACCESSES, OR |
| | EXIT DISCHARGES, UNLESS OTHERWISE PROVIDED IN 7.5.1.3.3 |
| | THROUGH |
| | 7.5.1.3.5. |
| | |
| | |
| | PLEASE REVIEW AND CORRECT OR JUSTIFY WITH SPECIFIC CODE |
| | REFERENCES |
| | |
| | |
| | |
| | |
| | |
| | 5) SHEET F 1.01 - THERE ARE INDICATIONS OF A FIRE PUMP |
| | TEST HEADER AND FIRE DEPARTMENT CONNECTION AT THE SAME |
| | LOCATION. |
| | |
| | PLEASE ENSURE THAT THESE ARE NOT ONE PIECE OF EQUIPMENT |
| | AS THEY ARE TWO DISTINCT PIECES WITH DIFFERENT |
| | FUNCTIONS. |
| | |
| | PLEASE REVIEW AND PROVIDE AN APPLICABLE NOTE OF |
| | ACKNOWLEDGEMENT. |
| | |
| | |
| | |
| | |
| | 6) SHEET P 1.01 - THERE DOES NOT APPEAR TO BE ANY CLEAR |
| | INDICATIONS OF A FLOOR DRAIN IN THE FIRE PUMP ROOM |
| | |
| | PER NFPA 20, CHAPTER 4, GENERAL REQUIREMENTS |
| | |
| | 4.12.7* DRAINAGE. |
| | 4.12.7.1 FLOORS SHALL BE PITCHED FOR ADEQUATE DRAINAGE |
| | OF ESCAPING |
| | WATER AWAY FROM CRITICAL EQUIPMENT SUCH AS THE PUMP, |
| | DRIVER, CONTROLLER, AND SO FORTH. |
| | 4.12.7.2 THE PUMP ROOM OR PUMP HOUSE SHALL BE PROVIDED |
| | WITH A FLOOR DRAIN THAT WILL DISCHARGE TO A FROST-FREE |
| | LOCATION. |
| | |
| | |
| | |
| | |
| | 7) SHEET A 4.01 - THE IS AN INDICATION OF A FUEL TANK |
| | IN THE FUEL TANK ROOM; HOWEVER, THERE ARE NO DETAILS |
| | PROVIDED ON THE FUEL TANK. |
| | |
| | THIS FUEL TANK PROVIDE EMERGENCY POWER AND SHALL COMPLY |
| | WITH NFPA |
| | |
| | PER NFPA 110 |
| | |
| | 7.9.1.1 ALL FUEL TANKS AND SYSTEMS SHALL BE INSTALLED |
| | AND MAINTAINED |
| | IN ACCORDANCE WITH NFPA 30, FLAMMABLE AND COMBUSTIBLE |
| | LIQUIDS CODE; NFPA 37, STANDARD FOR THE INSTALLATION |
| | AND USE OF |
| | STATIONARY COMBUSTION ENGINES AND GAS TURBINES; NFPA |
| | 54, NATIONAL |
| | FUEL GAS CODE; AND NFPA 58, LIQUEFIED PETROLEUM GAS |
| | CODE. |
| | 7.9.3.1* GALVANIZED FUEL LINES SHALL NOT BE USED. |
| | 7.9.3.2 APPROVED FLEXIBLE FUEL LINES SHALL BE USED |
| | BETWEEN THE |
| | PRIME MOVER AND THE FUEL PIPING. |
| | |
| | 7.9.11 ALL MANUAL FUEL SYSTEM VALVES SHALL BE OF THE |
| | INDICATING |
| | TYPE. |
| | 7.9.12.1 A MINIMUM CLEARANCE OF 0.9 M (36 IN.) SHALL BE |
| | MAINTAINED ON ALL SIDES. |
| | |
| | PLEASE PROVIDE DETAILS. |
| | |
| | |
| | |
| | 8) THERE IS AN INDICATION OF A FUEL TANK WITHIN THE |
| | GENERATOR ROOM. THERE IS NO INDICATION IF THIS TANK IS |
| | DOUBLE WALLED OR THERE IS CONTAIMENT. |
| | |
| | PER NFPA 30 |
| | |
| | 9.13* CONTAINMENT, DRAINAGE, AND SPILL CONTROL. |
| | 9.13.1 STORAGE AREAS SHALL BE DESIGNED AND OPERATED TO |
| | PREVENT |
| | THE DISCHARGE OF LIQUIDS TO PUBLIC WATERWAYS, PUBLIC |
| | SEWERS, |
| | OR ADJOINING PROPERTY, UNLESS SUCH DISCHARGE HAS BEEN |
| | SPECIFICALLY |
| | APPROVED. |
| | |
| | PLEASE PROVIDE SPECIFIC DETAILS FOR SPILL CONTAINMENT. |
| | |
| | |
| | 9) SHEET A 4.01 AND M 1.01 - THERE IS AN INDICATION OF |
| | A GENERATOR AND EXHAUST PIPING, HOWEVER, THERE ARE NO |
| | DETAILS. |
| | |
| | THE INSTALLATION OF THE GENERATOR SHALL BE UNDER |
| | SEPARATE PERMIT APPLICATION |
| | |
| | PER NFPA 110 |
| | |
| | 7.10 EXHAUST SYSTEM. |
| | 7.10.1 THE EXHAUST SYSTEM EQUIPMENT AND INSTALLATION, |
| | INCLUDING |
| | PIPING, MUFFLER, AND RELATED ACCESSORIES, SHALL BE IN |
| | ACCORDANCE WITH NFPA37, STANDARD FOR THE INSTALLATION |
| | AND USE OF |
| | STATIONARY COMBUSTION ENGINES AND GAS TURBINES, AND |
| | OTHER APPLICABLE |
| | STANDARDS. |
| | 7.10.2 EXHAUST SYSTEM INSTALLATION SHALL BE GASTIGHT TO |
| | PREVENT |
| | EXHAUST GAS FUMES FROM ENTERING INHABITED ROOMS OR |
| | BUILDINGS |
| | AND TERMINATE IN SUCH A MANNER THAT TOXIC FUMES CANNOT |
| | REENTER A BUILDING OR STRUCTURE, PARTICULARLY THROUGH |
| | WINDOWS, |
| | AIR VENTILATION INLETS, OR THE ENGINE AIR-INTAKE |
| | SYSTEM. |
| | 7.10.3* EXHAUST PIPING SHALL BE CONNECTED TO THE PRIME |
| | MOVER |
| | BY MEANS OF A FLEXIBLE CONNECTOR AND SHALL BE |
| | INDEPENDENTLY |
| | SUPPORTED THEREAFTER SO THAT NO DAMAGING WEIGHT OR |
| | STRESS IS |
| | APPLIED TO THE ENGINE EXHAUST MANIFOLD OR TURBOCHARGER. |
| | |
| | PLEASE PROVIDE SPECIFIC DETAILS AND SPEC SHEETS. |
| | |
| | |
| | |
| | 10) SHEET AE 4.01 - DOORS # 115A, 115C AND 122A |
| | INDICATION THEIR SWING TO WHAT APPEARS TO BE AGAINST |
| | THE PATH OF TRAVEL. |
| | |
| | PER NFPA 101, CHAPTER 7, MEANS OF EGRESS |
| | |
| | 7.2.1.4.2 DOOR LEAF SWING DIRECTION. DOOR LEAVES |
| | REQUIRED TO BE |
| | OF THE SIDE-HINGED OR PIVOTED-SWINGING TYPE SHALL SWING |
| | IN THE |
| | DIRECTION OF EGRESS TRAVEL UNDER ANY OF THE FOLLOWING |
| | CONDITIONS: |
| | (1) WHERE SERVING A ROOM OR AREA WITH AN OCCUPANT LOAD |
| | OF 50 OR |
| | MORE, EXCEPT UNDER ANY OF THE FOLLOWING CONDITIONS: |
| | (A) DOOR LEAVES IN HORIZONTAL EXITS SHALL NOT BE |
| | REQUIRED TO |
| | SWING IN THE DIRECTION OF EGRESS TRAVEL WHERE PERMITTED |
| | BY 7.2.4.3.8.1 OR 7.2.4.3.8.2. |
| | (B) DOOR LEAVES IN SMOKE BARRIERS SHALL NOT BE REQUIRED |
| | TO |
| | SWING IN THE DIRECTION OF EGRESS TRAVEL IN EXISTING |
| | HEALTH |
| | CARE OCCUPANCIES, AS PROVIDED IN CHAPTER 19. |
| | (2) WHERE THE DOOR ASSEMBLY IS USED IN AN EXIT |
| | ENCLOSURE, UNLESS |
| | THE DOOR OPENING SERVES AN INDIVIDUAL LIVING UNIT THAT |
| | OPENS |
| | DIRECTLY INTO AN EXIT ENCLOSURE |
| | (3) WHERE THE DOOR OPENING SERVES A HIGH HAZARD |
| | CONTENTS AREA |
| | |
| | PLEASE REVIEW THE OCCUPANCY LOAD CALCULATIONS AND |
| | POTENIAL EGRESS THRU THESE DOORS AND CORRECT OF JUSTIFY |
| | WITH SPECIFIC DETAILS. |
| | |
| | |
| | |
| | |
| | |
| | 11) SHEET LS 1.06 - THERE IS AN OPEN/PUBLIC SPACE WITH |
| | AN INDICATED OCCUPANCY LOAD OF 100 SQ FT 1 OCC. |
| | |
| | THIS IS AN ASSEMBLY SPACE PER THE FFPC WITH AN |
| | OCCUPANCY LOAD OF 15 SQ FT/PERSON OR 106 PERSONS. |
| | |
| | BASED ON THIS NEW OCCUPANCY LOAD THE DOORS/GATES |
| | LEADING INTO THE GARAGE AREA SHALL SWING IN THE PATH OF |
| | TRAVEL. |
| | |
| | PLEASE REVIEW AND OR JUSTIFY WITH SPECIFIC CODE |
| | REFERENCES. |
| | |
| | |
| | |
| | |
| | 12 A) SHEET LS 1.09 - THERE IS AN OPEN/PUBLIC SPACE |
| | WITH AN INDICATED OCCUPANCY LOAD OF 100 SQ FT 1 OCC. ; |
| | 14 PERSONS |
| | |
| | THIS IS AN ASSEMBLY SPACE PER THE FFPC WITH AN |
| | OCCUPANCY LOAD OF 15 SQ FT/PERSON OR 89 PERSONS. |
| | |
| | BASED ON THIS NEW OCCUPANCY LOAD THE DOORS LEADING INTO |
| | THE OFFICE AREA SHALL SWING IN THE PATH OF TRAVEL IN |
| | ADDITIONAL OF MEETING THE SEPARATION REQUIRED AS PER # |
| | 4 ABOVE. |
| | |
| | PLEASE REVIEW AND OR JUSTIFY WITH SPECIFIC CODE |
| | REFERENCES. |
| | |
| | |
| | |
| | 12 B) SHEET LS 1.09 - THERE IS AN OPEN/PUBLIC SPACE |
| | WITH AN INDICATED OCCUPANCY LOAD OF 100 SQ FT 1 OCC. ; |
| | 16 PERSONS |
| | |
| | THIS IS AN ASSEMBLY SPACE PER THE FFPC WITH AN |
| | OCCUPANCY LOAD OF 15 SQ FT/PERSON OR 199 PERSONS. |
| | |
| | BASED ON THIS NEW OCCUPANCY LOAD THE DOORS LEADING INTO |
| | THE OFFICE AREA SHALL SWING IN THE PATH OF TRAVEL IN |
| | ADDITIONAL OF MEETING THE SEPARATION REQUIRED AS PER # |
| | 4 ABOVE. |
| | |
| | PLEASE REVIEW AND OR JUSTIFY WITH SPECIFIC CODE |
| | REFERENCES. |
| | |
| | |
| | |
| | |
| | |
| | |
| | 13) SHEET FA 1.02 - THERE IS A PULL STATION AT STAIRWAY |
| | # 3 THAT IS INDICATED MORE THAN 5' FROM THE EXIT DOOR. |
| | |
| | THOUGH THIS IS NOT THE SHOP DRAWING IT NEEDS TO BE |
| | CALLED OUT FOR CORRECTION. |
| | |
| | |
| | PLEASE REVIEW AND CORRECT. |
| | |
| | |
| | |
| | 14) SHEET FA 1.02 - THERE IS NO PULL STATION LOCATED AT |
| | THE REAR OFFICE EXIT DOOR 201 FROM THE OFFICE AREA. |
| | |
| | THOUGH THIS IS NOT THE SHOP DRAWING IT NEEDS TO BE |
| | CALLED OUT FOR CORRECTION. |
| | |
| | |
| | PLEASE REVIEW AND CORRECT. |
| | |
| | |
| | 15) SHEET FA 1.02 - THERE IS A PULL STATION INDICATED |
| | ON THE ELEVATOR WALL BY STAIRWAY # 5, SHEET AE 4.02 |
| | DOES NOT INDICATE AND EXIT DOOR AT THAT LOCATION. |
| | |
| | THERE IS NO EXIT DOOR SHOWN ON THIS PLAN SHEET AT |
| | STAIRWAY # 5 AS COMPARED TO AE 4.02 WHICH INDICATES A |
| | COMPLETLY DIFFERENT STAIRWAY DESIGN. |
| | |
| | THOUGH THIS IS NOT THE SHOP DRAWING IT NEEDS TO BE |
| | CALLED OUT FOR CORRECTION. |
| | |
| | |
| | PLEASE REVIEW AND CORRECT |
| | |
| | |
| | |
| | 16) SHEET FA 1.03 - THERE IS A PULL STATION INDICATED |
| | ON THE ELEVATOR WALL BY STAIRWAY # 5, SHEET AE 4.03 |
| | DOES NOT INDICATE AND EXIT DOOR AT THAT LOCATION. |
| | |
| | THOUGH THIS IS NOT THE SHOP DRAWING IT NEEDS TO BE |
| | CALLED OUT FOR CORRECTION. |
| | |
| | |
| | PLEASE REVIEW AND CORRECT |
| | |
| | |
| | |
| | 17) SHEET FA 1.04 - THERE IS NO PULL STATION LOCATED AT |
| | THE REAR OFFICE EXIT DOOR 401 FROM THE OFFICE AREA. |
| | |
| | THOUGH THIS IS NOT THE SHOP DRAWING IT NEEDS TO BE |
| | CALLED OUT FOR CORRECTION. |
| | |
| | |
| | PLEASE REVIEW AND CORRECT. |
| | |
| | |
| | |
| | |
| | 18) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | |
| | |
| | 19) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |