| 2018-10-10 12:45:01 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT #18090428 |
| | 10/10/18 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) AC SYSTEMS #2 & 3 HAVE INCREASED IN CAPACITY WHICH |
| | INDICATES THEY ARE OVERSIZED ACCORDING TO THE APPROVED |
| | AC COOLING AND HEATING CALCULATIONS THAT WERE SUBMITTED |
| | UNDER PERMIT #17080883. THIS IS AN ENERGY CODE |
| | VIOLATION PER SECTION C403.2.2 FBC EC. |
| | |
| | 2) THE COOLING AND HEATING CAPACITIES FOR AC SYSTEMS #2 |
| | & 3 SHOWN IN THE REVISED EQUIPMENT SCHEDULE DO NOT |
| | MATCH THE DATA SHOWN IN THE APPROVED ENERGY |
| | CALCULATIONS. |
| | |
| | 3) DUCT SMOKE DETECTORS ARE REQUIRED IN THE SUPPLY AIR |
| | SYSTEMS OF AHU- 2 & 3 PER SECTION 606.2.1 FBC M. PLEASE |
| | NOTE THAT AN EXEMPTION CAN BE APPLIED IF THE |
| | MANUFACTURER'S SPECIFICATIONS INDICATE SYSTEMS ARE NOT |
| | CAPABLE OF PRODUCING OVER 2000 CFMS OF SUPPLY AIR. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS |
| | |