| 2018-10-04 14:35:30 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION |
| | FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION |
| | FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION |
| | FAC= FLORIDA ADMINISTRATIVE CODE |
| | FS = FLORIDA STATUTES |
| | |
| | 1ST REVIEW: |
| | PLUMBING COMMENTS: DENIED |
| | |
| | 1. CONSTRUCTION DOCUMENTS SHALL BE PREPARED BY A |
| | REGISTERED DESIGN PROFESSIONAL WHERE REQUIRED BY |
| | CHAPTER 471, FLORIDA STATUTES & 61G15 FLORIDA |
| | ADMINISTRATIVE CODE OR CHAPTER 481, FLORIDA STATUTES & |
| | 61G1 FLORIDA ADMINISTRATIVE CODE. SEAL AND SIGNATURE |
| | REQUIRED. |
| | 2. PROVIDE PIPING MATERIALS TYPE & FIRE RATED |
| | ASSEMBLIES FOR NEW OR RELOCATED PIPING FLOOR |
| | PENETRATIONS PER WPB FBC 107.2.1 |
| | 3. RE: PLAN SHEET P-1.0; FIXTURE DRAIN FOR KITCHEN SINK |
| | SHALL BE PROVIDED WITH AN AIR ADMITTANCE VALVE IN |
| | ACCORDANCE WITH FBC PL SECTION 918 OR SHALL CONNECT TO |
| | THE VERTICAL PORTION OF THE EXISTING VENT AND SHALL NOT |
| | CONNECT BELOW THE WEIR OF THE TRAP PER FBC PL 909.2. |
| | 4. RE: PLAN SHEET P-1.0; FIXTURE DRAIN FOR LAVATORY |
| | SHALL BE PROVIDED WITH AN AIR ADMITTANCE VALVE IN |
| | ACCORDANCE WITH FBC PL SECTION 918 OR SHALL CONNECT TO |
| | THE VERTICAL PORTION OF THE EXISTING VENT AND SHALL NOT |
| | CONNECT BELOW THE WEIR OF THE TRAP PER FBC PL 909.2. |
| | UPON REVIEW OF THE DIFFERENCE BETWEEN THE DEMO PLAN |
| | (A-2.0)AND THE PROPOSED PLAN (A-2.1) IT APPEARS THAT |
| | THE EXISTING VERTICAL VENT WILL BE DEMOLISHED ALONG |
| | WITH THE WALL REMOVAL. PLEASE CLARIFY. WPB FBC 107.2.1 |
| | 5. RE: PLAN SHEET P-1.0; THIS PROJECT IS NOT CONSIDERED |
| | RESIDENTIAL (ONE AND TWO FAMILY) AS NOTED IN WPB FBC |
| | 107.3.5.3, BUT PLUMBING AS NOTED IN WPB FBC |
| | 107.3.5.1.3; THEREFORE REFERENCES TO FBC RESIDENTIAL |
| | CODE SUCH AS P2701, TABLE P3002.1.1 AND P3002.1.2 SHALL |
| | BE REPLACED WITH APPROPRIATE SECTIONS OF FBC PLUMBING |
| | CHAPTERS 4 AND 7. ADDITIONALLY THE CHART FOR PLUMBING |
| | FIXTURE MAXIMUM FLOW RATES SHALL CONFORM TO THE |
| | REQUIREMENTS OF FBC PLUMBING CHAPTER 6. |
| | 6. RE: PLAN SHEET P-1.0; REPLACE THE NOTE CONCERNING |
| | THE ANTI-SCALD CONTROL VALVE(S) FOR SHOWERS AND |
| | BATHTUBS WITH THE FOLLOWING " SHOWER AND COMBINATION |
| | TUB/SHOWER CONTROLS SHALL BE PRESSURE BALANCED |
| | PB,THERMOSTATIC MIXING (TM) OR COMBINATION PB/TM VALVE |
| | TYPES WITH HIGH TEMPERATURE LIMITING STOP. FPC PL |
| | 424.3" |
| | 7. RE: PLAN SHEET P-1.0; PLUMBING NOTE #1. ADD THE WORD |
| | "PLUMBING" AFTER THE WORD "EDITION". WPB FBC 107.2.1 |
| | 8. RE: PLAN SHEET P-1.0; PLUMBING NOTE #10. REPLACE THE |
| | WORD "CHAMBERS" WITH THE WORDS "HAMMER ARRESTORS". WPB |
| | FBC 107.2.1, FPC PL 604.9 |
| | 9. RE: PLAN SHEET P-1.0; PLUMBING NOTE #5. ADD TO NOTE |
| | THE WORDS "SHOULD FIELD CONDITIONS WARRANT DESIGN |
| | CHANGE ' AREVION SHALL BE SUBMITTED TO THE WPB BUILDING |
| | DEPARTMENT FOR REVIEW FOR COMPLIANCE." WPB FBC SECTION |
| | 105 |
| | 10. RE: PLAN SHEET P-1.0; THE SCOPE OF WORK DOES NOT |
| | SEEM TO INDICATE ANY STORM DRAINAGE WORK. PLEASE REMOVE |
| | THE NOTE CONCERNING RAINWATER OR SHOW SUCH WORK ON THE |
| | PLANS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY |
| | REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED |
| | SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED "VOID". |
| | |
| | |