| Plan Review Notes For Permit 18090395 |
| Permit Number |
18090395 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2018-10-05 11:59:21 | 1ST REVIEW FBC-2017 MECHANICAL | | | PERMIT #18090395 | | | 10/5/18 | | | | | | CODES IN EFFECT: | | | | | | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 | | | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 | | | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION | | | 2017 | | | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION | | | 2017 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | | EDITION 2017 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) PROVIDE COOLING AND HEATING CALCULATIONS FOR THE NEW | | | DUCTLESS AC SYSTEM- SECTION C403.2.1 FBC-17 ENERGY | | | CONSERVATION. | | | | | | 2) M-1: PROVIDE A CHECK VALVE ON THE CONDENSATE LINE OF | | | THE FAN COIL UNIT- SECTION 307.2.4.1 FBC M. | | | | | | 3) M-1: INDICATE THE SIZE AND METAL GAUGE OF THE | | | CONDENSER STRAPS SHOWN IN THE MOUNTING DETAIL- SECTION | | | 107.2.1 WPB. | | | | | | 4) M-1: INDICATE HOW THE CU WILL PROTECTED AGAINST | | | VEHICULAR IMPACT- SECTION 303.4 FBC M. | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | | KEEP THEM WITH THE SUBMITTALS | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|