| 2018-12-12 14:37:42 | 3RD REVIEW FBC-2017 MECHANICAL |
| | PERMIT #18090371 |
| | 12/12/18 |
| | |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET M1: SIGNATURE OF CONTRACTOR OR QUALIFIER ON |
| | PLANS REQUIRED: SEE FLORIDA STATUTE 633.021, AND |
| | SECTION 107.2.1 FBC. WPB AMENDMENTS TO THE FBC: ALL |
| | INFORMATION, DRAWINGS, SPECIFICATIONS AND ACCOMPANYING |
| | DATA SHALL BEAR THE NAME AND SIGNATURE OF THE PERSON |
| | RESPONSIBLE FOR THE DESIGN. |
| | |
| | 2) M1: IT IS ACKNOWLEDGED THAT THE PARTITIONS LEAVE A |
| | 24" AIR SPACE FOR AIRFLOW, HOWEVER THE PLAN APPEARS TO |
| | SHOW FLEX DUCT RELOCATED OR EXTENDED TO AREA OF THE NEW |
| | ROOMS. PLEASE LABEL THE DUCTS ON THE PLAN AS NEW (N), |
| | EXISTING (E), OR RELOCATED (RE). |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS |
| | |