| 2018-10-02 10:35:20 | 1ST REVIEW: |
| | 2017 FLORIDA BUILDING CODE 6TH EDITION |
| | 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH |
| | EDITION |
| | 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH |
| | EDITION |
| | 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH |
| | EDITION |
| | |
| | PLUMBING COMMENTS: |
| | |
| | 1. INDICATE ON THE TYPE OF OCCUPANCY, THE OCCUPANT LOAD |
| | AND PROVIDE A PLUMBING FIXTURE COUNT BREAKDOWN IT SHALL |
| | COMPLY WITH FBC PL SEC 403.1 AND TABLE 403.1 IT MAY BE |
| | REQUIRED TO PROVIDE A WATER FOUNTAIN AND SERVICE SINK |
| | DEPENDING ON OCCUPANT LOAD. |
| | |
| | 2. THE RECONFIGURED BATHROOMS SHALL COMPLY WITH FBC ACC |
| | 2017 6TH EDITION SEC 213 |
| | PLEASE SHOW COMPLIANCE WITH THE FOLLOWING |
| | 604.2 LOCATION. THE WATER CLOSET SHALL BE POSITIONED |
| | WITH A WALL OR PARTITION TO THE REAR AND TO ONE SIDE. |
| | THE CENTERLINE OF THE WATER CLOSET SHALL BE 16 INCHES |
| | MINIMUM TO 18 INCHES MAXIMUM FROM THE SIDE WALL OR |
| | PARTITION |
| | 604.3.1 SIZE. CLEARANCE AROUND A WATER CLOSET SHALL BE |
| | 60 INCHES MINIMUM MEASURED PERPENDICULAR FROM THE SIDE |
| | WALL AND 56 INCHES MINIMUM MEASURED PERPENDICULAR FROM |
| | THE REAR WALL. |
| | 604.4 SEATS. THE SEAT HEIGHT OF A WATER CLOSET ABOVE |
| | THE FINISH FLOOR SHALL BE 17 INCHES MINIMUM AND 19 |
| | INCHES MAXIMUM MEASURED TO THE TOP OF THE SEAT. SEATS |
| | SHALL NOT BE SPRUNG TO RETURN TO A LIFTED POSITION. |
| | 604.5.1 SIDE WALL. THE SIDE WALL GRAB BAR SHALL BE 42 |
| | INCHES LONG MINIMUM, LOCATED 12 INCHES MAXIMUM FROM THE |
| | REAR WALL AND EXTENDING 54 INCHES MINIMUM FROM THE REAR |
| | WALL. |
| | 604.5.2 REAR WALL. THE REAR WALL GRAB BAR SHALL BE 36 |
| | INCHES LONG MINIMUM AND EXTEND FROM THE CENTERLINE OF |
| | THE WATER CLOSET 12 INCHES MINIMUM ON ONE SIDE AND 24 |
| | INCHES MINIMUM ON THE OTHER SIDE. |
| | 609.4 POSITION OF GRAB BARS. GRAB BARS SHALL BE |
| | INSTALLED IN A HORIZONTAL POSITION, 33 INCHES MINIMUM |
| | AND 36 INCHES MAXIMUM ABOVE THE FINISH FLOOR MEASURED |
| | TO THE TOP OF THE GRIPPING SURFACE |
| | 606.2 THE LAVATORY SHALL HAVE A CLEAR FLOOR SPACE. A |
| | CLEAR FLOOR SPACE COMPLYING WITH 305, POSITIONED FOR A |
| | FORWARD APPROACH, AND KNEE AND TOE CLEARANCE COMPLYING |
| | WITH 306 SHALL BE PROVIDED. |
| | 606.3 HEIGHT. LAVATORIES AND SINKS SHALL BE INSTALLED |
| | WITH THE FRONT OF THE HIGHER OF THE RIM OR COUNTER |
| | SURFACE 34 INCHES MAXIMUM ABOVE THE FINISH FLOOR OR |
| | GROUND. |
| | |
| | |
| | |
| | |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | |