| 2018-10-10 09:13:14 | 1ST REVIEW FBC-2017 MECHANICAL |
| | REVISION #18090360 |
| | MASTER # 18010368. |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET H1-101: ADDITIONAL UINFORMATION SHALL BE |
| | PROVIDED FOR THE NEW AIR-ROW/F18 FANS. THE NOTES ON THE |
| | PLAN INDICATE THE FANS ARE TO PAINTED HOWEVER THE |
| | APPLICATION OF PAINT MAY NOT BE APPROVED BY EITHER THE |
| | MANUFACTURER OR THE AGENCY THAT PROVIDED THE TESTING, |
| | LISTING AND LABELING OF THE PRODUCT. PLEASE SUBMIT |
| | PRODUCT DATA SHEETS FOR THE FANS AND FOR THE PAINT THAT |
| | WILL BE APPLIED TO THE FANS. THE ENGINEER OF RECORD |
| | SHALL PROVIDE SHOP DRAWING APPROVAL STAMPS ALL |
| | SUBMITTALS VERIFYING COMPLIANCE. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS |
| | |