| 2018-09-14 11:17:51 | PERMIT # 18090360 |
| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | |
| | APPROVED PROVISO: THE FOLLOWING ITEMS WILL BE REVIEWED |
| | AT TIME OF FIELD INSPECTION. FAILURE TO COMPLY WITH ALL |
| | FIRE CODE REQUIREMENTS WILL RESULT IN A FAILED |
| | INSPECTION UNTIL COMPLIANCE IS MET. |
| | |
| | 1) SHEET G.002: NORTH EXIT STATES - 3.6" WIDTH REQUIRED |
| | / 36" WIDTH PROVIDED ---- REMOVE DECIMAL TO CORRECT |
| | NUMBER |
| | |
| | 2) SHEET G.002: WEST EXIT STATES - 87.60" WIDTH |
| | REQUIRED / 52" WIDTH PROVIDED -----PLEASE CORRECT OR |
| | EXPLAIN DISCREPANCY IN REQUIREMENT. |
| | |
| | 3) PER NFPA 1: 13.3.2.6* EXTERIOR ROOFS, CANOPIES, |
| | PORTE-COCHERES, BALCONIES, DECKS, OR SIMILAR |
| | PROJECTIONS. IN BUILDINGS PROTECTED THROUGHOUT BY |
| | AUTOMATIC SPRINKLERS IN ACCORDANCE WITH |
| | NFPA 13, AUTOMATIC SPRINKLER PROTECTION SHALL BE |
| | PROVIDED FOR THE EXTERIOR SPACES IN ACCORDANCE WITH |
| | 13.3.2.6. |
| | 13.3.2.6.1: UNLESS THE REQUIREMENTS OF 13.3.2.6.2, |
| | 13.3.2.6.3, OR 13.3.2.6.4 ARE MET, SPRINKLERS SHALL BE |
| | INSTALLED UNDER EXTERIOR PROJECTIONS EXCEEDING 4 FT |
| | (1.2 M) IN WIDTH. [13:8.15.7.1] |
| | 13.3.2.6.2* SPRINKLERS SHALL BE PERMITTED TO BE OMITTED |
| | WHERE THE EXTERIOR PROJECTIONS ARE CONSTRUCTED WITH |
| | MATERIALS THAT ARE NONCOMBUSTIBLE, LIMITED-COMBUSTIBLE, |
| | OR FIRE RETARDANT? |
| | TREATED WOOD AS DEFINED IN NFPA 703, STANDARD FOR FIRE |
| | RETARDANT?TREATED WOOD AND FIRE-RETARDANT COATINGS FOR |
| | BUILDING MATERIALS. [13:8.15.7.2] |
| | |
| | |
| | SUE ELLEN CALDERON |
| | ASSISTANT FIRE MARSHAL |
| | [email protected] |
| | |