| Plan Review Notes For Permit 18090349 |
| Permit Number |
18090349 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2018-11-02 19:35:55 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | | | | 1. SHEET A-2.7, A-2.7D, PARKING SPACES WERE REMOVED | | | FROM THE WEST SIDE AND EAST CENTRAL SECTION OF THE | | | GARAGE. CONFIRM THIS IS CORRECT AND REVISE THE PARKING | | | SUMMARY PAGE, FBC 107. IF THIS IS CORRECT, CLARIFY USE | | | OF THE SPACE. | | | | | | 2. GA-2.7, SOUTH SIDE PARKING SPACES REMOVED, CLARIFY | | | USE OF SPACE. | | | | | | 3. GA-2.8, FBC 107, FBC B CHAPTER 10, PLEASE CONTACT ME | | | TO EXPLAIN THE CURB AND RAMP IT IS NOT CLEAR HOW ACCESS | | | TO THE STAIR IS AFFECTED. IT APPEARS THAT THIS | | | CONDITION OCCURS AT OTHER LOCATIONS. | | | | | | | | | |
|