| 2018-10-15 10:06:02 | BUILDING PLAN REVIEW |
| | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST |
| | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| | CHAPTER 1 ADMINISTRATION |
| | |
| | CHRISTOPHER S. THROOP, C.B.O. |
| | PLANS EXAMINER, PX3169 |
| | CONSTRUCTION SERVICES DIVISION |
| | TEL: 561-805-6726 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | 1ST REVIEW |
| | RESULTS: DENIED |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | |
| | 1. PROVIDE NOA FOR WINDOW MULLIONS. |
| | |
| | 2. THE FOLLOWING NOA'S SUBMITTED FOR REVIEW ARE NOT |
| | LISTED ON THE PLANS: |
| | 2A. WINDOW NOA 17-1212.21 SUBMITTED - NOA 17-1212.18 |
| | LISTED ON PLANS. |
| | 2B. RIDGE VENT NOA 17-1109.04 SUBMITTED - NOA |
| | 17-1107.04 LISTED ON PLANS. |
| | FBC 107.3.4 ? PROVIDE PRODUCT APPROVALS FOR THOSE |
| | PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED |
| | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. |
| | SPECIFICALLY, PROVIDE ROOFING AND WINDOW SUBMITTALS. |
| | |
| | 3. ENERGY SUBMITTAL R405 IS INCOMPLETE. SIGNATURE |
| | REQUIRED BY PREPARER, OWNER/AGENT. |
| | FBCE-101.5.1.1.2 SIMULATED PERFORMANCE ALTERNATIVE. |
| | AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R405 |
| | (GENERATED BY COMMISSION APPROVED SOFTWARE) SHALL BE |
| | SUBMITTED TO THE BUILDING OFFICIAL TO DEMONSTRATE CODE |
| | COMPLIANCE BY SECTION 405. |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY |
| | REVIEWED SHEETS DETACHED AND MARK VOID. |
| | |
| | |