| 2018-10-26 15:23:48 | ****CORRECTIONS**** |
| | W.P.B. PERMIT: 18090262 |
| | REVIEWED: OCTOBER 25, 2018 |
| | |
| | DYLAN BATTLES |
| | BUILDING PLANS EXAMINER I |
| | [email protected] |
| | 561-805-6718 |
| | |
| | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) |
| | FBC AMENDED = FLORIDA BUILDING CODE,6TH EDITION (2017) |
| | FBC B = FBC BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC ENERGY = FBC ENERGY CONSERVATION |
| | |
| | 1. [FBC AMENDED 109.3]HOW WAS VALUATION OF PROJECT |
| | DETERMINED? |
| | PLEASE PROVIDE COST EVALUATION AND THE MEANS BY WHICH |
| | IT WAS CALCULATED. ITEMS THAT WILL BE PERMITTED |
| | COMPLETELY SEPARATE AND THE VALUE NOT INCLUDED IN MAIN |
| | PERMIT/NO FEE SUB PERMITS CAN BE DEDUCTED FROM VALUE, |
| | FOR EXAMPLE FIRE ALARM AND SPRINKLER, BUT INCLUDE THESE |
| | DEDUCTIONS AS LINE ITEMS DEDUCTED FROM THE TOTAL |
| | EVALUATION FOR REFERENCE. |
| | [FBC AMENDED 109.3]BUILDING PERMIT VALUATIONS. IF, IN |
| | THE OPINION OF THE BUILDING OFFICIAL, THE CLAIMED |
| | VALUATION OF BUILDING, ALTERATION, STRUCTURE, |
| | ELECTRICAL, GAS, MECHANICAL OR PLUMBING SYSTEMS APPEARS |
| | TO BE UNDERESTIMATED ON THE APPLICATION, THE PERMIT |
| | SHALL BE DENIED, UNLESS THE APPLICANT CAN SHOW |
| | DETAILED, QUANTITY ESTIMATES, AND/OR BONA FIDE SIGNED |
| | CONTRACTS (EXCLUDING LAND VALUE) TO MEET THE APPROVAL |
| | OF THE BUILDING OFFICIAL. FOR PERMITTING PURPOSES, |
| | VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL |
| | REPLACEMENT VALUE TO INCLUDE STRUCTURAL, ELECTRIC, |
| | PLUMBING, MECHANICAL, INTERIOR FINISH, RELATIVE SITE |
| | WORK, ARCHITECTURAL AND DESIGN FEES, MARKETING COSTS, |
| | OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE. |
| | VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED |
| | DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES |
| | (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY |
| | INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT |
| | VALUATION SHALL BE SET BY THE BUILDING OFFICIAL. |
| | |
| | 2. ART IN PUBLIC PLACES |
| | THE CITY OF WEST PALM BEACH ART IN PUBLIC PLACES |
| | ORDINANCE REQUIREMENT THAT APPLIES TO ANY REMODEL OR |
| | NEW CONSTRUCTION PROJECT FOR WHICH THE PERMIT |
| | APPLICATION WAS SUBMITTED AFTER 6/29/14, AND THE TOTAL |
| | PROJECT CONSTRUCTION COSTS ARE EQUAL TO OR GREATER THAN |
| | $750,000 WILL NEED TO COMPLY WITH THIS ORDINANCE. |
| | PER CITY OF WEST PALM BEACH ORDINANCE NO. 4504-14, AND |
| | CITY OF WEST PALM BEACH CODE OF ORDINANCES, ARTICLE V, |
| | ART IN PUBLIC PLACES, SECTION 78-123(A) AND SECTION |
| | 78-126(A), THE ART ASSESSMENT IS 1% OF THE TOTAL |
| | PROJECT CONSTRUCTION COST. |
| | PER CITY OF WEST PALM BEACH CODE OF ORDINANCES, ARTICLE |
| | V, ART IN PUBLIC PLACES, SECTION 78-122, RENOVATION AND |
| | NEW CONSTRUCTION PROJECTS ARE ASSESSED CUMULATIVELY, SO |
| | THE ART ASSESSMENT WILL BE APPLICABLE TO ALL FUTURE |
| | PROJECTS. |
| | SEC. 78-129. - PUBLIC ART ASSESSMENT FOR PRIVATE |
| | DEVELOPMENT. |
| | (A) APPLICABILITY. THE PROVISIONS OF THIS ARTICLE AND |
| | THE PUBLIC ART ASSESSMENT SECTION SHALL APPLY TO ALL |
| | PRIVATE DEVELOPMENT PROJECTS, INCLUDING NEW |
| | CONSTRUCTION, OR THE RENOVATION OR IMPROVEMENT OF AN |
| | EXISTING BUILDING, WHERE TOTAL CONSTRUCTION COSTS ARE |
| | EQUAL TO OR GREATER THAN $750,000.00. ALL BUILDINGS |
| | WITHIN NEW PLANNED DEVELOPMENTS SHALL BE ASSESSED |
| | CUMULATIVELY TOWARDS THIS ART IN PUBLIC PLACES |
| | REQUIREMENT, EVEN IF THE BUILDINGS ARE PERMITTED |
| | SEPARATELY OR DEVELOPED IN PHASES. THE PROVISIONS OF |
| | THIS SECTION APPLY TO NEW DEVELOPMENT OR NEW |
| | CONSTRUCTION WITHIN EXISTING PLANNED DEVELOPMENTS. |
| | FOR CONTACT INFORMATION PLEASE CONTACT: |
| | MS. SYBILLE WELTER ART IN PUBLIC PLACES COORDINATOR |
| | 822-1515 E-MAIL: [email protected] |
| | |
| | 3. [FBC 107.3.5.3]PROVIDE SEDIMENT CONTROL PLAN TO KEEP |
| | CONSTRUCTION DEBRIS FROM ENTERING ADJACENT PROPERTIES |
| | AND STORM DRAINS DURING CONSTRUCTION. |
| | |
| | 4. [FBC 107.5][FBC 110.9]PROVIDE SITE DRAINAGE PLAN. |
| | NO CIVIL PLANS ARE SUBMITTED. PLEASE PROVIDE CIVIL |
| | PLANS TO RESPONSE TO SITE DRAINAGE AND SEDIMENT |
| | CONTROL. |
| | PROVIDE FULL GEO-TECHNICAL REPORT WITH FOUNDATION |
| | RECOMMENDATIONS. UPLOAD TO SUPPORTING FILE IN PROJECT |
| | DOX |
| | |
| | 5. [FBC AMENDED 107.3.5]PROVIDE BASE ELEVATION IN |
| | NAVD88 FOR THE LOWEST POINT IN THE PARKING GARAGE. |
| | |
| | 6. [FBC 406.4.1]WHAT IS THE MINIMUM HEIGHT CLEARANCE |
| | FOR THE STRUCTURE? |
| | ADD DIMENSIONS TO SECTIONS TO SHOW HOW 7' CLEARANCE IS |
| | PROVIDED THROUGHOUT LEVELS AND 8'-2" IS PROVIDED FOR |
| | VAN ACCESSIBLE SPACES. |
| | |
| | 7. [FBC 406.4.1]CLEAR HEIGHT. |
| | THE CLEAR HEIGHT OF EACH FLOOR LEVEL IN VEHICLE AND |
| | PEDESTRIAN TRAFFIC AREAS SHALL BE NOT LESS THAN 7 FEET |
| | (2134 MM). VEHICLE AND PEDESTRIAN AREAS ACCOMMODATING |
| | VAN-ACCESSIBLE PARKING SHALL COMPLY WITH THE FLORIDA |
| | BUILDING CODE, ACCESSIBILITY. |
| | |
| | SHEET GG102 STATES THE NUMBER OF SPOTS PROVIDED. ADD TO |
| | THE TABLE THE NUMBER OF SPOTS REQUIRED. |
| | SHEET GG102 DOESN'T STATE THE AMOUNT OF REQUIRED ADA |
| | SPOTS, BUT BASED ON WHAT IS PROVIDED THERE SHOULD BE |
| | TWO VAN ACCESSIBLE SPACES. |
| | |
| | PLEASE INDICATE WHICH SPACES ARE VAN ACCESSIBLE AND |
| | FOLLOW THE GUIDELINES FOR SIGNAGE TO INDICATE HEIGHT. |
| | |
| | ADVISORY 502.5 VERTICAL CLEARANCE. SIGNS PROVIDED AT |
| | ENTRANCES TO PARKING FACILITIES INFORMING DRIVERS OF |
| | CLEARANCES AND THE LOCATION OF VAN ACCESSIBLE PARKING |
| | SPACES CAN PROVIDE USEFUL CUSTOMER ASSISTANCE. |
| | |
| | FLORIDA LAW, S.553.511, F.S., REQUIRES SIGNS BE POSTED |
| | THAT WILL WARN HANDICAPPED-EQUIPPED VAN OPERATORS OF |
| | HEIGHT LIMITATIONS SO THEY WILL NOT PASS BEYOND A POINT |
| | WHERE THE VAN CANNOT BE MANEUVERED. |
| | |
| | [FBC A208.2.4]VAN PARKING SPACES. |
| | WHERE VAN PARKING IS PROVIDED PURSUANT TO SECTION |
| | 502.2, FOR EVERY SIX OR FRACTION OF SIX PARKING SPACES |
| | REQUIRED BY 208.2 TO COMPLY WITH 502, AT LEAST ONE |
| | SHALL BE A VAN PARKING SPACE COMPLYING WITH 502 |
| | |
| | 8. [FBC 1015]SHEET GA302 HAS NOTE THAT CRASH CABLES TO |
| | RESTRICT SPHERE 8" SPERE UP TO 42. PLEASE ADJUST NOTE |
| | TO CLARIFY THAT THE CRASH CABLES FUNCTION AS BOTH |
| | VEHICLE BARRIER AND GUARD TO 42". ALSO, IN RESPONSE |
| | SHEET EITHER STATE THE EXCEPTION TO ALLOW 8" FROM 34 TO |
| | 42, OR ADJUST NOTE TO COMPLY WITH 1016. I SEE EXCEPTION |
| | FOR 4 3/8" SPHERE FROM 36-42, BUT NOT 8". EVEN THOUGH |
| | DRAWING APPEARS TO COMPLY ALL THE WAY UP PLEASE ADJUST |
| | NOTE TO MATCH. |
| | |
| | 9. [FBC 1607.8.3]PROVIDE ENGINEERING TO SHOW HOW THE |
| | VEHICLE BARRIER IS RATED TO RESIST 6000 LBS AS |
| | REQUIRED. ALSO, PROVIDE SPECIFICATIONS THAT SHOW THIS |
| | PRODUCTS USE FOR PARKING GARAGE BARRIER FOR RAISED |
| | PLATFORM APPLICATIONS. |
| | |
| | 10. [FBC 406.5.2]SHEET GA201 AND GA 202. PLEASE PROVIDE |
| | A CLEARER DEPICTION OF OPENINGS THAT ARE USED TO |
| | DETERMINE TO AMOUNT OF OPENINGS PER TIER. PROVIDING |
| | ELEVATIONS WITHOUT THE SCREENING THAT WILL BE UNDER |
| | SEPARATE PERMIT WOULD HELP TO SEE HOW THE PERIMETER |
| | WALL PROVIDES OPENING. |
| | THE CALCULATIONS SHOULE BE PER TIER, BUT THE PROVIDED |
| | ARE BY LEVELS AND PERIMETER DISTANCES VARY. |
| | THE GROUND LEVEL WALL AREA MAKES SENSE SINCE 10'-6" |
| | (HEIGHT) X 641'-8" PERIMETER = 6,737 SQ. FT, BUT THEN |
| | THE PROVIDED LENGHT EXCEEDS THE PERIMETER. |
| | VP WEST ELEVATION SEEMS TO BE A GOOD INDICATER OF TIER |
| | HEIGHTS AND THERE SHOUD BE 3 TIERS SHOWN: |
| | TIER 1 FROM -10'-4" TO 0'-0" WITH 641'-8" PERIMETER |
| | TIER 2 FROM 0'-0" TO 10'-10" WITH 641'-8" PERIMETER |
| | TIER 3 FROM 10'-10" TO 21'-4" WITH 641'-8" PERIMETER |
| | SHOW TOAL AREA OF WALL, REQ'D AREA, AREA PROVIDED |
| | WITHOUT SCREENING (100% OPEN), OPENING AREA WITH |
| | SCREENING ADJUSTMENT FACTOR(61% OPEN) AND TOTAL OPENING |
| | PROVIDED. |
| | IF ELEVATIONS ARE SHOW WITHOUT THE SCREENING IT WILL |
| | ALSO BE EASIER TO SEE HOW OPENING ARE PROVIDED ALONG |
| | 40% OF THE PERIMETER. USE 641'-8" X .40 = 257' MINIMUM |
| | PER TIER AS YOU DID FOR GROUND LEVEL. |
| | |
| | 11. [FBC 406.5.2]ADD CALCULATION TO SHOW 20% OPENINGS |
| | EVENLY DISTRIBUTED ON INTERIOR WALL PER TIER. |
| | |
| | 12. [FBC 107.3.4.1]A CONSTRUCTION GUARDRAIL DETAIL, |
| | PREPARED BY A DESIGN PROFESSIONAL LICENSED UNDER FS471 |
| | OR FS481, IS REQUIRED TO BE SUBMITTED, REVIEWED AND |
| | ISSUED BY THE CITY OF WEST PALM BEACH, OR INDICATE THAT |
| | IT WILL BE DEFERRED. |
| | *SUBJECT TO THE INSPECTOR?S DISCRETION, THIS MAY BE |
| | ACCEPTED IN THE FIELD AT TIME OF INSPECTION. |
| | |
| | PROVISOS: |
| | PROVIDE SEPARATE PERMIT FOR STRUCTURAL ALUMINUM PANEL |
| | SYSTEM. |
| | SEPARATE PERMIT FOR ROOF TOP CANOPIES. |
| | |
| | NOTE: |
| | -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW |
| | EACH COMMENT IS BEING ADDRESSED. |
| | -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW |
| | OF MATERIALS REQUESTED. |
| | -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS |
| | OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS) |
| | SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT |
| | DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER |
| | SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID" |
| | OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS |
| | APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE |
| | NEED "VOID", RENDERING THEM NOT USABLE. |
| | |