| 2019-06-17 10:11:04 | 2ND REVIEW FBC-2017 MECHANICAL |
| | PERMIT #18090217 |
| | 9/27/18 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED |
| | |
| | THE RESULTS FROM THE 1ST REVIEW COMMENTS ARE INDICATED |
| | BELOW. |
| | |
| | 1) OK |
| | |
| | 2) OK |
| | |
| | 3) STILL EXISTS- GENERAL SCOPE OF WORK NOTES ON NEW M-1 |
| | SHEET INCLUDES THE PAINT SPRAY BOOTH. (PLEASE NOTE THAT |
| | A SEPARATE PERMIT IS REQUIRED FOR THE SPRAY BOOTH SO IT |
| | WILL NOT BE REVIEWED AT THIS TIME. THE CONTRACTOR OF |
| | RECORD SHALL SUBMIT A SEPARATE APPLICATION AND TWO SETS |
| | OF PLANS AND SPECIFICATIONS FOR REVIEW.) |
| | |
| | 4) STILL EXISTS- NO CONTRACT OR DOCUMENTATION SUBMITTED |
| | TO VERIFY COSTS. (THE $50,000 JOB VALUE ON THE PERMIT |
| | APPLICATION APPEARS LOW FOR THE SCOPE OF THE PROPOSED |
| | PROJECT. PLEASE SUBMIT DETAILED ESTIMATES AND/OR BONA |
| | FIDE CONTRACTS FOR ALL PHASES OF THE PROJECT INCLUDING |
| | STRUCTURAL, ELECTRIC, MECHANICALL, PLUMBING, INTERIOR |
| | AND EXTERIOR FINISH, SITE WORK, DESIGN FEES, AND OVER |
| | HEAD AND PROFIT. PLEASE NOTE VALUE IS BASED ON LABOR, |
| | MATERIALS, AND EQUIPMENT.) |
| | |
| | 5) STILL EXISTS- NEW SHEETS A-1 & A-2 SHOW THE 15000 |
| | CFM COLLECTOR LOCATED 8'4" TO THE ROLL UP DOOR. WHETHER |
| | NEW OR EXISTING, PROVIDE DOCUMENTATION INDICATING THE |
| | DOOR IS IMPACT RESISTANT AND CAPABLE OF RESISTING THE |
| | CURRENT WINDSPEEDS AND PRESSURES PER THE ASCE 7-10- SEE |
| | SECTION 1609 FBC B. (SHEET A2: THE PLAN DOES NOT |
| | CLEARLY SHOW THAT THE LOCATIONS OF THE NEW COLLECTORS |
| | ARE IN COMPLIANCE WITH SECTION 511.1 FBC M WHICH |
| | REQUIRES A MINIMUM 10' CLEARANCE TO COMBUSTIBLE |
| | CONSTRUCTION AND ALSO UNPROTECTED OPENINGS INTO THE |
| | BUILDINGS.) |
| | |
| | 6) STILL EXISTS- BASED ON COMMENT 35 ABOVE, A METAL |
| | VENT PIPE MAY BE REQUIRED TO BE LOCATED ABOVE THE |
| | HIGHEST ROOF LEVEL WITH A DISTANCE OF 30'- SECTION |
| | 511.1 FBC M. (A-2, M3, & M4: THE COLLECTOR DRAWINGS ARE |
| | INCONSISTENT ON HOW THE COLLECTION, EXHAUST, AND RETURN |
| | SYSTEMS ARE FUNCTIONING. THERE ARE NO EXHAUST |
| | DISCHARGES SHOWN, OR LABELED FOR THE COLLECTORS, |
| | HOWEVER THERE APPEARS TO BE A RETURN AIR DUCT INTO THE |
| | BUILDING AS SHOWN ON SHEETS A2 & M3. PLEASE VERIFY |
| | COMPLIANCE WITH SECTION 511.1.3). |
| | |
| | 7) STILL EXISTS- SPACING OF HANGERS AND ATTRACHMENT TO |
| | THE STRUCTURE NOT PROVIDED (PROVIDE TYPICAL DETAILS FOR |
| | DUCT HANGING AND SUPPORT INCLUDING SPACING OF THE |
| | HANGERS,). |
| | |
| | 8) STILL EXISTS- NOT PROVIDED SHEETS S1 & M3: THE |
| | STRUCTURAL ENGINEER OF RECORD MUST PROVIDE COMPLETE |
| | DETAILS FOR CONSTUCTION OF THE STEEL FRAIMING AND |
| | SUPPORT BASES FOR THE COLLECTORS INCLUDING WIND LOAD |
| | ENGINEERING FOR ATTACHING THE COLLECTORS TO THE |
| | SUPPORTS AND THE SUPPORTS TO THE FOUNDATIONS- SECTION |
| | 301.15 FBC M.). |
| | |
| | 9) STILL EXISTS- NOT PROVIDED (A FLORIDA LICENSED |
| | MECHANICAL CONTRACTOR SHALL SUBMIT A SUB-PERMIT |
| | APPLICATION FOR INSTALLATION OF THE DUCT COLLECTORS AND |
| | DUCT SYSTEMS- SECTION 489.113 (I) FS.). |
| | |
| | 10) NEW COMMENT: SHOW THE LOCATION OF THE REQUIRED |
| | EXPLOSION RELIEF VENT- SECTION 511.1.5 FBC M. |
| | |
| | 11) NEW COMMENT, SHEET M-3: MUCH OF THE PRINT IN THE |
| | MAXI-FILTER DETAILS IS TOO FAINT TO READ AND SCAN INTO |
| | THE CITY'S COMPUTER FILES- SECTION 107.2.1 WPB. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL PLANS EXAMINER |