2018-09-20 06:03:35SERVICE CONDUCTORS AND FEEDERS TO BOTH PANELS MUST BE
 3/0 WIRE NOT 2/0. REDLINED ON PLAN. SEE NEC
 310.15(B)(7) # 1&2