| Notes |
| Date |
Text |
| 2018-09-18 06:22:46 | APPLICATION SAYS 150AMP ATS AND PANEL. PLAN SHOWS | | | 200AMP ATS AND PANEL. WIRE ON PLAN ONLY RATED FOR | | | 150AMP. APPROVED PROVISIONALLY WITH REDLINED DRAWINGS | | | BY MYSELF FOR 150AMP PANEL AND ATS ONLY. |
|