Review Stop E
Sequence Number 1
Notes
Date Text
2018-09-18 06:22:46APPLICATION SAYS 150AMP ATS AND PANEL. PLAN SHOWS
 200AMP ATS AND PANEL. WIRE ON PLAN ONLY RATED FOR
 150AMP. APPROVED PROVISIONALLY WITH REDLINED DRAWINGS
 BY MYSELF FOR 150AMP PANEL AND ATS ONLY.