2018-10-02 12:33:26CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 1ST REVIEW:
 PLUMBING COMMENTS: DENIED
  
 1. RE: SUBMITTED LETTER FROM CLUB PILATES REQUESTING
 APPROVAL FOR ONE (1) SINGLE UNISEX BATHROOM; MEN'S AND
 WOMEN'S SEPERATE FACILITIES ARE REQUIRED BASED UPON FBC
 PLUMBING 403.1 AND SHALL COMPLY WITH FBC ACC 604 AND
 606
 A. THE TENANT'S LETTER STATING THE OCCUPANCY WOULD BE
 LESS THAN 15 DOES NOT CHANGE THE FACT THAT THE NUMBER
 OF OCCUPANTS (DEEMED 18) SHALL BE DETERMINED BY THE
 FLORIDA BUILDING CODE, BUILDING PER FBC PLUMBING 403.1,
 TABLE 403.1
 B. THE ONLY EXCEPTION FOR APPROVAL FOR A REDUCED
 OCCUPANCY LOAD IS NOTED IN FBC BUILDING 1004.1.2 AND
 NEEDS TO BE ADDRESSED TO THE BUILDING OFFICIAL FOR
 APPROVAL.
 2. A SERVICE SINK IS REQUIRED PER PER FBC PLUMBING
 403.1, TABLE 403.1
 A. THE TENANT'S LETTER STATING THE OCCUPANCY WOULD BE
 LESS THAN 15 DOES NOT CHANGE THE FACT THAT THE NUMBER
 OF OCCUPANTS (DEEMED 18) SHALL BE DETERMINED BY THE
 FLORIDA BUILDING CODE, BUILDING PER FBC PLUMBING 403.1,
 TABLE 403.1
 B. THE ONLY EXCEPTION FOR APPROVAL FOR A REDUCED
 OCCUPANCY LOAD IS NOTED IN FBC BUILDING 1004.1.2 AND
 NEEDS TO BE ADDRESSED TO THE BUILDING OFFICIAL FOR
 APPROVAL.
 3. RE: PLAN SHEET P-2; WATER ISOMETRIC. SHOW BRANCH TO
 TRAP PRIMER NOTED ON "FLOOR DRAIN & TRAP PRIMER"
 DETAIL. WPB FBC 107.2.1
 4. RE: PLAN SHEET P-2; WATER ISOMETRIC. PROVIDE
 INFORMATION FOR BACKFLOW PREVENTOR SHOWN ON SUPPLY TO
 WATER FILTER. INCLUDE TYPE, MODEL NUMBER AND ASSE
 STANDARD FOR COMPLIANCE. IF THERE IS A RELIEF OPENING
 ON THE DEVICE THEN PROVIDE DETAILS FOR DISCHARGE
 PIPING. WPB FBC 107.2.1
 5. RE: PLAN SHEET P-2; "HOT WATER LIMITING DEVICE"
 DETAIL. WHERE DOES HOT WATER CONTINUE TO AFTER
 SERVICING THE LAVATORY. PLEASE CLARIFY. WPB FBC 107.2.1
 6. VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS
 LOW. PROVIDE DETAILED, QUANTITY ESTIMATES, AND/OR BONA
 FIDE SIGNED CONTRACTS WITH SCOPE AND VALUE OF WORK, TO
 INCLUDE ALL MATERIALS AND LABOR. THIS IS FOR TOTAL
 PROJECT, NOT JUST PLUMBING. WPB FBC 109.3
  
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED "VOID".
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715