| 2018-10-02 12:33:26 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION |
| | FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION |
| | FAC= FLORIDA ADMINISTRATIVE CODE |
| | FS = FLORIDA STATUTES |
| | |
| | 1ST REVIEW: |
| | PLUMBING COMMENTS: DENIED |
| | |
| | 1. RE: SUBMITTED LETTER FROM CLUB PILATES REQUESTING |
| | APPROVAL FOR ONE (1) SINGLE UNISEX BATHROOM; MEN'S AND |
| | WOMEN'S SEPERATE FACILITIES ARE REQUIRED BASED UPON FBC |
| | PLUMBING 403.1 AND SHALL COMPLY WITH FBC ACC 604 AND |
| | 606 |
| | A. THE TENANT'S LETTER STATING THE OCCUPANCY WOULD BE |
| | LESS THAN 15 DOES NOT CHANGE THE FACT THAT THE NUMBER |
| | OF OCCUPANTS (DEEMED 18) SHALL BE DETERMINED BY THE |
| | FLORIDA BUILDING CODE, BUILDING PER FBC PLUMBING 403.1, |
| | TABLE 403.1 |
| | B. THE ONLY EXCEPTION FOR APPROVAL FOR A REDUCED |
| | OCCUPANCY LOAD IS NOTED IN FBC BUILDING 1004.1.2 AND |
| | NEEDS TO BE ADDRESSED TO THE BUILDING OFFICIAL FOR |
| | APPROVAL. |
| | 2. A SERVICE SINK IS REQUIRED PER PER FBC PLUMBING |
| | 403.1, TABLE 403.1 |
| | A. THE TENANT'S LETTER STATING THE OCCUPANCY WOULD BE |
| | LESS THAN 15 DOES NOT CHANGE THE FACT THAT THE NUMBER |
| | OF OCCUPANTS (DEEMED 18) SHALL BE DETERMINED BY THE |
| | FLORIDA BUILDING CODE, BUILDING PER FBC PLUMBING 403.1, |
| | TABLE 403.1 |
| | B. THE ONLY EXCEPTION FOR APPROVAL FOR A REDUCED |
| | OCCUPANCY LOAD IS NOTED IN FBC BUILDING 1004.1.2 AND |
| | NEEDS TO BE ADDRESSED TO THE BUILDING OFFICIAL FOR |
| | APPROVAL. |
| | 3. RE: PLAN SHEET P-2; WATER ISOMETRIC. SHOW BRANCH TO |
| | TRAP PRIMER NOTED ON "FLOOR DRAIN & TRAP PRIMER" |
| | DETAIL. WPB FBC 107.2.1 |
| | 4. RE: PLAN SHEET P-2; WATER ISOMETRIC. PROVIDE |
| | INFORMATION FOR BACKFLOW PREVENTOR SHOWN ON SUPPLY TO |
| | WATER FILTER. INCLUDE TYPE, MODEL NUMBER AND ASSE |
| | STANDARD FOR COMPLIANCE. IF THERE IS A RELIEF OPENING |
| | ON THE DEVICE THEN PROVIDE DETAILS FOR DISCHARGE |
| | PIPING. WPB FBC 107.2.1 |
| | 5. RE: PLAN SHEET P-2; "HOT WATER LIMITING DEVICE" |
| | DETAIL. WHERE DOES HOT WATER CONTINUE TO AFTER |
| | SERVICING THE LAVATORY. PLEASE CLARIFY. WPB FBC 107.2.1 |
| | 6. VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS |
| | LOW. PROVIDE DETAILED, QUANTITY ESTIMATES, AND/OR BONA |
| | FIDE SIGNED CONTRACTS WITH SCOPE AND VALUE OF WORK, TO |
| | INCLUDE ALL MATERIALS AND LABOR. THIS IS FOR TOTAL |
| | PROJECT, NOT JUST PLUMBING. WPB FBC 109.3 |
| | |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY |
| | REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED |
| | SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED "VOID". |
| | |
| | |
| | JERALD SMITH |
| | PLUMBING PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | EMAIL [email protected] |
| | PHONE 561-805-6715 |