2018-09-14 09:14:001) SUBMIT FACTORY SIZING CALCULATIONS FROM SCHIER FOR
 THE INTERCEPTOR. THE SIZING CALCULATIONS ON THE PLANS
 ARE VAGUE.2017 FBC- PLUMBING SEC. 1003.2.
 2) A SAMPLING PORT IS REQUIRED ON THE DISCHARGE SIDE OF
 THE GREASE INTERCEPTOR. A 4 INCH TWO WAY CLEANOUT WILL
 SUFFICE. ALTHOUGH IT IS IN THE NOTES ON THE PLANS,
 PLEASE SHOW THE CLEANOUTS ON THE INLET AND OUTLET LINES
 ON THE GREASE INTERCEPTOR.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW