| Plan Review Notes For Permit 18090126 |
| Permit Number |
18090126 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2018-09-14 09:14:00 | 1) SUBMIT FACTORY SIZING CALCULATIONS FROM SCHIER FOR | | | THE INTERCEPTOR. THE SIZING CALCULATIONS ON THE PLANS | | | ARE VAGUE.2017 FBC- PLUMBING SEC. 1003.2. | | | 2) A SAMPLING PORT IS REQUIRED ON THE DISCHARGE SIDE OF | | | THE GREASE INTERCEPTOR. A 4 INCH TWO WAY CLEANOUT WILL | | | SUFFICE. ALTHOUGH IT IS IN THE NOTES ON THE PLANS, | | | PLEASE SHOW THE CLEANOUTS ON THE INLET AND OUTLET LINES | | | ON THE GREASE INTERCEPTOR. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | | | | | | | |
|