| 2018-10-17 11:58:06 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT #18090121 |
| | 10/17/18 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET M2.1: SHOW THE LOCATIONS OF THE REQUIRED DUCT |
| | SMOKE DETECTORS IN THE SUPPLY AIR SYSTEMS OF RTU- 1 & 2 |
| | PER SECTION 606.2.1 FBC M, AND PROVIDE A SEQUENCE OF |
| | OPERATION FOR FAN SHUTDOWN AND HOW THE DEVICES WILL BE |
| | SUPERVISED- SECTIONS 606.4 & 606.4.1. |
| | |
| | 2) M2.1: THE PLAN DOES NOT CLEARLY SHOW THE LOCATION OF |
| | THE TOILET ROOM EXHAUST TERMINATION- SECTION 501.3.1 |
| | FBC M. |
| | |
| | 3) M2.1 & M2.2: PROVISDE CONDENSATE DISPOSAL PLANS FOR |
| | THE RTU'S AND THE AHU- SECTION 307 FBC M. |
| | |
| | 4) M2.2 & M6.1: PROVIDE COMPLETE WINDLOAD ENGINEERING |
| | FOR INSTALLATION OF THE RTU'S AND CURBS, AND FOR THE |
| | CONDENSER STAND ON THE ROOF- SECTION 301.15 FBC M. |
| | PLEASE INCLUDE THE DESIGN CRITERIA AS OUTLINED IN |
| | SECTION 1609 FBC M, AND SUBMIT THE NOA FOR THE STAND. |
| | |
| | 5) REFER TO SECTION 306.5 FBC M AND CLARIFY HOW ACCESS |
| | TO THE ROOFTOP EQUIPMENT IS BEING PROVIDED. |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS |
| | |