| Plan Review Notes For Permit 18090102 |
| Permit Number |
18090102 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2018-09-25 15:25:34 | MECHANICAL PROVISOS: | | | REVISION #18090102 | | | MASTER #18020252 | | | 10/4/18 | | | | | | 1) SHEET M103, 3RD-9TH FLOORS: PROVIDE FIRE DAMPERS FOR | | | THE 12X12 AND !2X10 SUPPLY DUCTS PENETRATING THE | | | FIRE-RATED CORRIDOR WALLS- SECTION 607.5.3 FBC M. | | | | | | 2) ACCORDING TO THE NARRATIVE SUBMITTED WITH THE | | | REVISED PLANS, THERE ARE CHANGES TO THE DUCTWORK ON THE | | | 10TH FLOOR (SHEET M104), HOWEVER THE REVISED PLAN WAS | | | NOT UPLOADED FOR REVIEW. PLEASE PROVIDE THE PLAN. | | | | | | 3) M106: THERE IS NO CODE REQUIREMENT FOR SMOKE | | | DETECTORS TO BE LOCATED BY THE STAIR PRESSURIZATION | | | FANS IN THE INTERIOR EXIT STAIRWAYS. PLEASE PROVIDE A | | | RATIONAL ANALYSIS TO CLARIFY THE FUNCTION AND CONTROLS | | | OPERATION OF THE DEVICES, AND HOW THEY WILL BE | | | SUPERVISED. | | | | | | 4) M106: PROVIDE FIRE-RATED DUCTS FOR THE ELEVATOR | | | PRESSURIZATION FAN SYSTEMS- SECTION 909.21.3 FBC B. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|