Plan Review Notes
Plan Review Notes For Permit 18090049
Permit Number 18090049
Review Stop B
Sequence Number 1
Notes
Date Text
2018-10-03 19:01:38PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SPECIFY THE WIND SPEED AND EXPOSURE CATEGORY AND
 PROVIDE THE DESIGN PRESSURES FOR THE WINDOWS AND
 SLIDING GLASS DOOR. FBC 1603.1.4
  
 2) INDICATE THE WINDOW SIZE AND PRESSURES BY CIRCLING
 THE APPROPRIATE ONES IN THE CHARTS ON SHEET 2 OF THE
 PRODUCT APPROVAL (NOA NO. 17-1018.08). FBC 107.2.1
  
 3) THE PHOTO THAT WAS SUBMITTED SHOWS TWO SINGLE HUNG
 WINDOWS JOINED TOGETHER WITH A MULLION. SUBMIT TWO SETS
 OF PRODUCT APPROVALS FOR THE STRUCTURAL MULLION. FAC
 RULE 612G20
  
 4) INDICATE THE DESIGN PRESSURES FOR THE SLIDING GLASS
 DOOR PANELS BY CIRCLING THE APPROPRIATE ITEMS ON THE
 CHART ON SHEET 13 AND THE DESIGN LOAD CAPACITY OF THE
 ANCHORS THAT WILL BE USED FROM THE CHART ON SHEET 15 OF
 THE PRODUCT APPROVAL (NOA NO. 17-1011.18).
  
 5) ALL FRAMING IS REQUIRED TO BE OF NONCOMBUSTIBLE
 MATERIALS. SPECIFY THE FRAMING MATERIAL TO BE USED ON
 THE PLANS. FBC 602.2
  
  
  
  
  