| 2018-10-11 13:51:37 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. ALL BRANCH CIRCUITS THAT SUPPLY 120-VOLT, |
| | SINGLE-PHASE, 15- AND 20-AMPERE OUTLETS INSTALLED IN |
| | KITCHENS, FAMILY ROOMS, DINING ROOMS, LIVING ROOMS, |
| | PARLORS, LIBRARIES, DENS, BEDROOMS, SUN-ROOMS, |
| | RECREATIONS ROOMS, CLOSETS, HALLWAYS, LAUNDRY AREAS AND |
| | SIMILAR ROOMS OR AREAS SHALL BE AFCI PROTECTED. PROVIDE |
| | CORRECTION. NEC 210.12; FBC RE E3902.16 |
| | 2. PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE |
| | EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE |
| | IS ADEQUATE. NEC 215.2, 220, 408.30; FBC RE E3602.2 |
| | 3. FEEDERS THAT SUPPLY A SEPARATE STRUCTURE REQUIRE A |
| | DISCONNECTING MEANS AT THE BUILDING OR SEPARATE |
| | STRUCTURE SUPPLIED. PROVIDE EITHER A MAIN DISCONNECT OR |
| | MAIN BREAKER AT THE PANEL FOR 50 AMP SUB-PANEL. NEC |
| | 225.31, 225.32 |
| | 4. PROVIDE GROUNDING ELECTRODE SYSTEM AS REQUIRED FOR A |
| | BUILDING OR STRUCTURE SUPPLIED BY A FEEDER OR BRANCH |
| | CIRCUIT. NEC 250.32; FBC RE3607.3 |
| | 5. CONDUIT/FEEDER FROM MAIN PANEL TO SUB-PANEL MUST |
| | INCLUDE AN EQUIPMENT GROUNDING CONDUCTOR. PROVIDE |
| | CORRECTION. NEC 250.122; FBC RE E3704.6, 3607.3.1 |
| | 6. PROVIDE TAMPER RESISTANT RECEPTACLES PER CODE. A |
| | NOTE WILL SUFFICE. NEC 406.12; FBC RE E4002.14 |
| | 7. PROVIDE GFCI PROTECTED OUTLET FOR SERVICING OF A/C |
| | EQUIPMENT WITHIN 25 FEET OF THE EQUIPMENT PER CODE. NEC |
| | 210.63; FBC RE E3901.12 |
| | 8. RISER DAIGRAM STATES TO "INSTALL NEW DOUBLE LUG" IN |
| | THE 200 AMP MAIN PANEL. WHAT IS THE PURPOSE OF THIS? |
| | MEANS SHALL BE PROVIDED TO DISCONNECT ALL CONDUCTORS IN |
| | A BUILDING OR OTHER STRUCTURE FROM THE SERVICE-ENTRANCE |
| | CONDUCTORS. PROVIDE CLARIFICATION AND/OR CORRECTION. |
| | NEC 230.70; FBC RE E3601.6 |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY |
| | REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED |
| | SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD |
| | SHEETS. |
| | |