| 2018-10-12 12:10:38 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT #18090013 |
| | 10/12/18 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET M1.1: DUCT SMOKE DETECTORS ARE REQUIRED IN THE |
| | SUPPLY AIR SYSTEMS OF EACH 5-TON RTU SYSTEM PER SECTION |
| | 606.2.1. PLEASE NOTE THAT AN EXEMPTION CAN BE APPLIED |
| | IF THE MANUFACTURER'S SPECIFICATIONS INDICATE SYSTEMS |
| | ARE NOT CAPABLE OF PRODUCING OVER 2000 CFMS OF SUPPLY |
| | AIR. PLEASE PROVIDE SYMBOLS ON THE PLAN TO INDICATE |
| | INDICATE THE DEVICE LOCATIONS. |
| | |
| | 2) PROVIDE NOTES ON THE PLAN TO INDICATE THE FAN |
| | SHUTDOWN SEQUENCE AND HOW THE DETECTORS WILL BE |
| | SUPERVISED- SECTIONS 606.4 & 606.4.1 FBC M. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL PLANS EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL 33401 |
| | 561-805-6719 |
| | [email protected] |
| | |