| 2019-02-20 09:30:31 | 3RD REVIEW: |
| | 2017 FLORIDA BUILDING CODE 6TH EDITION |
| | 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH |
| | EDITION |
| | 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH |
| | EDITION |
| | 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH |
| | EDITION |
| | |
| | PLUMBING COMMENTS: PREVIOUS COMMENTS NOT COMPLIED 2ND |
| | REQUEST |
| | |
| | 3. DETAILS ON SHT. P101 THAT ARE NOT UNDER THE SCOPE OF |
| | THIS PERMIT PLEASE REMOVE IF NOT BEING USED. IF WORK IS |
| | BEING DONE ON THE ROOF DRAINS OR CONDENSATE PLEASE |
| | PROVIDE PIPING DETAILS AND FLOOR PLANS SHOWING NEW WORK |
| | . PER WPB AMEND TO FBC 107..2.1 |
| | |
| | 4. PROVIDE MANUFACTURE SPECIFICATIONS AND INSTALLATION |
| | GUIDE FOR THE TUB DRAINS INSTALLED IN THE SHOWER STALLS |
| | SHOW DETAIL OF HOW THE SHOWER PAN WILL BE SEALED AROUND |
| | TUB DRAIN, THE MANUFACTURE SPECIFICATIONS SHALL ALSO |
| | SHOW APPROVAL OF USE IN THIS APPLICATION. PER WPB AMEND |
| | TO FBC 107..2.1 |
| | |
| | NEW COMMENTS: |
| | |
| | 1. SHT A-3 DETAIL #10 THE WATER PROOF MEMBRANE SHALL |
| | PITCH TO DRAIN. PER FBC PL 417.5.2 |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | |
| | GEORGE JOHNSON |
| | PLUMBING PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | 561-805-6711 |
| | [email protected] |
| | |