2018-10-24 12:42:042ND REVIEW FBC-2017 MECHANICAL
 PERMIT #18081585
 10/24/18
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC R- FLORIDA RESIDENTIAL CODE SIXTH EDITION 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) AC CALCULATIONS: THE CALCULATIONS DO NOT SHOW ANY
 INTERNAL HEAT GAIN LOADS- SEE PAGE 1 AND REFER TO
 SECTION C403.2.1 FBC M.
  
 2) SHEET M201: A DUCT SMOKE DETECTOR IS REQUIRED IN THE
 SUPPLY SYSTEM OF WSHP 1-01 PER SECTION 606.2.1 FBC M.
 PLEASE NOTE THAT THE AIR DISTRIBUTION PLAN INDICATES
 SUPPLY AIR OVER 2000 CFMS, AND IT IS THE POLICY OF THE
 BUILDING DEPARTMENT TO REQUIRE DUCT SMOKE DETECTORS ON
 5-TON SYSTEMS UNLESS MANUFACTURER'S DATA VERIFIES THE
 SYSTEMS CANNOT PRODUCE OVER 2000 CFMS.
  
 3) M201: IT APPEARS THAT AN ADDITIONAL EXHAUST FAN WILL
 BE REQUIRED IN THE BATHUB/SHOWER ROOM OF BATHROOM #3
 (BEDROOM #3 ON THE PLAN) IF THE WALLS OF THE ROOM ARE
 NOT OPEN AT THE TOP.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER