| 2018-09-18 08:53:30 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT #18081585 |
| | 9/18/18 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC R- FLORIDA RESIDENTIAL CODE SIXTH EDITION 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) PLEASE CORRECT THE ADDRESS ON THE PERMIT |
| | APPLICATION, THE PLANS AND THE CALCULATIONS. THE |
| | CORRECT ADDRESS IS 529 S. FLAGLER DRIVE. |
| | |
| | 2) REFER TO SECTION R101.5.1.2 FBC EC. THE PROJECT |
| | SHALL BE IN COMPLIANCE WITH THE COMMERCIAL PROVISIONS |
| | OF THE FBC EC. REFER TO SECTIONS C101.5 AND C403.2.1 |
| | AND SUBMIT REVISED ENERGY AND AC CALCULATIONS. |
| | |
| | 3) SHEET M201: UNDERSIZED BEDROOM RETURN SYSTEMS: A) |
| | MASTER BEDROOM & BERDOOM #1- RETURN DUCTS SHALL BE |
| | SIZED 1.5 TIMES THE CROSS SECTIONAL AREA OF THE SUPPLY |
| | DUCT ENTERING THE ROOM. B) BEDROOMS 2 & 3: THE TRANSFER |
| | GRILLS SHALL BE SIZED AT 50 SQUARE INCHES PER 100 CFMS |
| | OF SUPPLY AIR- SECTION 601.6 FBC M. |
| | |
| | 4) M201: THE PLAN SHOWS DRYER EXHAUST AND TOILET |
| | EXHAUST DUCTS CONNECTING INTO THE SAME SHAFT, HOWEVER A |
| | COMMON MULTI-STORY DRYER EXHAUST SYSTEM SHALL SERVE |
| | ONLY CLOTHES DRYERS. REFER TO SECTION 504.10 ITEMS 1-12 |
| | AND PROVIDE ADDITIONAL DETAILS AND NOTES TO CLARIFY. |
| | |
| | 5) M201: THE PLAN SHOWS KITCHEN HOOD EXHAUST AND TOILET |
| | EXHAUST DUCTS CONNECTING INTO THE SAME SHAFT, HOWEVER A |
| | COMMON MULTI-STORY HOOD EXHAUST SYSTEM SHALL SERVE ONLY |
| | KITCHEN HOOD EXHAUST. REFER TO SECTION 505.3 ITEMS 1-12 |
| | AND PROVIDE ADDITIONAL DETAILS AND NOTES TO CLARIFY. |
| | |
| | 6) M201: VERIFY THAT ALL MATERIALS IN AC CLOSETS USED |
| | AS PLENUM RETURNS ARE NON-COMBUSTIBLE OR ARE LISTED AND |
| | LABELED AS HAVING A FLAME SPREAD OF NOT MORE THAN 25 |
| | AND A SMOKE-DEVELOPED INDEX OF NOT MORE THN 50- SECTION |
| | 602.2.1 FBC M. |
| | |
| | 7) PLEASE SUBMIT PRODUCT DATA SHEETS FOR ALL COOKING |
| | APPLIANCES, KITCHEN HOOD, AND DRYER. ALL SUBMITTALS |
| | SHALL BE APPROVED BY THE EOR. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL PLANS EXAMINER |