2018-09-18 08:53:301ST REVIEW FBC-2017 MECHANICAL
 PERMIT #18081585
 9/18/18
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC R- FLORIDA RESIDENTIAL CODE SIXTH EDITION 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE CORRECT THE ADDRESS ON THE PERMIT
 APPLICATION, THE PLANS AND THE CALCULATIONS. THE
 CORRECT ADDRESS IS 529 S. FLAGLER DRIVE.
  
 2) REFER TO SECTION R101.5.1.2 FBC EC. THE PROJECT
 SHALL BE IN COMPLIANCE WITH THE COMMERCIAL PROVISIONS
 OF THE FBC EC. REFER TO SECTIONS C101.5 AND C403.2.1
 AND SUBMIT REVISED ENERGY AND AC CALCULATIONS.
  
 3) SHEET M201: UNDERSIZED BEDROOM RETURN SYSTEMS: A)
 MASTER BEDROOM & BERDOOM #1- RETURN DUCTS SHALL BE
 SIZED 1.5 TIMES THE CROSS SECTIONAL AREA OF THE SUPPLY
 DUCT ENTERING THE ROOM. B) BEDROOMS 2 & 3: THE TRANSFER
 GRILLS SHALL BE SIZED AT 50 SQUARE INCHES PER 100 CFMS
 OF SUPPLY AIR- SECTION 601.6 FBC M.
  
 4) M201: THE PLAN SHOWS DRYER EXHAUST AND TOILET
 EXHAUST DUCTS CONNECTING INTO THE SAME SHAFT, HOWEVER A
 COMMON MULTI-STORY DRYER EXHAUST SYSTEM SHALL SERVE
 ONLY CLOTHES DRYERS. REFER TO SECTION 504.10 ITEMS 1-12
 AND PROVIDE ADDITIONAL DETAILS AND NOTES TO CLARIFY.
  
 5) M201: THE PLAN SHOWS KITCHEN HOOD EXHAUST AND TOILET
 EXHAUST DUCTS CONNECTING INTO THE SAME SHAFT, HOWEVER A
 COMMON MULTI-STORY HOOD EXHAUST SYSTEM SHALL SERVE ONLY
 KITCHEN HOOD EXHAUST. REFER TO SECTION 505.3 ITEMS 1-12
 AND PROVIDE ADDITIONAL DETAILS AND NOTES TO CLARIFY.
  
 6) M201: VERIFY THAT ALL MATERIALS IN AC CLOSETS USED
 AS PLENUM RETURNS ARE NON-COMBUSTIBLE OR ARE LISTED AND
 LABELED AS HAVING A FLAME SPREAD OF NOT MORE THAN 25
 AND A SMOKE-DEVELOPED INDEX OF NOT MORE THN 50- SECTION
 602.2.1 FBC M.
  
 7) PLEASE SUBMIT PRODUCT DATA SHEETS FOR ALL COOKING
 APPLIANCES, KITCHEN HOOD, AND DRYER. ALL SUBMITTALS
 SHALL BE APPROVED BY THE EOR.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
 HTTPS://WWW.SURVEYMONKEY.COM/R/WESTPALMBEACHCONSTRUCTIO
 NSERVICES
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved