| 2018-09-17 16:03:22 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. NOTE 9 AND PANEL SCHEDULES SHOWN ARE NOT CODE |
| | COMPLIANT IN REFERENCE TO AFCI PROTECTION. ALL BRANCH |
| | CIRCUITS THAT SUPPLY 120-VOLT, SINGLE-PHASE, 15- AND |
| | 20-AMPERE OUTLETS INSTALLED IN KITCHENS, FAMILY ROOMS, |
| | DINING ROOMS, LIVING ROOMS, PARLORS, LIBRARIES, DENS, |
| | BEDROOMS, SUN-ROOMS, RECREATIONS ROOMS, CLOSETS, |
| | HALLWAYS, LAUNDRY AREAS AND SIMILAR ROOMS OR AREAS |
| | SHALL BE AFCI PROTECTED. THIS INCLUDES LIGHTING AND |
| | POWER OUTLETS AND RECEPTACLES. SOME AREAS REQUIRE BOTH |
| | AFCI AND GFCI PROTECTION. PROVIDE CORRECTION. NEC |
| | 210.8, 210.12 |
| | 2. PROVIDE GFCI PROTECTION FOR DISHWASHER. NEC 210.8(D) |
| | 3. POWER PLAN SHOWS 3 PANELS, PANEL A, PANEL B, AND |
| | PANEL L. RISER DIAGRAM ONLY SHOWS 2 PANELS, AND ONLY 2 |
| | PANEL SCHEDULES ARE PROVIDED. PROVIDE CLARIFICAITON |
| | AND/OR CORRECTION. NEC 215.5; WPB FBC 107.2.1 |
| | 4. LIGHTING IN SHOWER/TUB AREAS IS SHOWN AS STANDARD |
| | RECESS LIGHTS. LIGHTING IN BATHTUB OR SHOWER AREAS |
| | SHALL BE SUITABLE FOR DAMP LOCATIONS. NO PARTS OF |
| | CORD-CONNECTED LUMINAIRES, CHAIN-, CABLE-, OR |
| | CORD-SUSPENDED LUMINAIRES, LIGHTING TRACK, PENDANTS, OR |
| | CEILING-SUSPENDED (PADDLE) FANS SHALL BE LOCATED WITHIN |
| | A ZONE MEASURED 3 FEET HORIZONTALLY AND 8 FEET |
| | VERTICALLY FROM THE TOP OF THE BATHTUB RIM OR SHOWER |
| | STALL THRESHOLD. PROVIDE CORRECTION. NEC 410.10(D) |
| | 5. LIGHTING IN CLOSETS IS SHOWN AS STANDARD RECESS |
| | LIGHTS. LIGHTING WITH OPEN OR PARTIALLY ENCLOSED LAMPS |
| | AND PENDANT LUMINAIRES OR LAMPHOLDERS SHALL NOT BE |
| | PERMITTED IN CLOTHES CLOSETS. PROVIDE CORRECTION. NEC |
| | 410.16 |
| | 6. IT APPEARS THAT A GFCI RECEPTACLE IS SHOWN WITHIN |
| | THE TUB/SHOWER AREA OF THE MASTER BATH. RECEPTACLES |
| | SHALL NOT BE INSTALLED WITHIN A TUB OR SHOWER SPACE. |
| | PROVIDE CLARIFICATION AND/OR CORRECTION. NEC 406.9(C) |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY |
| | REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED |
| | SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD |
| | SHEETS. |
| | |