Plan Review Notes
Plan Review Notes For Permit 18081585
Permit Number 18081585
Review Stop B
Sequence Number 1
Notes
Date Text
2018-09-25 17:52:25****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. FBC B 1609, ON THE PRODUCT APPROVALS, INDICATE WHICH
 OPTION IS PROPOSED TO SHOW COMPLIANCE WITH DESIGN
 PRESSURES SPECIFIED.
  
 2. FBC 107, PRODUCT APPROVALS ARE TO BE REVIEWED BY
 DESIGNER OF RECORD (SHOP DRAWING REVIEW OR LETTER OR
 INCORPORATE INTO PLAN).
  
 2. PLEASE ADVISE, WHAT TYPE OF FLOORING IS PROPOSED?
 SEE ITEM 4.
  
 3. FOR THE FLOORING UNDERLAYMENT, PROVIDE THE FOLLOWING
 TEST REPORTS. IT IS RECOMMENDED THAT THIS BE RESOLVED
 VIA EMAIL PRIOR TO RESUBMITTAL. EMAIL THE NAME OF THE
 UNDERLAYMENT PROPOSED TO [email protected] WITH THE PERMIT
 NUMBER IN THE SUBJECT LINE. IF THE MANUFACTURER HAS
 ALREADY PROVIDED THE REQUIRED TEST REPORTS DIRECTLY TO
 US, TEST REPORTS DO NOT NEED TO BE SUBMITTED WHEN
 RESUBMITTING.
  
 PLEASE NOTE THAT TEST REPORTS ARE REQUIRED -
 MANUFACTURER SPEC SHEETS ARE NOT ACCEPTABLE DUE TO
 DISCREPANCIES BETWEEN SPEC SHEETS/BROCHURES AND TEST
 REPORTS FOR SOME MANUFACTURERS (NOT NECESSARILY THE
 MANUFACTURER SELECTED; THIS IS A GENERAL COMMENT)
  
 A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR
 BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90.
 THE TEST REPORT CANNOT INCLUDE A DROPPED GYPSUM
 CEILING. PROVIDE A COPY OF THE TEST REPORT.
  
 B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN
 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH
 ASTM E 492. THE TEST REPORT CANNOT INCLUDE A DROPPED
 GYPSUM CEILING. PROVIDE A COPY OF THE TEST REPORT.
  
 C. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE
 BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE
 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84
 OR UL 723.
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved