| 2018-10-23 16:06:58 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT #18081353 |
| | 10/23/18 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) PROVIDE AC COOLING AND HEATING CALCULATIONS FOR THE |
| | NEW SYSTEMS IN ACCORDANCE WITH SECTION C403.2.1 FBC EC. |
| | |
| | 2) REFER TO SECTION C505.1 FBC-17 ENERGY CONSERVATION |
| | AND SUBMIT AN ENERGY EFFICIENCY COMPLIANCE REPORT FOR |
| | THE CHANGE IN OCCUPANCY FROM S1 TO A2. |
| | |
| | 3) SHEET M-1: PLEASE PROVIDE A MORE SPECIFIC OCCUPANCY |
| | CLASSIFICATION IN THE VENTILATION SCHEDULE FOR THE MAIN |
| | ROOMS- TABLE 403.3.1.1 FBC M. |
| | |
| | 4) M-2: THE SUPPLY AIR DUCTS PENETRATING THE INTERIOR |
| | EXIT STAIRWAY ARE PROHIBITED PER SECTIONS 1023.5 & |
| | 1023.6 FBC B. |
| | |
| | 5) M-2: DUCT SMOKE DETECTORS ARE REQUIRED IN THE SUPPLY |
| | AIR SYSTEMS OF EACH 5-TON AC SYSTEM PER SECTION 606.2.1 |
| | FBC M. PLEASE NOTE THAT AN EXEMPTION CAN BE APPLIED IF |
| | THE MANUFACTURER'S SPECIFICATIONS INDICATE SYSTEMS ARE |
| | NOT CAPABLE OF PRODUCING OVER 2000 CFMS OF SUPPLY AIR. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS |
| | |