| Notes |
| Date |
Text |
| 2018-10-31 15:33:44 | CONCRETE ROOF TILE NOA 14-0102.04 IS OK. | | | THE TWO UNDERLAYMENT PRODUCT APPROVALS BACK TO | | | CONTRACTOR AND SUBMIT WITH ROOF SUB PERMIT THE ONE THAT | | | WILL BE USED (SEE COMMENTS BELOW FOR ADDITIONAL INFO | | | NEEDED). | | | | | | 1. PROVIDE PRODUCT APPROVAL FOR TILE ATTACHMENT | | | MATERIAL BASED ON THE MAXIMUM DESIGN PRESSURE FOR THE | | | ROOF. | | | | | | 2. WHY ARE THERE TWO PRODUCT APPROVALS FOR | | | UNDERLAYMENTS. | | | CHOOSE WHICH ONE WILL BE USED AND SELECT ON THE PRODUCT | | | APPROVAL THE ONE THAT MEETS REQUIRMENTS FOR | | | UNDERLAYMENT FOR CONCRETE TILE ROOF (SEE NOA 14-0102.04 | | | SECTION 4.1) | | | PROVIDE UNDERLAYMENT ATTACHMENT ENGINEERING FOR | | | SELECTED UNDERLAYMENT FOR APPLICABLE ROOF ZONES. | | | | | | DYLAN BATTLES | | | BUILDING PLANS EXAMINER I | | | [email protected] | | | 561-805-6718 | | | |
|