2018-09-28 15:20:09****CORRECTIONS****
 W.P.B. PERMIT: 18081580
 REVIEWED: SEPTEMBER 28, 2018
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER I
 [email protected]
 561-805-6718
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC AMENDED = FLORIDA BUILDING CODE,6TH EDITION (2017)
 FBC EB = FBC EXISTING BUILDING
 FBC ENERGY = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. [FBC ENERGY R401.2]PROVIDE ENERGY CALCULATIONS TO
 MEET REQUIREMENTS IN RESIDENTIAL ENERGY CODE. CHOOSE
 METHOD IN R401.2 AND SUPPLY DOCUMENTATION.
 PLEASE INCLUDE ALL SKYLIGHTS AND SOLAR TUBES IN THE
 CALCULATIONS.
  
 2. [FBC R302.10]PROVIDE CUT SHEET FOR ICYNENE(ICC-ES
 REPORT OR EQUAL) WITH THE TYPE SELECTED TO ESTABLISH
 THICKNESS NEEDED TO MEET REQUIRED R-VALUE, FLAME SPREAD
 INDEX AND SMOKE DEVELOPED INDEX.
  
 3. [FBC R408.4]ACCESS TO UNDER FLOOR SPACE. ACCESS
 OPENINGS THROUGH THE FLOOR SHALL BE A MINIMUM OF 18
 INCHES BY 24 INCHES. OPENINGS THROUGH A PERIMETER WALL
 SHALL BE NOT LESS THAN 16 INCHES BY 24 INCHES.
  
 4. [FBC R408.4]IS THERE CURRENTLY ACCESS TO UNDER FLOOR
 SPACE? SHOW WHERE IT IS LOCATED.
 ALSO, PROVIDE EXISTING UNDER FLOOR VENTING AMOUNT AND
 ADDITIONAL VENTING FOR ENTRY RAISED FLOOR.
  
 5. [FBC R318]SHEET S1 SHOWS TERMITE TREATMENT AT NEW
 CONCRETE ONLY.
 PLEASE ADD NOTE TO TREAT AREA AT ENTRY WHERE NEW FLOOR
 IS GOING IN AND AT REAR WHERE COVERING SLAB. EVEN
 THOUGH EXISTING SLAB REMAINS THAT AREA SHOULD MEET
 CURRENT CODES.
  
 6. [FBC R506.2.3]AT EXISTING SLAB TO REMAIN. THIS SLAB
 SEEMS LIKE SOMETHING THAT WAS EXTERIOR AND WOULD NOT
 HAVE PROPER VAPOR BARRIER, OR IT WOULS BE TO OLD TO
 CONSIDER ADEQUATE. PLEASE ADDRESS HOW PROPER VAPOR
 BARRIER IS BEING PROVIDED FOR AREAS WHERE EXISTING SLAB
 IS TO REMAIN.
  
 7. [FBC R301.4]&[FBC R301.5]PROVIDE LIVE LOAD AND DEAD
 LOAD INFORMATION ON SHEET S-2 FOR ROOF LOADS.
  
 8. [FBC 107.2.5]SHEET A1 AT GARAGE DETAIL LEFT SIDE
 A/A1. IS THIS SUPPOSE TO LEAD TO A DETAIL?
 PROVIDE DETAIL, DETAIL NUMBER OR DELETE AS APPLICABLE.
  
 9. [FBC 107.2.5]SHEET S1 CALL OUTS A/S1 DON'T LEAD TO
 CORRECT DETAIL PAGE.
 PLEASE ADJUST PAGE NUMBER ON CALLOUTS.
  
 10. [FAC RULE 9N-3]PROVIDE PRODUCT APPROVAL FOR FRENCH
 DOOR, WINDOW MULL, SKYLIGHTS AND SOLAR TUBES.
  
 11. IS THE ENTRYWAY THE MAHOGANY DOOR FROM FL-15209.3?
 THIS PRODUCT APPROVAL FOR OXO ARRANGEMENT PROVIDES MAX
 +40/-40. SHEET A2A DESIGN DATA SHOW DESIGN PRESSURES AT
 +52.2/-56.8 FOR INTERIOR ZONES.
 PLEASE PROVIDE DATA TO SHOW THAT THE DOOR WILL MEET
 PRESSURES.
  
 12. [FBC AMENDED 107.3.4.1]SUBMIT TRUSS SHOP DRAWINGS
 TO THE BUILDING INSPECTOR PRIOR TO INSTALLATION.
  
 13. [FBC AMENDED 107.3.4.1]SEE COMMENTS IN ROOFING
 REVIEW, OR INDICATE THAT YOU WOULD LIKE THEM DEFERED.
 IF DEFERRED THE NOA'S WILL BE APPROVED, BUT THE
 ADDITIONAL ATTACHMENT MATERIALS WILL NEED TO BE
 SUBMITTED WITH THE ROOFING SUB PERMIT.
  
 NOTE:
 -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW
 EACH COMMENT IS BEING ADDRESSED.
 -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW
 OF MATERIALS REQUESTED.
 -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS
 OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS)
 SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT
 DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER
 SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID"
 OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS
 APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE
 NEED "VOID", RENDERING THEM NOT USABLE.
  