Plan Review Notes
Plan Review Notes For Permit 18081528
Permit Number 18081528
Review Stop Z
Sequence Number 3
Notes
Date Text
2019-07-03 17:04:39FAILED
  
 PROVIDE WRITTEN RESPONSES TO COMMENTS.
  
 1) REVISED COMMENT: STAFF HAS REVIEWED THE COMMENT
 RESPONSE IN ADDITION TO THE LETTER PROVIDED BY AARON
 KNIGHT, DATED APRIL 25, 2019, AS WELL AS THE ENLARGED
 UNIT PLANS AND ENLARGED ELECTRICAL PLANS AND HAS THE
 FOLLOWING COMMENTS.
  
 A. YOU MAY PROVIDE A "SECONDARY KITCHEN" PROVIDED THAT
 THERE ARE NO RANGES/COOK TOPS OR OVENS IN THE SECONDARY
 KITCHEN. STAFF NOTED THAT THE ARCHITECTURAL PLANS DO
 NOT SHOW THESE COOKING FACILITIES IN THE SECONDARY
 KITCHENS IN UNITS G, H OR I (UNIT E IS STATED IN THE
 LETTER AS HAVING A SECONDARY KITCHEN, BUT NONE SHOWN ON
 THE UNIT PLAN), SO THIS IS PERMITTED BY THE ZONING
 CODE. PLEASE NOTE THE ELECTRICAL PLANS FOR THESE UNITS
 DOES SHOW A "COOK TOP" ON THE ELECTRICAL PANEL, WITH
 THE ASSOCIATED OUTLET, WHICH IS NOT PERMITTED AND MAY
 NOT BE INSTALLED, AND THE MECHANICAL PLANS SHOW
 RECIRCULATING HOODS WHICH ARE NOT PERMITTED AND MAY NOT
 BE INSTALLED.
  
 B. SHEET A-229A SHOWS AN OVEN/RANGE IN THE SECONDARY
 KITCHEN, WHICH IS NOT PERMITTED AS THIS IS THE SECOND
 SET OF COOKING FACILITIES IN THE PENTHOUSE UNIT. NOTE:
 SHEET E-229 SHOWS A "COOK TOP" IN THE ELECTRICAL PANEL
 FOR THE SECONDARY KITCHEN; HOWEVER, THE OUTLET IS NOT
 SHOWN WHERE THE ARCHITECTURAL PLAN SHOWS THE
 NON-PERMITTED OVEN/RANGE IS SHOWN. THE SECOND
 OVEN/RANGE NEEDS TO BE REMOVED FROM THE PLANS AND THE
 ELECTRICAL PLANS CORRECTED.
  
 2) NEW COMMENT: ON SHEET A114 THE "TOTAL PROVIDED
 PARKING COUNT" TABLE (LOWER LEFT CORNER OF SHEET) NOW
 LISTS 183 PARKING SPACES PROVIDED BASED ON CHANGING THE
 MIX OF PARKING SPACES. THE "PARKING PROVIDED" TABLE
 (TOP MIDDLE OF SHEET) CONTINUES TO LIST 184 PARKING
 SPACES PROVIDED. ALL TABLES MUST LIST CORRECT,
 CONSISTENT INFORMATION. NOTE THERE ARE 18 BICYCLE
 PARKING SPACES PROVIDED.
  
 3) NEW COMMENT: ON SHEET A114 THE NEW PARKING LAYOUT
 CHANGED (NO CLOUDING OF PLANS PROVIDED) AND STAFF NOTED
 THE FOLLOWING ISSUES:
  
 A. PARKING SPACE #8 IS NO LONGER DESIGNATED ON THE
 PLANS AND NO DIMENSIONS WERE PROVIDED TO VERIFY THAT IT
 MEETS MINIMUM CODE REQUIREMENTS.
 B. PARKING SPACE #9 DOES NOT FUNCTION DUE TO THE COLUMN
 AT ITS HEAD MAKING THE SPACE LESS THAN THE REQUIRED 16
 FEET IN DEPTH (FOR A COMPACT SPACE) DUE TO THE
 ELIMINATION OF THE WHEEL STOP OVERHANG. NOTE: THIS IS
 DIFFERENT FROM HOW IT APPEARS ON SHEETS A-101 AND
 A-101A
 C. PARKING SPACE #26 IS NO LONGER DESIGNATED ON THE
 PLANS AND NO DIMENSIONS WERE PROVIDED TO VERIFY THAT IT
 MEETS MINIMUM CODE REQUIREMENTS.
 D. PARKING SPACE #29 CHANGED FROM A COMPACT SPACE TO A
 REGULAR SPACE; HOWEVER THE STRIPING AT THE PARKING
 SPACE WAS NOT CORRECTED TO MEET CODE REQUIREMENTS.
 E. PARKING SPACE #58, #95 AND #96 NO LONGER EXIST. DID
 THE SHIFT TO WHERE THE OLD SPACE #96 WAS? THE PAVEMENT
 MARKING IS UNCLEAR ON THE PLANS. NO DIMENSIONS FOR WHAT
 APPEAR TO BE THE NEW SPACES IS PROVIDED FOR STAFF TO
 VERIFY CODE COMPLIANCE, THIS INCLUDES THE AISLE WIDTH
 AT THIS LOCATION. NOTE: SHEET A-101A PARKING SPACE
 DEPTH DIFFERS FROM WHAT IS SHOWN ON SHEET A114.
  
 4) NEW COMMENT: PLEASE EXPLAIN WHY THE GRAND TOTAL GBA
 GROUND LEVEL AREA SHOWN ON SHEET A114 INCREASED FROM
 47,179 SF ON VERSION 2 OF THE PLANS TO 47,611 SF ON
 VERSION 3 OF THE PLANS. STAFF WAS NOT ABLE TO SEE ANY
 INCREASE IN THE BUILDING FOOTPRINT, NOR WAS CLOUDING
 USED TO HIGHLIGHT CHANGES.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
 [email protected]
  
  