| Date |
Text |
| 2019-06-05 09:28:28 | |
| | 3RD REVIEW: 18011528 |
| | 2017 FLORIDA BUILDING CODE 6TH EDITION |
| | 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH |
| | EDITION |
| | 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH |
| | EDITION |
| | 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH |
| | EDITION |
| | |
| | PLUMBING COMMENTS: PREVIOUS COMMENTS. |
| | |
| | 1. SHT. A-772 DETAIL #12 TYPE 10 BATHROOM, THE CLEAR |
| | FLOOR SPACE FOR THE SHOWER SHALL RUN PARALLEL TO THE |
| | FIXTURE AND THE END LINE UP WITH THE CONTROL WALL. PER |
| | FHA DESIGN MANUAL REQUIREMENT #7 PG. 7.5 |
| | |
| | 14. SHT. P-502 LABEL ALL WATER PIPING WITH HOT , COLD, |
| | RETURN . PER WPB AMEND TO FBC 107.2.1 |
| | |
| | NEW COMMENTS: |
| | |
| | 1. SHOWERS IN SPA SHALL COMPLY WITH ANSI 117.1 1986 |
| | SEC. 4.21 SHOW COMPLIANCE ON PLAN CONTROLS, GRAB BARS |
| | AND CLEAR FLOOR SPACE. |
| | |
| | 2. THE MEN AND WOMENS BATHROOM ON LEVEL 3 SHALL HAVE A |
| | LAVATORY OUT SIDE THE ACCESSIBLE STALL AND IN THE SAME |
| | ROOM AS THE REQUIRED WATER CLOSET.PER FBC PL 405.3.2 |
| | |
| | 3.COMMON AREA BATHROOMS SHOW THE DISTANCE OF THE SIDE |
| | WALL GRAB BAR FROM THE REAR WALL OF THE TOILET. ANZI |
| | 117.1 1986 SEC 416.4 |
| | |
| | 4. COMMON AREA BATHROOMS SHOW HEIGHT OF TOILET PER ANZI |
| | 117.1 1986 SEC 416.3 |
| | |
| | 5. COMMON AREA BATHROOMS SHOW DIMENSIONS OF REAR GRAB |
| | BARS IN REFERENCE TO CENTER OF TOILET. ANZI 117.1 1968 |
| | SEC 416.4 |
| | |
| | 6. COMMON AREA BATHROOMS SHOW HEIGHT OF TOILET PAPER |
| | DISPENSER. ANZI 117.1 1968 SEC 416.6 |
| | |
| | 7. COMMON AREA BATHROOMS SHOW CENTER OF TOILET OFF SIDE |
| | WALL ANZI 117.1 1968 SEC 416.2 |
| | |
| | 8. SHT. P-502B COMPLY WITH THE FOLLOWING:REQUIRED TO |
| | DETERMINE CODE COMPLIANCE. PER WPB AMEND TO FBC 107.2.1 |
| | A) EXPAND THE ISOMETRIC DRAWING. |
| | B) SHOW FLOOR LEVELS ON ISOMETRIC DRAWING. |
| | C) THERE ARE PIPES THAT END WITH NO LABEL OR LOCATION |
| | TAG PLEASE LABEL ALL PIPING TERMINATION POINTS SOME |
| | EXAMPLES ARE BRANCHES OFF THE FOLLOWING STACKS S/1, |
| | S/20, S/4, S/6, S13, S/13, S/12, S/11 |
| | D) SHOW THE REQUIRED CLEAN OUTS AT THE BASE OF THE |
| | STACKS. |
| | |
| | 9. SHT. P-502A COMPLY WITH THE FOLLOWING:REQUIRED TO |
| | DETERMINE CODE COMPLIANCE. PER WPB AMEND TO FBC 107.2.1 |
| | A) PLEASE ORIENTATE THE ISOMETRIC SO THAT THE BOTTOM OF |
| | THE DRAWING IS LINED UP WITH THE BOTTOM OF THE PLAN |
| | PAGE. |
| | B) THERE ARE PIPES THAT END WITH NO LABEL OR LOCATION |
| | TAG PLEASE LABEL ALL PIPING TERMINATION POINTS. |
| | C) SHOW FLOOR LEVELS ON THE SOILSTACKS NOT JUST VENTS. |
| | D) SHOW ALL BRANCHES ON THE SANITARY STACKS FOR EACH |
| | FLOOR. |
| | E) ARE THE TOP OF THE SOIL STACKS CONNECTING TO THE |
| | VENT STACKS IF SO PLEASE SHOW ON THE DRAWING. |
| | F) THE TOP OF S/14 SHWS A FLOOR DRAIN THAT IS NOT |
| | CONNECTED TO PIPING PLEASE CLARIFY. |
| | |
| | 10. P-501 PLEASE ORIENTATE ISOMETRIC SO THAT THE BOTTOM |
| | OF THE DRAWING IS LINED UP WITH THE BOTTOM OF THE PLAN |
| | PAGE. |
| | |
| | 11. SHT A-774 COMPLY WITH THE FOLLOWING:REQUIRED TO |
| | DETERMINE CODE COMPLIANCE. PER WPB AMEND TO FBC 107.2.1 |
| | A) DETAIL #4 THE TOILET SHALL BE 18" OFF THE SIDE WALL |
| | OR GRAB BAR SIDE FHA REQ. #6 |
| | B) DETAIL #4 THE CLEAR FLOOR SPACE PARALLEL TO THE |
| | SHOWER AND LINED UP WITH THE CONTROL WALL FHA REQ 7 PG |
| | 7.56 |
| | C)DETAIL #7 THE TOILET SHALL BE 18" OFF THE SIDE WALL |
| | OR GRAB BAR SIDE FHA REQ. #6 |
| | D) DETAIL #7 THE CLEAR FLOOR SPACE PARALLEL TO THE |
| | SHOWER AND LINED UP WITH THE CONTROL WALL FHA REQ 7 PG |
| | 7.56 |
| | E) DETAIL #10 THE CLEAR FLOOR SPACE PARALLEL TO THE |
| | SHOWER AND LINED UP WITH THE CONTROL WALL FHA REQ 7 PG |
| | 7.56 |
| | F) DETAIL #10 THE TOILET SHALL BE 18" OFF THE SIDE WALL |
| | OR GRAB BAR SIDE FHA REQ. #6 |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | |
| | GEORGE JOHNSON |
| | PLUMBING PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | 561-805-6711 |
| | [email protected] |