Plan Review Notes
Plan Review Notes For Permit 18081528
Permit Number 18081528
Review Stop P
Sequence Number 3
Notes
Date Text
2019-06-05 09:28:28 
 3RD REVIEW: 18011528
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS: PREVIOUS COMMENTS.
  
 1. SHT. A-772 DETAIL #12 TYPE 10 BATHROOM, THE CLEAR
 FLOOR SPACE FOR THE SHOWER SHALL RUN PARALLEL TO THE
 FIXTURE AND THE END LINE UP WITH THE CONTROL WALL. PER
 FHA DESIGN MANUAL REQUIREMENT #7 PG. 7.5
  
 14. SHT. P-502 LABEL ALL WATER PIPING WITH HOT , COLD,
 RETURN . PER WPB AMEND TO FBC 107.2.1
  
 NEW COMMENTS:
  
 1. SHOWERS IN SPA SHALL COMPLY WITH ANSI 117.1 1986
 SEC. 4.21 SHOW COMPLIANCE ON PLAN CONTROLS, GRAB BARS
 AND CLEAR FLOOR SPACE.
  
 2. THE MEN AND WOMENS BATHROOM ON LEVEL 3 SHALL HAVE A
 LAVATORY OUT SIDE THE ACCESSIBLE STALL AND IN THE SAME
 ROOM AS THE REQUIRED WATER CLOSET.PER FBC PL 405.3.2
  
 3.COMMON AREA BATHROOMS SHOW THE DISTANCE OF THE SIDE
 WALL GRAB BAR FROM THE REAR WALL OF THE TOILET. ANZI
 117.1 1986 SEC 416.4
  
 4. COMMON AREA BATHROOMS SHOW HEIGHT OF TOILET PER ANZI
 117.1 1986 SEC 416.3
  
 5. COMMON AREA BATHROOMS SHOW DIMENSIONS OF REAR GRAB
 BARS IN REFERENCE TO CENTER OF TOILET. ANZI 117.1 1968
 SEC 416.4
  
 6. COMMON AREA BATHROOMS SHOW HEIGHT OF TOILET PAPER
 DISPENSER. ANZI 117.1 1968 SEC 416.6
  
 7. COMMON AREA BATHROOMS SHOW CENTER OF TOILET OFF SIDE
 WALL ANZI 117.1 1968 SEC 416.2
  
 8. SHT. P-502B COMPLY WITH THE FOLLOWING:REQUIRED TO
 DETERMINE CODE COMPLIANCE. PER WPB AMEND TO FBC 107.2.1
 A) EXPAND THE ISOMETRIC DRAWING.
 B) SHOW FLOOR LEVELS ON ISOMETRIC DRAWING.
 C) THERE ARE PIPES THAT END WITH NO LABEL OR LOCATION
 TAG PLEASE LABEL ALL PIPING TERMINATION POINTS SOME
 EXAMPLES ARE BRANCHES OFF THE FOLLOWING STACKS S/1,
 S/20, S/4, S/6, S13, S/13, S/12, S/11
 D) SHOW THE REQUIRED CLEAN OUTS AT THE BASE OF THE
 STACKS.
  
 9. SHT. P-502A COMPLY WITH THE FOLLOWING:REQUIRED TO
 DETERMINE CODE COMPLIANCE. PER WPB AMEND TO FBC 107.2.1
 A) PLEASE ORIENTATE THE ISOMETRIC SO THAT THE BOTTOM OF
 THE DRAWING IS LINED UP WITH THE BOTTOM OF THE PLAN
 PAGE.
 B) THERE ARE PIPES THAT END WITH NO LABEL OR LOCATION
 TAG PLEASE LABEL ALL PIPING TERMINATION POINTS.
 C) SHOW FLOOR LEVELS ON THE SOILSTACKS NOT JUST VENTS.
 D) SHOW ALL BRANCHES ON THE SANITARY STACKS FOR EACH
 FLOOR.
 E) ARE THE TOP OF THE SOIL STACKS CONNECTING TO THE
 VENT STACKS IF SO PLEASE SHOW ON THE DRAWING.
 F) THE TOP OF S/14 SHWS A FLOOR DRAIN THAT IS NOT
 CONNECTED TO PIPING PLEASE CLARIFY.
  
 10. P-501 PLEASE ORIENTATE ISOMETRIC SO THAT THE BOTTOM
 OF THE DRAWING IS LINED UP WITH THE BOTTOM OF THE PLAN
 PAGE.
  
 11. SHT A-774 COMPLY WITH THE FOLLOWING:REQUIRED TO
 DETERMINE CODE COMPLIANCE. PER WPB AMEND TO FBC 107.2.1
 A) DETAIL #4 THE TOILET SHALL BE 18" OFF THE SIDE WALL
 OR GRAB BAR SIDE FHA REQ. #6
 B) DETAIL #4 THE CLEAR FLOOR SPACE PARALLEL TO THE
 SHOWER AND LINED UP WITH THE CONTROL WALL FHA REQ 7 PG
 7.56
 C)DETAIL #7 THE TOILET SHALL BE 18" OFF THE SIDE WALL
 OR GRAB BAR SIDE FHA REQ. #6
 D) DETAIL #7 THE CLEAR FLOOR SPACE PARALLEL TO THE
 SHOWER AND LINED UP WITH THE CONTROL WALL FHA REQ 7 PG
 7.56
 E) DETAIL #10 THE CLEAR FLOOR SPACE PARALLEL TO THE
 SHOWER AND LINED UP WITH THE CONTROL WALL FHA REQ 7 PG
 7.56
 F) DETAIL #10 THE TOILET SHALL BE 18" OFF THE SIDE WALL
 OR GRAB BAR SIDE FHA REQ. #6
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]