2019-06-05 10:05:25CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: 3RD REVIEW, DENIED, SEE
 COMMENTS BELOW.
  
 BE ADVISED THAT THERE IS SO MUCH CONFLICTING AND
 INCOMPLETE INFORMATION ON THIS SUBMISSION THAT A FULL
 REVIEW WILL BE REQUIRED FOR THE NEXT REVIEW, LIKELY
 RESULTING IN FURTHER COMMENTS.
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY HAVE BEEN REMOVED. PREVIOUS COMMENTS
 THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY HAVE
 ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW COMMENTS
 WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
  
 14. SHEET E-102B, CIRCUIT AL-17 IS SHOWN FEEDING THE
 TRATAM ROOM. WHAT IS THIS ROOM USED FOR, IS GFCI
 PROTECTION REQUIRED. PROVIDE CLARIFICATION AND/OR
 CORRECTION. NEC 210.8; WPB FBC 107.2.1 (RESPONSE
 RECEIVED STATES THAT GFCI PROTECTION IS NOT REQUIRED. I
 DISAGREE, SEE CODE SECTION STATED AT THE END OF THIS
 COMMENT. LOCKER ROOMS REQUIRE GFCI PROTECTION. PROVIDE
 CORRECTION. NEC 210.8(B)(7) )
 84. LIGHTING SHEETS (ALL) DO NOT SHOW THE AUTOMATIC
 CONTROL REQUIRED. PROVIDE THE ADDITIONAL AUTOMATIC
 LIGHTING CONTROLS STIPULATED IN THE FBC ENERGY CODE.
 FBC EC C405.2 (RESPONSE LETTER STATES THIS IS PROVIDED,
 BUT IT HAS NOT BEEN PROVIDED. NONE OF THE INTERIOR
 SPACES I CHECHED SHOW THE AUTOMATIC CONTROL REQUIRED.
 PROVIDE CORRECTION.)
 85. PROVIDE GRAPH/CALCULATION OF EXTERIOR LIGHTING
 POWER ALLOWANCES PER THE FBC ENERGY CONSERVATION IN
 RELATION TO THE CONNECTED EXTERIOR LIGHTING PROPOSED TO
 COMPLY WITH CODE. FBC EC C405.5.1 (NOT SURE WHICH CODE
 BOOK YOU ARE LOOKING IN, BUT C405.6.2 AS MENTIONED IN
 YOUR RESPONSE IS NOT THE SECTION FROM THE CURRENT CODE
 THAT REQUIRES EXTERIOR LIGHTING COMPLIANCE. PROVIDE AS
 PREVIOUSLY REQUESTED.)
 97. ON RISER DIAGRAM PANEL EQEH IS SHOWN AS A 1200 AMP
 PANEL. IN THE PANEL SCHEDULE FOR THIS PANEL, IT IS
 SHOWN AS AN 800 AMP PANEL. PROVIDE CORRECTION. WPB FBC
 107.2.1 (STILL NOT CORRECTED. E-502 AND E-602 SHOW EQEH
 AS AN 800 AMP PANEL. LOAD CALCULATION ON E-601A STATES
 THIS IS A 1200 AMP PANEL WITH A LOAD OF 963 AMPS.
 PROVIDE CORRECTION.)
 102. AS ADJUSTMENTS ARE MADE TO DISCREPANCIES IN PLAN,
 PROVIDE UPDATED LOAD CALCULATION FOR EACH PANEL AND
 SERVICE. NEC 220 (LOAD CALCULATION STILL NOT CORRECT OR
 COMPLETE, SEE NEW COMMENTS BELOW.)
 103. SHEET E-601A, LOADS LISTED FOR LOAD CALCULATION
 SHOWN ARE MUCH DIFFERENT THAN THE LOADS SHOWN IN THE
 CORRESPONDING PANEL SCHEDULES. PROVIDE CLARIFICATION
 AND CORRECTION. WPB FBC 107.2.1; NEC 220 (THIS COMMENT
 NOT ADDRESSED SATISFACTORILY, SEE NEW COMMENTS.)
 107. LOAD FOR PANEL H SHOWN IN PANEL SCHEDULE FOR PANEL
 MDP1 IS MUCH DIFFERENT THAN THE LOAD SHOWN IN THE PANEL
 SCHEDULE FOR PANEL H. PROVIDE CORRECTION. WPB FBC
 107.2.1; NEC 220 (NOT CORRECTED, SEE NEW COMMENTS FOR
 FURTHER EXPLANATION.)
 111. PROVIDE PANEL SCHEDULE FOR ALL PANELS. SOME ARE
 MISSING, SUCH AS RDEH AND RH. WPB FBC 107.2.1; NEC
 408.4 (NOT ALL PANEL SCHEDULES PROVIDED.)
  
 NEW COMMENTS:
  
 114. IN REFERENCE TO PREVIOUS COMMENT 103, LOAD FOR
 EQEH IS SHOWN IN ON E-601A AS 963 AMPS. PANEL SCHEDULE
 FOR EM ON SHEET E-602 SHOWS THIS IS BEING FED FROM AN
 800 AMP BREAKER WITH THREE SETS OF 400 KCMIL AL WIRE,
 WHICH IS RATED FOR 810 AMPS. PROVIDE CORRECTION. NEC
 215.2, 408.30, 408.36
 115. IN REFERENCE TO PREVIOUS COMMENT 103, LOAD
 CALCULATION ON SHEET E-601A SHOWS A LOAD OF 1451 AMPS
 FOR PANEL EM. SHEET E-602 SHOWS A LOAD OF 557 AMPS FOR
 THE SAME PANEL. CORRECT DISCREPANCY, UPDATE LOAD
 CALCULATION AS NEEDED. WPB FBC 107.2.1; NEC 220, 215.2,
 215.5, 408.30, 408.36
 116. IN REFERENCE TO PREVIOUS COMMENT 103, LOAD
 CALCULATION ON SHEET E-601A SHOWS A 3RD LOAD ON THE 480
 VOLT SERVICE FOR RETAILS. THIS IS NOT SHOWN ON RISER
 DIAGRAM OR ANY OTHER LOCATION. PROVIDE DETAILS. WPB FBC
 107.2.1
 117. IN REFERENCE TO PREVIOUS COMMENT 103, LOAD
 CALCULATION ON SHEET E-601A SHOWS A LOAD OF 596 AMPS
 FOR MDP1. ON SHEET E-605, THIS PANEL SHOWS A LOAD OF
 1101 AMPS. CORRECT DISCREPANCY, UPDATE LOAD CALCULATION
 AS NEEDED. NEC 220; WPB FBC 107.2.1
 118. SHEET E-601A SHOWS MDP1 AS AN 800 AMP PANEL.
 SHEETS E-502 AND E-605 SHOW IT AS 1200 AMP. CORRECT
 DISCREPANCY, UPDATE LOAD CALCULATION AS NEEDED. WPB FBC
 107.2.1; NEC 220, 215.2, 215.5, 408.30, 408.36
 119. IN REFERENCE TO PREVIOUS COMMENT 103, LOAD
 CALCULATION ON SHEET E-601A SHOWS A LOAD OF 481 AMPS IN
 PANEL SCHEDULE FOR MDP1. SHEET E-605 SHOWS A LOAD OF
 872 AMPS FOR THIS PANEL. WPB FBC 107.2.1; NEC 220,
 215.2, 215.5, 408.30, 408.36
 120. SHEET E-601A SHOWS PANEL H FED FROM MDP1 ON A 700
 AMP BREAKER, AND THE FEEDERS AS THREE SETS OF 350 AL
 KCMIL, WHICH IS RATED FOR 750 AMPS. CORRECT CONDUCTOR
 AND BREAKER SIZE TO MATCH RESULTS FROM COMMENT 119. NEC
 220, 215.2, 215.5, 310.15(B)(16), 408.30, 408.36
 121. PANEL SCHEDULE FOR PANEL GMP SHOWS A LOAD NAMED TE
 THAT IS 408 KVA. PROVIDE DETAILS AND PANEL SCHEDULE,
 UPDATE LOAD CALCULATION AS NEEDED. SHEET E-601A SHOWS A
 LOAD OF 360 KVA FOR EDPH, A LOAD OF 800 KVA FOR EQEH,
 AND A LOAD OF 45 KVA FOR EOPH. WHEN THIS IS ADDED TO
 THE LOAD OF 408 KVA FOR TE, THE GENERATOR WOULD BE
 OVERLOADED. PROVIDE CLAIFICATIONS AND CORRECTIONS AS
 NEEDED. WPB FBC 107.2.1; NEC 220, 215.2, 215.5, 408.30,
 408.36
 122. IN REFERENCE TO PREVIOUS COMMENT 103, LOAD
 CALCULATION ON SHEET E-601A SHOWS A LOAD OF 433.5 AMPS
 FOR PANEL EDPH. SHEET E-602 SHOWS A LOAD OF 179 AMPS.
 CORRECT DISCREPANCY, UPDATE LOAD CALCULATION AS NEEDED.
 WPB FBC 107.2.1; NEC 220, 215.2, 215.5, 408.30, 408.36
 123. PROVIDE VOLTAGE DROP CALCULATIONS TO COMPLY WITH
 CODE FOR ENTIRE SYSTEM. CURRENTLY, THE ONLY VOLTAGE
 DROP PROVIDED IS FOR THE LOADS ON SHEET E-601. NONE OF
 THE LOADS ON SHEET E-601A SHOW THE VOLTAGE DROP
 CALCULATIONS. PROVIDE CORRECTION. FBC EC C405.6.3
 124. PROVIDE BLOCK NOTE INDICATING COMPLIANCE: WITHIN
 30 DAYS AFTER THE DATE OF SYSTEM ACCEPTANCE, RECORD
 DRAWINGS OF THE ACTUAL INSTALLATION SHALL BE PROVIDE TO
 THE BUILDING OWNER, INCLUDING: 1. A SINGLE LINE DIAGRAM
 OF THE BUILDING ELECTRICAL DISTRIBUTION SYSTEM AND 2.
 FLOOR PLANS INDICATING LOCATION AND AREA SERVED FOR ALL
 DISTRIBUTION. FBC EC C405.6.4.1
 125. NO LOAD CALCULATION FOR GUEST SUITES IS PROVIDED
 OR INCLUDED IN THE LOAD CALCULATION ON SHEET E-601 FOR
 METER CENTER 1 / PANEL L. PROVIDE CORRECTION. WPB FBC
 107.2.1; NEC 220, 215.2, 215.5, 408.30, 408.36
 126. SHEET E-501 AND E-502 ARE NAMED RESIDENTIAL POWER
 RISER DIAGRAM. ONLY ONE OF THEM IS THE RESIDENTIAL
 PORTION, THE OTHER IS NOT. PROVIDE DISTINCT NAME FOR
 PLAN SHEET FOR CLARITY. WPB FBC 107.2.1
 127. SHEET E-229 SHOWS A 125 AMP PANEL FOR PH-D. LOAD
 CALCULATION PROVIDED SHOWS A LOAD FOR THIS UNIT OF 272
 AMPS. PROVIDE CORRECTION. PROVIDE WIRE AND CONDUIT
 SIZES FOR FEEDS TO UNIT PANEL. PROVIDE ACCURATE
 LOCATION OF ELECTRICAL PANEL. ALL PANEL SCHEDULES FOR
 THE UNITS STATE THAT THE PANEL IS IN THE UTILITY ROOM,
 BUT THIS IS NOT THE CASE. EDIT LOCATIONS IN PANEL
 SCHEDULES AND SHOW LOCATION ON PLAN TO CONFIRM CODE
 COMPLIANCE. REMOVE OR EDIT CLOUDS FROM PREVIOUS
 REVISIONS THAT BLOCK OTHER INFORMATION ON PLAN. WPB FBC
 107.2.1; NEC 220, 215.2, 215.5, 310.15(B)(16), 408.30,
 408.36
 128. SHEET E-227 AND E-228 SHOWS A 125 AMP PANEL FOR
 PH-B AND PH-C. LOAD CALCULATION PROVIDED SHOWS A LOAD
 FOR THIS UNIT OF 202 AND 200 AMPS, RESPCTIVELY. PROVIDE
 CORRECTION. PROVIDE WIRE AND CONDUIT SIZES FOR FEEDS TO
 UNIT PANEL. PROVIDE ACCURATE LOCATION OF ELECTRICAL
 PANEL. ALL PANEL SCHEDULES FOR THE UNITS STATE THAT THE
 PANEL IS IN THE UTILITY ROOM, BUT THIS IS NOT THE CASE.
 EDIT LOCATIONS IN PANEL SCHEDULES AND SHOW LOCATION ON
 PLAN TO CONFIRM CODE COMPLIANCE. REMOVE OR EDIT CLOUDS
 FROM PREVIOUS REVISIONS THAT BLOCK OTHER INFORMATION ON
 PLAN. WPB FBC 107.2.1; NEC 220, 215.2, 215.5,
 310.15(B)(16), 408.30, 408.36
 129. SHEET E-226 SHOWS A 125 AMP PANEL FOR PH-A. LOAD
 CALCULATION PROVIDED SHOWS A LOAD FOR THIS UNIT OF 190
 AMPS. PROVIDE CORRECTION. PROVIDE WIRE AND CONDUIT
 SIZES FOR FEEDS TO UNIT PANEL. PROVIDE ACCURATE
 LOCATION OF ELECTRICAL PANEL. ALL PANEL SCHEDULES FOR
 THE UNITS STATE THAT THE PANEL IS IN THE UTILITY ROOM,
 BUT THIS IS NOT THE CASE. EDIT LOCATIONS IN PANEL
 SCHEDULES AND SHOW LOCATION ON PLAN TO CONFIRM CODE
 COMPLIANCE. REMOVE OR EDIT CLOUDS FROM PREVIOUS
 REVISIONS THAT BLOCK OTHER INFORMATION ON PLAN. WPB FBC
 107.2.1; NEC 220, 215.2, 215.5, 310.15(B)(16), 408.30,
 408.36
 130. SHEET E-225 SHOWS A 125 AMP PANEL FOR UNIT F. LOAD
 CALCULATION PROVIDED SHOWS A LOAD FOR THIS UNIT OF 154
 AMPS. PROVIDE CORRECTION. PROVIDE WIRE AND CONDUIT
 SIZES FOR FEEDS TO UNIT PANEL. PROVIDE ACCURATE
 LOCATION OF ELECTRICAL PANEL. ALL PANEL SCHEDULES FOR
 THE UNITS STATE THAT THE PANEL IS IN THE UTILITY ROOM,
 BUT THIS IS NOT THE CASE. EDIT LOCATIONS IN PANEL
 SCHEDULES AND SHOW LOCATION ON PLAN TO CONFIRM CODE
 COMPLIANCE. REMOVE OR EDIT CLOUDS FROM PREVIOUS
 REVISIONS THAT BLOCK OTHER INFORMATION ON PLAN. WPB FBC
 107.2.1; NEC 220, 215.2, 215.5, 310.15(B)(16), 408.30,
 408.36
 131. SHEET E-224 SHOWS A 125 AMP PANEL FOR UNIT E. LOAD
 CALCULATION PROVIDED SHOWS A LOAD FOR THIS UNIT OF 157
 AMPS. PROVIDE CORRECTION. PROVIDE WIRE AND CONDUIT
 SIZES FOR FEEDS TO UNIT PANEL. PROVIDE ACCURATE
 LOCATION OF ELECTRICAL PANEL. ALL PANEL SCHEDULES FOR
 THE UNITS STATE THAT THE PANEL IS IN THE UTILITY ROOM,
 BUT THIS IS NOT THE CASE. EDIT LOCATIONS IN PANEL
 SCHEDULES AND SHOW LOCATION ON PLAN TO CONFIRM CODE
 COMPLIANCE. REMOVE OR EDIT CLOUDS FROM PREVIOUS
 REVISIONS THAT BLOCK OTHER INFORMATION ON PLAN. WPB FBC
 107.2.1; NEC 220, 215.2, 215.5, 310.15(B)(16), 408.30,
 408.36
 132. SHEET E-223 SHOWS A 125 AMP PANEL FOR UNIT D.
 PROVIDE WIRE AND CONDUIT SIZES FOR FEEDS TO UNIT PANEL.
 PROVIDE ACCURATE LOCATION OF ELECTRICAL PANEL. ALL
 PANEL SCHEDULES FOR THE UNITS STATE THAT THE PANEL IS
 IN THE UTILITY ROOM, BUT THIS IS NOT THE CASE. EDIT
 LOCATIONS IN PANEL SCHEDULES AND SHOW LOCATION ON PLAN
 TO CONFIRM CODE COMPLIANCE. REMOVE OR EDIT CLOUDS FROM
 PREVIOUS REVISIONS THAT BLOCK OTHER INFORMATION ON
 PLAN. WPB FBC 107.2.1; NEC 220, 215.2, 215.5,
 310.15(B)(16), 408.30, 408.36
 133. SHEET E-222 SHOWS A 125 AMP PANEL FOR UNIT C.
 PROVIDE WIRE AND CONDUIT SIZES FOR FEEDS TO UNIT PANEL.
 PROVIDE ACCURATE LOCATION OF ELECTRICAL PANEL. ALL
 PANEL SCHEDULES FOR THE UNITS STATE THAT THE PANEL IS
 IN THE UTILITY ROOM, BUT THIS IS NOT THE CASE. EDIT
 LOCATIONS IN PANEL SCHEDULES AND SHOW LOCATION ON PLAN
 TO CONFIRM CODE COMPLIANCE. REMOVE OR EDIT CLOUDS FROM
 PREVIOUS REVISIONS THAT BLOCK OTHER INFORMATION ON
 PLAN. WPB FBC 107.2.1; NEC 220, 215.2, 215.5,
 310.15(B)(16), 408.30, 408.36
 134. SHEET E-221 SHOWS A 125 AMP PANEL FOR UNIT B. LOAD
 CALCULATION PROVIDED SHOWS A LOAD FOR THIS UNIT OF 126
 AMPS. PROVIDE CORRECTION. PROVIDE WIRE AND CONDUIT
 SIZES FOR FEEDS TO UNIT PANEL. PROVIDE ACCURATE
 LOCATION OF ELECTRICAL PANEL. ALL PANEL SCHEDULES FOR
 THE UNITS STATE THAT THE PANEL IS IN THE UTILITY ROOM,
 BUT THIS IS NOT THE CASE. EDIT LOCATIONS IN PANEL
 SCHEDULES AND SHOW LOCATION ON PLAN TO CONFIRM CODE
 COMPLIANCE. REMOVE OR EDIT CLOUDS FROM PREVIOUS
 REVISIONS THAT BLOCK OTHER INFORMATION ON PLAN. WPB FBC
 107.2.1; NEC 220, 215.2, 215.5, 310.15(B)(16), 408.30,
 408.36
 135. SHEET E-220 SHOWS A 125 AMP PANEL FOR UNIT A.
 PROVIDE WIRE AND CONDUIT SIZES FOR FEEDS TO UNIT PANEL.
 PROVIDE ACCURATE LOCATION OF ELECTRICAL PANEL. ALL
 PANEL SCHEDULES FOR THE UNITS STATE THAT THE PANEL IS
 IN THE UTILITY ROOM, BUT THIS IS NOT THE CASE. EDIT
 LOCATIONS IN PANEL SCHEDULES AND SHOW LOCATION ON PLAN
 TO CONFIRM CODE COMPLIANCE. REMOVE OR EDIT CLOUDS FROM
 PREVIOUS REVISIONS THAT BLOCK OTHER INFORMATION ON
 PLAN. WPB FBC 107.2.1; NEC 220, 215.2, 215.5,
 310.15(B)(16), 408.30, 408.36
 136. SHEET E-230 SHOWS A 125 AMP PANEL FOR GUEST
 SUITES. PROVIDE LOAD CALCULATION FOR PANEL. PROVIDE
 WIRE AND CONDUIT SIZES FOR FEEDS TO UNIT PANEL. PROVIDE
 ACCURATE LOCATION OF ELECTRICAL PANEL. ALL PANEL
 SCHEDULES FOR THE UNITS STATE THAT THE PANEL IS IN THE
 UTILITY ROOM, BUT THIS IS NOT THE CASE. EDIT LOCATIONS
 IN PANEL SCHEDULES AND SHOW LOCATION ON PLAN TO CONFIRM
 CODE COMPLIANCE. REMOVE OR EDIT CLOUDS FROM PREVIOUS
 REVISIONS THAT BLOCK OTHER INFORMATION ON PLAN. WPB FBC
 107.2.1; NEC 220, 215.2, 215.5, 310.15(B)(16), 408.30,
 408.36
 137. IN REFERENCE TO PREVIOUS COMMENT 103, LOAD
 CALCULATION ON SHEET E-601A SHOWS A LOAD OF 54.2 AMPS
 FOR PANEL EOPH. SHEET E-602 SHOWS A LOAD OF 96 AMPS.
 CORRECT DISCREPANCY, UPDATE LOAD CALCULATION AS NEEDED.
 WPB FBC 107.2.1; NEC 220, 215.2, 215.5, 408.30, 408.36
 138. DIAGRAM ON SHEET E-501 SHOWS TWO PANELS IN EVERY
 UNIT WITH A TRANSFER SWITCH. THIS DETAIL IS NOT
 REFLECTED ANYWHERE ELSE IN PLAN. ENLARGED UNIT PLANS
 SHOULD SHOW CONTAIN THIS INFORMATION, INCLUDING WHAT
 LOADS ARE ON MAIN PANEL AND WHICH ARE ON EMERGENCY
 PANEL. SHOW LOCATION OF PANELS IN THE UNITS. PROVIDE
 DETAILS. WPB FBC 107.2.1; NEC 215.5, 220
 139. SHEET E-502 SHOWS A 1000 KW GENERATOR. LOAD
 CALCULATION PROVIDED ON SHEET E-601A SHOWS A LOAD OF
 1205 KVA ON EMERGENCY SYSTEM, AND A LOAD OF 200 KVA FOR
 FIRE PUMP, FOR A TOTAL OF 1405 KVA. THE LEGALLY
 REQUIRED GENERATOR MUST BE SIZED TO HANDLE ALL OF THIS
 LOAD. PROVIDE CORRECTION. NEC 695.3(D)(1), 701.4
 140. SHEET E-701, DETAILS 3, 4, AND 5 DO NOT IDENTIFY
 THE EQUIPMENT IN THE ELECTRICAL ROOMS. PROVIDE
 CORRECTION. WPB FBC 107.2.1
 141. PROVIDE LIGHT FIXTURE LEGEND AND SCHEDULE TO
 CORRESPOND WITH DRAWINGS. LIGHTING IN BATHTUB OR SHOWER
 AREAS SHALL BE SUITABLE FOR DAMP LOCATIONS. LIGHTING
 WITH OPEN OR PARTIALLY ENCLOSED LAMPS AND PENDANT
 LUMINAIRES OR LAMPHOLDERS SHALL NOT BE PERMITTED IN
 CLOTHES CLOSETS. NONE OF THESE ARE CLEAR ON PLAN,
 PROVIDE CORRECTION. NEC 410.10(D), 410.16.
 142. PROVIDE COMPLIANCE WITH FBC C402.5.8: RECESSED
 LUMINAIRES INSTALLED IN THE BUILDING THERMAL ENVELOPE
 SHALL BE ALL OF THE FOLLOWING:
  1.IC-RATED.
  2.LABELED AS HAVING AN AIR LEAKAGE RATE OF NOT MORE
 2.0 CFM (0.944 L/S) WHEN TESTED IN ACCORDANCE WITH ASTM
 E283 AT A 1.57 PSF (75 PA) PRESSURE DIFFERENTIAL.
  3.SEALED WITH A GASKET OR CAULK BETWEEN THE HOUSING
 AND INTERIOR WALL OR CEILING COVERING.
 143. PLEASE BE ADVISED THAT SOME OF THESE COMMENTS HAVE
 NOT BEEN ADDRESSED FOR TWO REVIEWS. IF UPON THE NEXT
 REVIEW, IF IT IS NECESSARY TO REJECT THE SUBMITTED PLAN
 AGAIN FOR THE SAME REASONS, AN ADDITIONAL PLAN REVIEW
 IS REQUIRED. FLORIDA STATUTES STATE: WITH RESPECT TO
 EVALUATION OF DESIGN PROFESSIONALS DOCUMENTS, IF A
 LOCAL GOVERNMENT FINDS IT NECESSARY, IN ORDER TO
 ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING CODE AND
 ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS REQUIRED BY
 THE CODE THREE OR MORE TIMES FOR FAILURE TO CORRECT A
 CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY NOTED IN
 EACH REJECTION, INCLUDING, BUT NOT LIMITED TO, EGRESS,
 FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY,
 ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL,
 MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER
 REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING
 COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL
 GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH
 REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION,
 A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE
 PERMIT FEE ATTRIBUTED TO PLANS REVIEW. FS 553.80(2)(B)
 THE ADDITIONAL FEE FOR THIS PROJECT WOULD BE
 $735,550.00
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER