| 2019-06-05 10:05:25 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | ELECTRICAL REVIEW STATUS: 3RD REVIEW, DENIED, SEE |
| | COMMENTS BELOW. |
| | |
| | BE ADVISED THAT THERE IS SO MUCH CONFLICTING AND |
| | INCOMPLETE INFORMATION ON THIS SUBMISSION THAT A FULL |
| | REVIEW WILL BE REQUIRED FOR THE NEXT REVIEW, LIKELY |
| | RESULTING IN FURTHER COMMENTS. |
| | |
| | PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED |
| | SATISFACTORILY HAVE BEEN REMOVED. PREVIOUS COMMENTS |
| | THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY HAVE |
| | ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW COMMENTS |
| | WILL BE LISTED AFTER PREVIOUS COMMENTS. |
| | |
| | |
| | 14. SHEET E-102B, CIRCUIT AL-17 IS SHOWN FEEDING THE |
| | TRATAM ROOM. WHAT IS THIS ROOM USED FOR, IS GFCI |
| | PROTECTION REQUIRED. PROVIDE CLARIFICATION AND/OR |
| | CORRECTION. NEC 210.8; WPB FBC 107.2.1 (RESPONSE |
| | RECEIVED STATES THAT GFCI PROTECTION IS NOT REQUIRED. I |
| | DISAGREE, SEE CODE SECTION STATED AT THE END OF THIS |
| | COMMENT. LOCKER ROOMS REQUIRE GFCI PROTECTION. PROVIDE |
| | CORRECTION. NEC 210.8(B)(7) ) |
| | 84. LIGHTING SHEETS (ALL) DO NOT SHOW THE AUTOMATIC |
| | CONTROL REQUIRED. PROVIDE THE ADDITIONAL AUTOMATIC |
| | LIGHTING CONTROLS STIPULATED IN THE FBC ENERGY CODE. |
| | FBC EC C405.2 (RESPONSE LETTER STATES THIS IS PROVIDED, |
| | BUT IT HAS NOT BEEN PROVIDED. NONE OF THE INTERIOR |
| | SPACES I CHECHED SHOW THE AUTOMATIC CONTROL REQUIRED. |
| | PROVIDE CORRECTION.) |
| | 85. PROVIDE GRAPH/CALCULATION OF EXTERIOR LIGHTING |
| | POWER ALLOWANCES PER THE FBC ENERGY CONSERVATION IN |
| | RELATION TO THE CONNECTED EXTERIOR LIGHTING PROPOSED TO |
| | COMPLY WITH CODE. FBC EC C405.5.1 (NOT SURE WHICH CODE |
| | BOOK YOU ARE LOOKING IN, BUT C405.6.2 AS MENTIONED IN |
| | YOUR RESPONSE IS NOT THE SECTION FROM THE CURRENT CODE |
| | THAT REQUIRES EXTERIOR LIGHTING COMPLIANCE. PROVIDE AS |
| | PREVIOUSLY REQUESTED.) |
| | 97. ON RISER DIAGRAM PANEL EQEH IS SHOWN AS A 1200 AMP |
| | PANEL. IN THE PANEL SCHEDULE FOR THIS PANEL, IT IS |
| | SHOWN AS AN 800 AMP PANEL. PROVIDE CORRECTION. WPB FBC |
| | 107.2.1 (STILL NOT CORRECTED. E-502 AND E-602 SHOW EQEH |
| | AS AN 800 AMP PANEL. LOAD CALCULATION ON E-601A STATES |
| | THIS IS A 1200 AMP PANEL WITH A LOAD OF 963 AMPS. |
| | PROVIDE CORRECTION.) |
| | 102. AS ADJUSTMENTS ARE MADE TO DISCREPANCIES IN PLAN, |
| | PROVIDE UPDATED LOAD CALCULATION FOR EACH PANEL AND |
| | SERVICE. NEC 220 (LOAD CALCULATION STILL NOT CORRECT OR |
| | COMPLETE, SEE NEW COMMENTS BELOW.) |
| | 103. SHEET E-601A, LOADS LISTED FOR LOAD CALCULATION |
| | SHOWN ARE MUCH DIFFERENT THAN THE LOADS SHOWN IN THE |
| | CORRESPONDING PANEL SCHEDULES. PROVIDE CLARIFICATION |
| | AND CORRECTION. WPB FBC 107.2.1; NEC 220 (THIS COMMENT |
| | NOT ADDRESSED SATISFACTORILY, SEE NEW COMMENTS.) |
| | 107. LOAD FOR PANEL H SHOWN IN PANEL SCHEDULE FOR PANEL |
| | MDP1 IS MUCH DIFFERENT THAN THE LOAD SHOWN IN THE PANEL |
| | SCHEDULE FOR PANEL H. PROVIDE CORRECTION. WPB FBC |
| | 107.2.1; NEC 220 (NOT CORRECTED, SEE NEW COMMENTS FOR |
| | FURTHER EXPLANATION.) |
| | 111. PROVIDE PANEL SCHEDULE FOR ALL PANELS. SOME ARE |
| | MISSING, SUCH AS RDEH AND RH. WPB FBC 107.2.1; NEC |
| | 408.4 (NOT ALL PANEL SCHEDULES PROVIDED.) |
| | |
| | NEW COMMENTS: |
| | |
| | 114. IN REFERENCE TO PREVIOUS COMMENT 103, LOAD FOR |
| | EQEH IS SHOWN IN ON E-601A AS 963 AMPS. PANEL SCHEDULE |
| | FOR EM ON SHEET E-602 SHOWS THIS IS BEING FED FROM AN |
| | 800 AMP BREAKER WITH THREE SETS OF 400 KCMIL AL WIRE, |
| | WHICH IS RATED FOR 810 AMPS. PROVIDE CORRECTION. NEC |
| | 215.2, 408.30, 408.36 |
| | 115. IN REFERENCE TO PREVIOUS COMMENT 103, LOAD |
| | CALCULATION ON SHEET E-601A SHOWS A LOAD OF 1451 AMPS |
| | FOR PANEL EM. SHEET E-602 SHOWS A LOAD OF 557 AMPS FOR |
| | THE SAME PANEL. CORRECT DISCREPANCY, UPDATE LOAD |
| | CALCULATION AS NEEDED. WPB FBC 107.2.1; NEC 220, 215.2, |
| | 215.5, 408.30, 408.36 |
| | 116. IN REFERENCE TO PREVIOUS COMMENT 103, LOAD |
| | CALCULATION ON SHEET E-601A SHOWS A 3RD LOAD ON THE 480 |
| | VOLT SERVICE FOR RETAILS. THIS IS NOT SHOWN ON RISER |
| | DIAGRAM OR ANY OTHER LOCATION. PROVIDE DETAILS. WPB FBC |
| | 107.2.1 |
| | 117. IN REFERENCE TO PREVIOUS COMMENT 103, LOAD |
| | CALCULATION ON SHEET E-601A SHOWS A LOAD OF 596 AMPS |
| | FOR MDP1. ON SHEET E-605, THIS PANEL SHOWS A LOAD OF |
| | 1101 AMPS. CORRECT DISCREPANCY, UPDATE LOAD CALCULATION |
| | AS NEEDED. NEC 220; WPB FBC 107.2.1 |
| | 118. SHEET E-601A SHOWS MDP1 AS AN 800 AMP PANEL. |
| | SHEETS E-502 AND E-605 SHOW IT AS 1200 AMP. CORRECT |
| | DISCREPANCY, UPDATE LOAD CALCULATION AS NEEDED. WPB FBC |
| | 107.2.1; NEC 220, 215.2, 215.5, 408.30, 408.36 |
| | 119. IN REFERENCE TO PREVIOUS COMMENT 103, LOAD |
| | CALCULATION ON SHEET E-601A SHOWS A LOAD OF 481 AMPS IN |
| | PANEL SCHEDULE FOR MDP1. SHEET E-605 SHOWS A LOAD OF |
| | 872 AMPS FOR THIS PANEL. WPB FBC 107.2.1; NEC 220, |
| | 215.2, 215.5, 408.30, 408.36 |
| | 120. SHEET E-601A SHOWS PANEL H FED FROM MDP1 ON A 700 |
| | AMP BREAKER, AND THE FEEDERS AS THREE SETS OF 350 AL |
| | KCMIL, WHICH IS RATED FOR 750 AMPS. CORRECT CONDUCTOR |
| | AND BREAKER SIZE TO MATCH RESULTS FROM COMMENT 119. NEC |
| | 220, 215.2, 215.5, 310.15(B)(16), 408.30, 408.36 |
| | 121. PANEL SCHEDULE FOR PANEL GMP SHOWS A LOAD NAMED TE |
| | THAT IS 408 KVA. PROVIDE DETAILS AND PANEL SCHEDULE, |
| | UPDATE LOAD CALCULATION AS NEEDED. SHEET E-601A SHOWS A |
| | LOAD OF 360 KVA FOR EDPH, A LOAD OF 800 KVA FOR EQEH, |
| | AND A LOAD OF 45 KVA FOR EOPH. WHEN THIS IS ADDED TO |
| | THE LOAD OF 408 KVA FOR TE, THE GENERATOR WOULD BE |
| | OVERLOADED. PROVIDE CLAIFICATIONS AND CORRECTIONS AS |
| | NEEDED. WPB FBC 107.2.1; NEC 220, 215.2, 215.5, 408.30, |
| | 408.36 |
| | 122. IN REFERENCE TO PREVIOUS COMMENT 103, LOAD |
| | CALCULATION ON SHEET E-601A SHOWS A LOAD OF 433.5 AMPS |
| | FOR PANEL EDPH. SHEET E-602 SHOWS A LOAD OF 179 AMPS. |
| | CORRECT DISCREPANCY, UPDATE LOAD CALCULATION AS NEEDED. |
| | WPB FBC 107.2.1; NEC 220, 215.2, 215.5, 408.30, 408.36 |
| | 123. PROVIDE VOLTAGE DROP CALCULATIONS TO COMPLY WITH |
| | CODE FOR ENTIRE SYSTEM. CURRENTLY, THE ONLY VOLTAGE |
| | DROP PROVIDED IS FOR THE LOADS ON SHEET E-601. NONE OF |
| | THE LOADS ON SHEET E-601A SHOW THE VOLTAGE DROP |
| | CALCULATIONS. PROVIDE CORRECTION. FBC EC C405.6.3 |
| | 124. PROVIDE BLOCK NOTE INDICATING COMPLIANCE: WITHIN |
| | 30 DAYS AFTER THE DATE OF SYSTEM ACCEPTANCE, RECORD |
| | DRAWINGS OF THE ACTUAL INSTALLATION SHALL BE PROVIDE TO |
| | THE BUILDING OWNER, INCLUDING: 1. A SINGLE LINE DIAGRAM |
| | OF THE BUILDING ELECTRICAL DISTRIBUTION SYSTEM AND 2. |
| | FLOOR PLANS INDICATING LOCATION AND AREA SERVED FOR ALL |
| | DISTRIBUTION. FBC EC C405.6.4.1 |
| | 125. NO LOAD CALCULATION FOR GUEST SUITES IS PROVIDED |
| | OR INCLUDED IN THE LOAD CALCULATION ON SHEET E-601 FOR |
| | METER CENTER 1 / PANEL L. PROVIDE CORRECTION. WPB FBC |
| | 107.2.1; NEC 220, 215.2, 215.5, 408.30, 408.36 |
| | 126. SHEET E-501 AND E-502 ARE NAMED RESIDENTIAL POWER |
| | RISER DIAGRAM. ONLY ONE OF THEM IS THE RESIDENTIAL |
| | PORTION, THE OTHER IS NOT. PROVIDE DISTINCT NAME FOR |
| | PLAN SHEET FOR CLARITY. WPB FBC 107.2.1 |
| | 127. SHEET E-229 SHOWS A 125 AMP PANEL FOR PH-D. LOAD |
| | CALCULATION PROVIDED SHOWS A LOAD FOR THIS UNIT OF 272 |
| | AMPS. PROVIDE CORRECTION. PROVIDE WIRE AND CONDUIT |
| | SIZES FOR FEEDS TO UNIT PANEL. PROVIDE ACCURATE |
| | LOCATION OF ELECTRICAL PANEL. ALL PANEL SCHEDULES FOR |
| | THE UNITS STATE THAT THE PANEL IS IN THE UTILITY ROOM, |
| | BUT THIS IS NOT THE CASE. EDIT LOCATIONS IN PANEL |
| | SCHEDULES AND SHOW LOCATION ON PLAN TO CONFIRM CODE |
| | COMPLIANCE. REMOVE OR EDIT CLOUDS FROM PREVIOUS |
| | REVISIONS THAT BLOCK OTHER INFORMATION ON PLAN. WPB FBC |
| | 107.2.1; NEC 220, 215.2, 215.5, 310.15(B)(16), 408.30, |
| | 408.36 |
| | 128. SHEET E-227 AND E-228 SHOWS A 125 AMP PANEL FOR |
| | PH-B AND PH-C. LOAD CALCULATION PROVIDED SHOWS A LOAD |
| | FOR THIS UNIT OF 202 AND 200 AMPS, RESPCTIVELY. PROVIDE |
| | CORRECTION. PROVIDE WIRE AND CONDUIT SIZES FOR FEEDS TO |
| | UNIT PANEL. PROVIDE ACCURATE LOCATION OF ELECTRICAL |
| | PANEL. ALL PANEL SCHEDULES FOR THE UNITS STATE THAT THE |
| | PANEL IS IN THE UTILITY ROOM, BUT THIS IS NOT THE CASE. |
| | EDIT LOCATIONS IN PANEL SCHEDULES AND SHOW LOCATION ON |
| | PLAN TO CONFIRM CODE COMPLIANCE. REMOVE OR EDIT CLOUDS |
| | FROM PREVIOUS REVISIONS THAT BLOCK OTHER INFORMATION ON |
| | PLAN. WPB FBC 107.2.1; NEC 220, 215.2, 215.5, |
| | 310.15(B)(16), 408.30, 408.36 |
| | 129. SHEET E-226 SHOWS A 125 AMP PANEL FOR PH-A. LOAD |
| | CALCULATION PROVIDED SHOWS A LOAD FOR THIS UNIT OF 190 |
| | AMPS. PROVIDE CORRECTION. PROVIDE WIRE AND CONDUIT |
| | SIZES FOR FEEDS TO UNIT PANEL. PROVIDE ACCURATE |
| | LOCATION OF ELECTRICAL PANEL. ALL PANEL SCHEDULES FOR |
| | THE UNITS STATE THAT THE PANEL IS IN THE UTILITY ROOM, |
| | BUT THIS IS NOT THE CASE. EDIT LOCATIONS IN PANEL |
| | SCHEDULES AND SHOW LOCATION ON PLAN TO CONFIRM CODE |
| | COMPLIANCE. REMOVE OR EDIT CLOUDS FROM PREVIOUS |
| | REVISIONS THAT BLOCK OTHER INFORMATION ON PLAN. WPB FBC |
| | 107.2.1; NEC 220, 215.2, 215.5, 310.15(B)(16), 408.30, |
| | 408.36 |
| | 130. SHEET E-225 SHOWS A 125 AMP PANEL FOR UNIT F. LOAD |
| | CALCULATION PROVIDED SHOWS A LOAD FOR THIS UNIT OF 154 |
| | AMPS. PROVIDE CORRECTION. PROVIDE WIRE AND CONDUIT |
| | SIZES FOR FEEDS TO UNIT PANEL. PROVIDE ACCURATE |
| | LOCATION OF ELECTRICAL PANEL. ALL PANEL SCHEDULES FOR |
| | THE UNITS STATE THAT THE PANEL IS IN THE UTILITY ROOM, |
| | BUT THIS IS NOT THE CASE. EDIT LOCATIONS IN PANEL |
| | SCHEDULES AND SHOW LOCATION ON PLAN TO CONFIRM CODE |
| | COMPLIANCE. REMOVE OR EDIT CLOUDS FROM PREVIOUS |
| | REVISIONS THAT BLOCK OTHER INFORMATION ON PLAN. WPB FBC |
| | 107.2.1; NEC 220, 215.2, 215.5, 310.15(B)(16), 408.30, |
| | 408.36 |
| | 131. SHEET E-224 SHOWS A 125 AMP PANEL FOR UNIT E. LOAD |
| | CALCULATION PROVIDED SHOWS A LOAD FOR THIS UNIT OF 157 |
| | AMPS. PROVIDE CORRECTION. PROVIDE WIRE AND CONDUIT |
| | SIZES FOR FEEDS TO UNIT PANEL. PROVIDE ACCURATE |
| | LOCATION OF ELECTRICAL PANEL. ALL PANEL SCHEDULES FOR |
| | THE UNITS STATE THAT THE PANEL IS IN THE UTILITY ROOM, |
| | BUT THIS IS NOT THE CASE. EDIT LOCATIONS IN PANEL |
| | SCHEDULES AND SHOW LOCATION ON PLAN TO CONFIRM CODE |
| | COMPLIANCE. REMOVE OR EDIT CLOUDS FROM PREVIOUS |
| | REVISIONS THAT BLOCK OTHER INFORMATION ON PLAN. WPB FBC |
| | 107.2.1; NEC 220, 215.2, 215.5, 310.15(B)(16), 408.30, |
| | 408.36 |
| | 132. SHEET E-223 SHOWS A 125 AMP PANEL FOR UNIT D. |
| | PROVIDE WIRE AND CONDUIT SIZES FOR FEEDS TO UNIT PANEL. |
| | PROVIDE ACCURATE LOCATION OF ELECTRICAL PANEL. ALL |
| | PANEL SCHEDULES FOR THE UNITS STATE THAT THE PANEL IS |
| | IN THE UTILITY ROOM, BUT THIS IS NOT THE CASE. EDIT |
| | LOCATIONS IN PANEL SCHEDULES AND SHOW LOCATION ON PLAN |
| | TO CONFIRM CODE COMPLIANCE. REMOVE OR EDIT CLOUDS FROM |
| | PREVIOUS REVISIONS THAT BLOCK OTHER INFORMATION ON |
| | PLAN. WPB FBC 107.2.1; NEC 220, 215.2, 215.5, |
| | 310.15(B)(16), 408.30, 408.36 |
| | 133. SHEET E-222 SHOWS A 125 AMP PANEL FOR UNIT C. |
| | PROVIDE WIRE AND CONDUIT SIZES FOR FEEDS TO UNIT PANEL. |
| | PROVIDE ACCURATE LOCATION OF ELECTRICAL PANEL. ALL |
| | PANEL SCHEDULES FOR THE UNITS STATE THAT THE PANEL IS |
| | IN THE UTILITY ROOM, BUT THIS IS NOT THE CASE. EDIT |
| | LOCATIONS IN PANEL SCHEDULES AND SHOW LOCATION ON PLAN |
| | TO CONFIRM CODE COMPLIANCE. REMOVE OR EDIT CLOUDS FROM |
| | PREVIOUS REVISIONS THAT BLOCK OTHER INFORMATION ON |
| | PLAN. WPB FBC 107.2.1; NEC 220, 215.2, 215.5, |
| | 310.15(B)(16), 408.30, 408.36 |
| | 134. SHEET E-221 SHOWS A 125 AMP PANEL FOR UNIT B. LOAD |
| | CALCULATION PROVIDED SHOWS A LOAD FOR THIS UNIT OF 126 |
| | AMPS. PROVIDE CORRECTION. PROVIDE WIRE AND CONDUIT |
| | SIZES FOR FEEDS TO UNIT PANEL. PROVIDE ACCURATE |
| | LOCATION OF ELECTRICAL PANEL. ALL PANEL SCHEDULES FOR |
| | THE UNITS STATE THAT THE PANEL IS IN THE UTILITY ROOM, |
| | BUT THIS IS NOT THE CASE. EDIT LOCATIONS IN PANEL |
| | SCHEDULES AND SHOW LOCATION ON PLAN TO CONFIRM CODE |
| | COMPLIANCE. REMOVE OR EDIT CLOUDS FROM PREVIOUS |
| | REVISIONS THAT BLOCK OTHER INFORMATION ON PLAN. WPB FBC |
| | 107.2.1; NEC 220, 215.2, 215.5, 310.15(B)(16), 408.30, |
| | 408.36 |
| | 135. SHEET E-220 SHOWS A 125 AMP PANEL FOR UNIT A. |
| | PROVIDE WIRE AND CONDUIT SIZES FOR FEEDS TO UNIT PANEL. |
| | PROVIDE ACCURATE LOCATION OF ELECTRICAL PANEL. ALL |
| | PANEL SCHEDULES FOR THE UNITS STATE THAT THE PANEL IS |
| | IN THE UTILITY ROOM, BUT THIS IS NOT THE CASE. EDIT |
| | LOCATIONS IN PANEL SCHEDULES AND SHOW LOCATION ON PLAN |
| | TO CONFIRM CODE COMPLIANCE. REMOVE OR EDIT CLOUDS FROM |
| | PREVIOUS REVISIONS THAT BLOCK OTHER INFORMATION ON |
| | PLAN. WPB FBC 107.2.1; NEC 220, 215.2, 215.5, |
| | 310.15(B)(16), 408.30, 408.36 |
| | 136. SHEET E-230 SHOWS A 125 AMP PANEL FOR GUEST |
| | SUITES. PROVIDE LOAD CALCULATION FOR PANEL. PROVIDE |
| | WIRE AND CONDUIT SIZES FOR FEEDS TO UNIT PANEL. PROVIDE |
| | ACCURATE LOCATION OF ELECTRICAL PANEL. ALL PANEL |
| | SCHEDULES FOR THE UNITS STATE THAT THE PANEL IS IN THE |
| | UTILITY ROOM, BUT THIS IS NOT THE CASE. EDIT LOCATIONS |
| | IN PANEL SCHEDULES AND SHOW LOCATION ON PLAN TO CONFIRM |
| | CODE COMPLIANCE. REMOVE OR EDIT CLOUDS FROM PREVIOUS |
| | REVISIONS THAT BLOCK OTHER INFORMATION ON PLAN. WPB FBC |
| | 107.2.1; NEC 220, 215.2, 215.5, 310.15(B)(16), 408.30, |
| | 408.36 |
| | 137. IN REFERENCE TO PREVIOUS COMMENT 103, LOAD |
| | CALCULATION ON SHEET E-601A SHOWS A LOAD OF 54.2 AMPS |
| | FOR PANEL EOPH. SHEET E-602 SHOWS A LOAD OF 96 AMPS. |
| | CORRECT DISCREPANCY, UPDATE LOAD CALCULATION AS NEEDED. |
| | WPB FBC 107.2.1; NEC 220, 215.2, 215.5, 408.30, 408.36 |
| | 138. DIAGRAM ON SHEET E-501 SHOWS TWO PANELS IN EVERY |
| | UNIT WITH A TRANSFER SWITCH. THIS DETAIL IS NOT |
| | REFLECTED ANYWHERE ELSE IN PLAN. ENLARGED UNIT PLANS |
| | SHOULD SHOW CONTAIN THIS INFORMATION, INCLUDING WHAT |
| | LOADS ARE ON MAIN PANEL AND WHICH ARE ON EMERGENCY |
| | PANEL. SHOW LOCATION OF PANELS IN THE UNITS. PROVIDE |
| | DETAILS. WPB FBC 107.2.1; NEC 215.5, 220 |
| | 139. SHEET E-502 SHOWS A 1000 KW GENERATOR. LOAD |
| | CALCULATION PROVIDED ON SHEET E-601A SHOWS A LOAD OF |
| | 1205 KVA ON EMERGENCY SYSTEM, AND A LOAD OF 200 KVA FOR |
| | FIRE PUMP, FOR A TOTAL OF 1405 KVA. THE LEGALLY |
| | REQUIRED GENERATOR MUST BE SIZED TO HANDLE ALL OF THIS |
| | LOAD. PROVIDE CORRECTION. NEC 695.3(D)(1), 701.4 |
| | 140. SHEET E-701, DETAILS 3, 4, AND 5 DO NOT IDENTIFY |
| | THE EQUIPMENT IN THE ELECTRICAL ROOMS. PROVIDE |
| | CORRECTION. WPB FBC 107.2.1 |
| | 141. PROVIDE LIGHT FIXTURE LEGEND AND SCHEDULE TO |
| | CORRESPOND WITH DRAWINGS. LIGHTING IN BATHTUB OR SHOWER |
| | AREAS SHALL BE SUITABLE FOR DAMP LOCATIONS. LIGHTING |
| | WITH OPEN OR PARTIALLY ENCLOSED LAMPS AND PENDANT |
| | LUMINAIRES OR LAMPHOLDERS SHALL NOT BE PERMITTED IN |
| | CLOTHES CLOSETS. NONE OF THESE ARE CLEAR ON PLAN, |
| | PROVIDE CORRECTION. NEC 410.10(D), 410.16. |
| | 142. PROVIDE COMPLIANCE WITH FBC C402.5.8: RECESSED |
| | LUMINAIRES INSTALLED IN THE BUILDING THERMAL ENVELOPE |
| | SHALL BE ALL OF THE FOLLOWING: |
| | 1.IC-RATED. |
| | 2.LABELED AS HAVING AN AIR LEAKAGE RATE OF NOT MORE |
| | 2.0 CFM (0.944 L/S) WHEN TESTED IN ACCORDANCE WITH ASTM |
| | E283 AT A 1.57 PSF (75 PA) PRESSURE DIFFERENTIAL. |
| | 3.SEALED WITH A GASKET OR CAULK BETWEEN THE HOUSING |
| | AND INTERIOR WALL OR CEILING COVERING. |
| | 143. PLEASE BE ADVISED THAT SOME OF THESE COMMENTS HAVE |
| | NOT BEEN ADDRESSED FOR TWO REVIEWS. IF UPON THE NEXT |
| | REVIEW, IF IT IS NECESSARY TO REJECT THE SUBMITTED PLAN |
| | AGAIN FOR THE SAME REASONS, AN ADDITIONAL PLAN REVIEW |
| | IS REQUIRED. FLORIDA STATUTES STATE: WITH RESPECT TO |
| | EVALUATION OF DESIGN PROFESSIONALS DOCUMENTS, IF A |
| | LOCAL GOVERNMENT FINDS IT NECESSARY, IN ORDER TO |
| | ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING CODE AND |
| | ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS REQUIRED BY |
| | THE CODE THREE OR MORE TIMES FOR FAILURE TO CORRECT A |
| | CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY NOTED IN |
| | EACH REJECTION, INCLUDING, BUT NOT LIMITED TO, EGRESS, |
| | FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY, |
| | ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL, |
| | MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER |
| | REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING |
| | COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL |
| | GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH |
| | REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION, |
| | A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE |
| | PERMIT FEE ATTRIBUTED TO PLANS REVIEW. FS 553.80(2)(B) |
| | THE ADDITIONAL FEE FOR THIS PROJECT WOULD BE |
| | $735,550.00 |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY |
| | REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED |
| | SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD |
| | SHEETS. |
| | |
| | SINCERELY, |
| | |
| | JOHN PEARSON |
| | ELECTRICAL PLANS EXAMINER |
| | 561-805-6746 |
| | [email protected] |
| | |
| | |