| 2019-03-11 09:08:32 | SAMANTHA HILL |
| | BUILDING PLANS EXAMINER |
| | [email protected] |
| | 561-805-6724 |
| | |
| | 1. ARCHITECTURAL PAGES LACK THE ARCHITECT BUSINESS |
| | NUMBER (AA26000733) WHICH IS REQUIRED TO BE ON EVERY |
| | PAGE PER FS481. PLEASE ADD TO ALL PAGES, BUT DO NOT |
| | RESUBMIT THESE PAGES UNLESS THERE ARE OTHER CHANGES. |
| | |
| | ARCHITECT'S DIGITAL SIGNATURE OK (ANDREW WYLIE BURNETT, |
| | AR98495) |
| | |
| | 2. CIVIL PAGES LACK THE CERTIFICATE OF AUTHORIZATION |
| | NUMBER REQUIRED PER FS471. AS KIMLEY HORN HAS MORE THAN |
| | ONE, IT IS NOT CLEAR THROUGH WHIH COMPANY THIS IS BEING |
| | SIGNED AND SEALED. REVISE ALL PAGES TO INCLUDE, BUT |
| | RESUBMIT ONLY ONE PAGE UNLESS THERE ARE CHANGES AS A |
| | RESULT OF A PLAN REVIEW COMMENT. |
| | |
| | CIVIL ENGINEER'S DIGITAL SIGNATURE OK (MICHAEL DAVID |
| | SPRUCE, PE52776) |
| | |
| | 3. STRUCTURAL PAGES OK (BRAD W. MALMSTEN, PE 71012, |
| | THORNTON TOMASETTI, CA7519) |
| | |
| | 4. FIRE PROTECTION PAGES LACK THE CERTIFICATE OF |
| | AUTHORIZATION NUMBER REQUIRED PER FS471 FOR STANTEC |
| | CONSULTING SERVICES INC. (APPEARS TO BE CA27013 AS THE |
| | OTHERS ARE NULL AND VOID OR CLOSED). REVISE ALL PAGES |
| | TO INCLUDE, BUT RESUBMIT ONLY ONE PAGE UNLESS THERE ARE |
| | CHANGES AS A RESULT OF A PLAN REVIEW COMMENT. |
| | |
| | FP PAGES DIGITAL SIGNATURE OK (MATTHEW DONOLLI, |
| | PE56407) |
| | |
| | 5. PLUMBING, MECHANICAL, ELECTRICAL, FIRE ALARM PAGES |
| | LACK THE CERTIFICATE OF AUTHORIZATION NUMBER REQUIRED |
| | PER FS471 FOR STANTEC CONSULTING SERVICES INC. (APPEARS |
| | TO BE CA27013 AS THE OTHERS ARE NULL AND VOID OR |
| | CLOSED). REVISE ALL PAGES TO INCLUDE, BUT RESUBMIT ONLY |
| | ONE PAGE UNLESS THERE ARE CHANGES AS A RESULT OF A PLAN |
| | REVIEW COMMENT. |
| | |
| | ELECTRICAL, PLUMBING AND MECHANICAL PAGES UPLOADED |
| | 8/31/18 DIGITAL SIGNATURE OK (MATTHEW DONOLLI, PE56407) |
| | ALL FIRE ALARM PAGES DIGITAL SIGNATURE OK (MATTHEW |
| | DONOLLI, PE56407) |
| | |
| | THE FOLLOWING PAGES HAVE AN INVALID SIGNATURE: |
| | P100, P101A, P101B, 102B, OTHERS |
| | IT APPEARS THAT THE PAGES UPLOADED ON 1/12, 1/14 & 1/15 |
| | HAVE AN INVALID SIGNATURE. |
| | |
| | 6. DIGITAL SIGNATURES SUBMITTED NEXT REVIEW CYCLE |
| | REQUIRE REVIEW. |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| 2019-02-12 09:19:45 | 2ND SUBMITTAL: ELECTRICAL SHEETS OK. |