Date Text
2019-02-13 09:58:43 
 2ND REVIEW: 18011528
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS: PREVIOUS COMMENTS.
 1. COMPLIED
 2. COMPLIED
 A) COMPLIED
 A) COMPLIED
 B) LABEL ALL CLEAR FLOOR SPACE WITH DIMENSIONS PER ANSI
 A117.1-1986 4.17.3 AND4.19.2.2 AND FHA REQUIREMENT #7
 ON ALL ENLARGED BATHROOM FLOOR PLANS PLEASE EITHER NOTE
 NEXT TO OR ON, PLACE THE DIMENSIONS ON THE CLEAR FLOOR
 SPACE.
 C) COMPLIED
 3. COMPLIED
 4. COMPLIED
 5. COMPLIED
 6. THE LINE FOR THE INTERIOR WALLS AND FIXTURES ARE
 EXTREMELY LIGHT SOME PLUMBING FIXTURES ARE MISSING ON
 THE FLOOR PLANS PLEASE DARKEN LINES AND INCLUDE FIXTURE
 ON ALL FLOOR PLAN SHEETS. PER WPB AMEND TO FBC THE GRID
 LINES ARE SO DARK AND THE LINES FOR THE WALLS ARE SO
 LIGHT IT IS EXTREMELY DEFAULT TO READ THE PLAN PLEASE
 CLARIFY.
 7. COMPLIED
 8. COMPLIED
 9.COMPLIED
 10. COMPLIED
 11. COMPLIED
 12. COMPLIED
 13. SHT A-790/ A-791/ A-792 THE DRAWING ARE EXTREMELY
 LIGHT PLEASE DARKEN. PER WPB AMEND TO FBC 107.2.1
 14. COMPLIED
 15. PROVIDE MANUFACTURE SPECIFICATION FOR RUBBERIZED
 SHOWER PAN LINER TO COMPLY WITH FBC PL 417.5.2-
 417.5.2.6
 16. PROVIDE DETAIL FOR EMERGENCY SCUPPER WITH
 DIMENSIONS. PER WPB AMEND TO FBC 107.2.1SHT. A-809
 DETAIL #2 DID NOT GIVE THE WIDTH DIMENSIONS PLEASE
 CLARIFY.
 17. COMPLIED
 18. COMPLIED
 19. COMPLIED
  
 NEW COMMENTS:
  
 1. SHT. A-772 DETAIL #12 TYPE 10 BATHROOM, THE CLEAR
 FLOOR SPACE FOR THE SHOWER SHALL RUN PARALLEL TO THE
 FIXTURE AND THE END LINE UP WITH THE CONTROL WALL. PER
 FHA DESIGN MANUAL REQUIREMENT #7 PG. 7.56
 2. PLEASE SHOW THE CLEAR FLOOR SPACE WITH DIMENSIONS
 FOR THE TOILETS IN THE FHA BATHROOMS ON THE UNIT
 BATHROOM PLAN SHEETS. PER FHA DESIGN MANUAL REQ. #7
 PG.7.43
 3.SHT A-774 THE GUEST SUITES SHALL COMPLY WITH FAIR
 HOUSING PLEASE INDICATE DESIGN SPEC FOR THE BATHROOMS A
 OR B PER FHA DESIGN MANUAL REQUIREMENT #7
 4.SHT. A-221 SHOWS BATHROOM TYPE 2 AS THE FHA SPEC B
 BATHROOM SHT A-771 SHOWS THE TYPE # AS THE FHA BATHROOM
 AND SHT G-5 LIST TYPE 3 PLEASE CLARIFY. PER WPB AMEND
 TO FBC 107.2.1
 5. SHT. A-222 INDICATE ON THE PLAN WHICH IS THE FHA
 BATHROOM. PER WPB AMEND TO FBC 107.2.1
 6.SHT. A-222 UNIT C IF FHA SPEC A IS USED ALL THE
 BATHROOMS SHALL COMPLY. PER FHA REQUIREMENT #7 PG. 7.34
 AND 7.35
 7.SHT. A-222,223,224,225,226 INDICATE TYPE FHA BATHROOM
 . PER FHA REQUIREMENT #7
 8.SHT. A-229A INDICATE ON THE PLAN WHICH BATHROOM IS
 THE FHA BATHROOM PER FHA REQUIREMENT #7
 9. SHT. A-770, 771, 772,773, 774 PLEASE INDICATE ON THE
 PLAN WHERE THE GRAB BAR BACKING IS REQUIRED ALL
 BATHROOMS EXCEPT THE POWDER ROOM SHALL HAVE IT. PER FHA
 DESIGN MANUAL REQ. #6
 10.ANY WING WALL OR VANITY NEXT TO THE TOILET IN THE
 FHA BATHROOMS SHALL NOT EXTEND OVER 24" FROM THE BACK
 WALL. PER FHA DESIGN MANUAL REQ. #7 PG. 7.43
 11.PLEASE PROVIDE A DETAIL FOR THE GREASE INTERCEPTOR
 PIPING AND MOUNTING SYSTEM. PER WPB AMEND TO FBC
 107.2.1
 12. PLEASE PROVIDE MANUFACTURE SPECIFICATIONS AND
 INSTILLATION GUIDE FOR THE GREASE INTERCEPTOR. PER WPB
 AMEND TO FBC 107.2.1
 13. PROVIDE SIZING CALCULATION FROM THE MANUFACTURE FOR
 THE GREASE INTERCEPTOR. PER WPB AMEND TO FBC 107.2.1
 AND FBC PL 1003.2
 14. SHT. P-502 LABEL ALL WATER PIPING WITH HOT , COLD,
 RETURN AND UNIT TYPE. PER WPB AMEND TO FBC 107.2.1
 15. SHT P-502 THE SANITARY RISER DIAGRAM IS DO
 DIFFICULT TO DETERMINE CODE COMPLIANCE PLEASE PROVIDE A
 3 DIMENSIONAL ISOMETRIC DRAWING FOR THE UNDERGROUND
 COLLECTION PIPING AND SEPARATE SOIL STACK ISOMETRICS.
 PER WPB AMEND TO FBC 107.2.1
 16. FOR THE FUEL OIL SYSTEM PLEASE SUBMIT THE
 FOLLOWING:
 A)MANUFACTURES SPECIFICATION FOR ALL EQUIPMENT BEING
 USED ON FUEL OIL SYSTEM INCLUDING TANK.
 B) A FLOOR PLAN AND ISOMETRIC DRAWING OF THE PIPING AND
 TANK.
 PER WPB AMEND TO FBC 107.2.1
 THE FUEL OIL SYSTEM CAN BE SUBMITTED AS A SEPARATE
 PERMIT IF THAT IS YOUR INTENT PLEASE REMOVE ANY DETAILS
 OR DRAWING FROM THE MASTER SET.
 17. PROVIDE AN ENLARGED FLOOR PLAN FOR ALL BOILER AND
 PUMP ROOMS ON THE 1ST AND 23RD FLOORS AND PIPING
 DETAIL. PER WPB AMEND TO FBC 107.2.1
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]