| 2019-02-13 09:58:43 | |
| | 2ND REVIEW: 18011528 |
| | 2017 FLORIDA BUILDING CODE 6TH EDITION |
| | 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH |
| | EDITION |
| | 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH |
| | EDITION |
| | 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH |
| | EDITION |
| | |
| | PLUMBING COMMENTS: PREVIOUS COMMENTS. |
| | 1. COMPLIED |
| | 2. COMPLIED |
| | A) COMPLIED |
| | A) COMPLIED |
| | B) LABEL ALL CLEAR FLOOR SPACE WITH DIMENSIONS PER ANSI |
| | A117.1-1986 4.17.3 AND4.19.2.2 AND FHA REQUIREMENT #7 |
| | ON ALL ENLARGED BATHROOM FLOOR PLANS PLEASE EITHER NOTE |
| | NEXT TO OR ON, PLACE THE DIMENSIONS ON THE CLEAR FLOOR |
| | SPACE. |
| | C) COMPLIED |
| | 3. COMPLIED |
| | 4. COMPLIED |
| | 5. COMPLIED |
| | 6. THE LINE FOR THE INTERIOR WALLS AND FIXTURES ARE |
| | EXTREMELY LIGHT SOME PLUMBING FIXTURES ARE MISSING ON |
| | THE FLOOR PLANS PLEASE DARKEN LINES AND INCLUDE FIXTURE |
| | ON ALL FLOOR PLAN SHEETS. PER WPB AMEND TO FBC THE GRID |
| | LINES ARE SO DARK AND THE LINES FOR THE WALLS ARE SO |
| | LIGHT IT IS EXTREMELY DEFAULT TO READ THE PLAN PLEASE |
| | CLARIFY. |
| | 7. COMPLIED |
| | 8. COMPLIED |
| | 9.COMPLIED |
| | 10. COMPLIED |
| | 11. COMPLIED |
| | 12. COMPLIED |
| | 13. SHT A-790/ A-791/ A-792 THE DRAWING ARE EXTREMELY |
| | LIGHT PLEASE DARKEN. PER WPB AMEND TO FBC 107.2.1 |
| | 14. COMPLIED |
| | 15. PROVIDE MANUFACTURE SPECIFICATION FOR RUBBERIZED |
| | SHOWER PAN LINER TO COMPLY WITH FBC PL 417.5.2- |
| | 417.5.2.6 |
| | 16. PROVIDE DETAIL FOR EMERGENCY SCUPPER WITH |
| | DIMENSIONS. PER WPB AMEND TO FBC 107.2.1SHT. A-809 |
| | DETAIL #2 DID NOT GIVE THE WIDTH DIMENSIONS PLEASE |
| | CLARIFY. |
| | 17. COMPLIED |
| | 18. COMPLIED |
| | 19. COMPLIED |
| | |
| | NEW COMMENTS: |
| | |
| | 1. SHT. A-772 DETAIL #12 TYPE 10 BATHROOM, THE CLEAR |
| | FLOOR SPACE FOR THE SHOWER SHALL RUN PARALLEL TO THE |
| | FIXTURE AND THE END LINE UP WITH THE CONTROL WALL. PER |
| | FHA DESIGN MANUAL REQUIREMENT #7 PG. 7.56 |
| | 2. PLEASE SHOW THE CLEAR FLOOR SPACE WITH DIMENSIONS |
| | FOR THE TOILETS IN THE FHA BATHROOMS ON THE UNIT |
| | BATHROOM PLAN SHEETS. PER FHA DESIGN MANUAL REQ. #7 |
| | PG.7.43 |
| | 3.SHT A-774 THE GUEST SUITES SHALL COMPLY WITH FAIR |
| | HOUSING PLEASE INDICATE DESIGN SPEC FOR THE BATHROOMS A |
| | OR B PER FHA DESIGN MANUAL REQUIREMENT #7 |
| | 4.SHT. A-221 SHOWS BATHROOM TYPE 2 AS THE FHA SPEC B |
| | BATHROOM SHT A-771 SHOWS THE TYPE # AS THE FHA BATHROOM |
| | AND SHT G-5 LIST TYPE 3 PLEASE CLARIFY. PER WPB AMEND |
| | TO FBC 107.2.1 |
| | 5. SHT. A-222 INDICATE ON THE PLAN WHICH IS THE FHA |
| | BATHROOM. PER WPB AMEND TO FBC 107.2.1 |
| | 6.SHT. A-222 UNIT C IF FHA SPEC A IS USED ALL THE |
| | BATHROOMS SHALL COMPLY. PER FHA REQUIREMENT #7 PG. 7.34 |
| | AND 7.35 |
| | 7.SHT. A-222,223,224,225,226 INDICATE TYPE FHA BATHROOM |
| | . PER FHA REQUIREMENT #7 |
| | 8.SHT. A-229A INDICATE ON THE PLAN WHICH BATHROOM IS |
| | THE FHA BATHROOM PER FHA REQUIREMENT #7 |
| | 9. SHT. A-770, 771, 772,773, 774 PLEASE INDICATE ON THE |
| | PLAN WHERE THE GRAB BAR BACKING IS REQUIRED ALL |
| | BATHROOMS EXCEPT THE POWDER ROOM SHALL HAVE IT. PER FHA |
| | DESIGN MANUAL REQ. #6 |
| | 10.ANY WING WALL OR VANITY NEXT TO THE TOILET IN THE |
| | FHA BATHROOMS SHALL NOT EXTEND OVER 24" FROM THE BACK |
| | WALL. PER FHA DESIGN MANUAL REQ. #7 PG. 7.43 |
| | 11.PLEASE PROVIDE A DETAIL FOR THE GREASE INTERCEPTOR |
| | PIPING AND MOUNTING SYSTEM. PER WPB AMEND TO FBC |
| | 107.2.1 |
| | 12. PLEASE PROVIDE MANUFACTURE SPECIFICATIONS AND |
| | INSTILLATION GUIDE FOR THE GREASE INTERCEPTOR. PER WPB |
| | AMEND TO FBC 107.2.1 |
| | 13. PROVIDE SIZING CALCULATION FROM THE MANUFACTURE FOR |
| | THE GREASE INTERCEPTOR. PER WPB AMEND TO FBC 107.2.1 |
| | AND FBC PL 1003.2 |
| | 14. SHT. P-502 LABEL ALL WATER PIPING WITH HOT , COLD, |
| | RETURN AND UNIT TYPE. PER WPB AMEND TO FBC 107.2.1 |
| | 15. SHT P-502 THE SANITARY RISER DIAGRAM IS DO |
| | DIFFICULT TO DETERMINE CODE COMPLIANCE PLEASE PROVIDE A |
| | 3 DIMENSIONAL ISOMETRIC DRAWING FOR THE UNDERGROUND |
| | COLLECTION PIPING AND SEPARATE SOIL STACK ISOMETRICS. |
| | PER WPB AMEND TO FBC 107.2.1 |
| | 16. FOR THE FUEL OIL SYSTEM PLEASE SUBMIT THE |
| | FOLLOWING: |
| | A)MANUFACTURES SPECIFICATION FOR ALL EQUIPMENT BEING |
| | USED ON FUEL OIL SYSTEM INCLUDING TANK. |
| | B) A FLOOR PLAN AND ISOMETRIC DRAWING OF THE PIPING AND |
| | TANK. |
| | PER WPB AMEND TO FBC 107.2.1 |
| | THE FUEL OIL SYSTEM CAN BE SUBMITTED AS A SEPARATE |
| | PERMIT IF THAT IS YOUR INTENT PLEASE REMOVE ANY DETAILS |
| | OR DRAWING FROM THE MASTER SET. |
| | 17. PROVIDE AN ENLARGED FLOOR PLAN FOR ALL BOILER AND |
| | PUMP ROOMS ON THE 1ST AND 23RD FLOORS AND PIPING |
| | DETAIL. PER WPB AMEND TO FBC 107.2.1 |
| | |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | |
| | GEORGE JOHNSON |
| | PLUMBING PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | 561-805-6711 |
| | [email protected] |