| 2019-02-13 11:10:54 | |
| | 2ND REVIEW: |
| | 2017 FLORIDA BUILDING CODE 6TH EDITION |
| | 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH |
| | EDITION |
| | 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH |
| | EDITION |
| | 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH |
| | EDITION |
| | |
| | GAS COMMENTS: PREVIOUS COMMENTS |
| | 1. COMPLIED |
| | 2. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE 2017 |
| | FBC-FUEL GAS CODE SEC.304.1, 614.6 (CLOTHES DRYERS) OR |
| | 2017 FBC-RES. SEC.G 2407.1 AND G2439.4 (CLOTHES |
| | DRYERS). NEED CALCULATIONS FOR RANGES IN CATERING |
| | KITCHEN |
| | 3. SUBMIT TWO COPIES OF A DETAIL SHOWING THE TYPE OF |
| | VENT, LOCATION, SIZE, TERMINATION POINT, HEIGHT ABOVE |
| | THE ROOF AND ANCHORING DETAILS OF THE GAS VENT(S) PER |
| | 2017 FBC-FUEL GAS SECS. 502 THRU 505 OR 2017 FBC-RES. |
| | SEC.G2426 THROUGH G2439.WHAT WAS SUBMITTED IS UNCLEAR |
| | IN HOW AND WHERE THE VENTS AND INTAKES ARE RUNNING |
| | PLEASE PROVIDE ELEVATION DRAWING SHOWING INTAKES AND |
| | EXHAUST LOCATION THE OPENINGS ALSO DRAWING SHOWING THE |
| | LENGTH AND SIZE AND LEVEL ABOVE GROUND FLOOR. ALL SHALL |
| | COMPLY WITH MANUFACTURE INSTILLATION GUIDES. |
| | |
| | 4. SUBMIT TWO COPIES OF THE MANUFACTURER?S |
| | SPECIFICATION SHEETS / INSTALLATION MANUAL FOR ALL GAS |
| | EQUIPMENT AND REGULATORS TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND FBC-2017 FUEL GAS CODE |
| | SEC. 402.2, AND 301.3 OR 2017 FBC-RES. SEC. G2404.3. |
| | GAS APPLIANCES SHALL BE LISTED AND LABELED. THE |
| | INSTALLATION MANUALS FOR ALL GAS APPLIANCES / EQUIPMENT |
| | SHALL BE ONSITE AT THE TIME OF INSPECTION. FGC |
| | SEC.305.1, FBC-RES. SEC.G2408.1. SPECIFICATIONS SHALL |
| | BE SUBMITTED BEFORE A GAS PERMIT WILL BE ISSUED. THEY |
| | CAN BE DIFFERED FOR THE MASTER BUILDING PERMIT ISSUE IF |
| | REQUESTED. |
| | |
| | NEW COMMENTS |
| | 1. LABEL GAS PIPING ON FLOOR PLANS. PER WPB AMEND TO |
| | FBC 107.2.1 |
| | 2. PROVIDE AN ENLARGE FLOOR PLAN FOR ALL BOILER AND |
| | PUMP ROOMS ON THE 1ST AND 23RD FLOORS |
| | 3. SHT P-505 THE SECTION OF PIPING BETWEEN THE THE .5LB |
| | REGULATOR AND THE FIRST HVAC BOILER SHALL BE A MIN OF |
| | 3" ALSO THE SECTION BETWEEN THE TWO POOL HEATERS SHALL |
| | BE 11/4" |
| | |
| | |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | |