Date Text
2019-02-13 11:10:54 
 2ND REVIEW:
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 GAS COMMENTS: PREVIOUS COMMENTS
 1. COMPLIED
 2. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE 2017
 FBC-FUEL GAS CODE SEC.304.1, 614.6 (CLOTHES DRYERS) OR
 2017 FBC-RES. SEC.G 2407.1 AND G2439.4 (CLOTHES
 DRYERS). NEED CALCULATIONS FOR RANGES IN CATERING
 KITCHEN
 3. SUBMIT TWO COPIES OF A DETAIL SHOWING THE TYPE OF
 VENT, LOCATION, SIZE, TERMINATION POINT, HEIGHT ABOVE
 THE ROOF AND ANCHORING DETAILS OF THE GAS VENT(S) PER
 2017 FBC-FUEL GAS SECS. 502 THRU 505 OR 2017 FBC-RES.
 SEC.G2426 THROUGH G2439.WHAT WAS SUBMITTED IS UNCLEAR
 IN HOW AND WHERE THE VENTS AND INTAKES ARE RUNNING
 PLEASE PROVIDE ELEVATION DRAWING SHOWING INTAKES AND
 EXHAUST LOCATION THE OPENINGS ALSO DRAWING SHOWING THE
 LENGTH AND SIZE AND LEVEL ABOVE GROUND FLOOR. ALL SHALL
 COMPLY WITH MANUFACTURE INSTILLATION GUIDES.
  
 4. SUBMIT TWO COPIES OF THE MANUFACTURER?S
 SPECIFICATION SHEETS / INSTALLATION MANUAL FOR ALL GAS
 EQUIPMENT AND REGULATORS TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND FBC-2017 FUEL GAS CODE
 SEC. 402.2, AND 301.3 OR 2017 FBC-RES. SEC. G2404.3.
 GAS APPLIANCES SHALL BE LISTED AND LABELED. THE
 INSTALLATION MANUALS FOR ALL GAS APPLIANCES / EQUIPMENT
 SHALL BE ONSITE AT THE TIME OF INSPECTION. FGC
 SEC.305.1, FBC-RES. SEC.G2408.1. SPECIFICATIONS SHALL
 BE SUBMITTED BEFORE A GAS PERMIT WILL BE ISSUED. THEY
 CAN BE DIFFERED FOR THE MASTER BUILDING PERMIT ISSUE IF
 REQUESTED.
  
 NEW COMMENTS
 1. LABEL GAS PIPING ON FLOOR PLANS. PER WPB AMEND TO
 FBC 107.2.1
 2. PROVIDE AN ENLARGE FLOOR PLAN FOR ALL BOILER AND
 PUMP ROOMS ON THE 1ST AND 23RD FLOORS
 3. SHT P-505 THE SECTION OF PIPING BETWEEN THE THE .5LB
 REGULATOR AND THE FIRST HVAC BOILER SHALL BE A MIN OF
 3" ALSO THE SECTION BETWEEN THE TWO POOL HEATERS SHALL
 BE 11/4"
  
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  