Plan Review Notes
Plan Review Notes For Permit 18081528
Permit Number 18081528
Review Stop E
Sequence Number 2
Notes
Date Text
2019-02-12 09:17:38CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY HAVE BEEN REMOVED. PREVIOUS COMMENTS
 THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY HAVE
 ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW COMMENTS
 WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
  
 14. SHEET E-102B, CIRCUIT AL-17 IS SHOWN FEEDING THE
 TRATAM ROOM. WHAT IS THIS ROOM USED FOR, IS GFCI
 PROTECTION REQUIRED. PROVIDE CLARIFICATION AND/OR
 CORRECTION. NEC 210.8; WPB FBC 107.2.1 (BASED ON
 DESCRIPTION PROVIDED, GFCI PROTECTION IS REQUIRED.
 PROVIDE CORRECTION. NEC 210.8(B)(7) )
 15. SHEET E-102B, CIRCUIT AL-1, 3, 5 IS SHOWN FEEDING
 HP-2L-2, BUT THE PANEL SCHEDULE SHOWS CIRCUIT 1 AND 3
 FEEDING POOL RECEPTACLES. PROVIDE CORRECTION. WPB FBC
 107.2.1 (IT SEEMS WE DID NOT RECEIVE THE CORRECTED
 SHEET, THIS INFORMATION IS STILL SHOWN.)
 16. SHEET E-103, ALL RECEPTACLE OUTLETS IN CATERING
 KITCHEN AND PERFORMANCE KITCHEN REQUIRE GFCI
 PROTECTION. PROVIDE CORRECTION. NEC 210.8(B)(2) (IT
 SEEMS WE DID NOT RECEIVE THE CORRECTED SHEET, THIS
 INFORMATION IS STILL SHOWN.)
 84. LIGHTING SHEETS (ALL) DO NOT SHOW THE AUTOMATIC
 CONTROL REQUIRED. PROVIDE THE ADDITIONAL AUTOMATIC
 LIGHTING CONTROLS STIPULATED IN THE FBC ENERGY CODE.
 FBC EC C405.2 (NOT PROVIDED, THIS IS FOR INTERIOR
 SPACES NOT PART OF A DWELLING UNIT.)
 85. PROVIDE GRAPH/CALCULATION OF EXTERIOR LIGHTING
 POWER ALLOWANCES PER THE FBC ENERGY CONSERVATION IN
 RELATION TO THE CONNECTED EXTERIOR LIGHTING PROPOSED TO
 COMPLY WITH CODE. FBC EC C405.5.1 (NOT PROVIDED.)
 87. SHEET E-501, LABEL ALL FEEDERS TO SHOW WIRE AND
 CONDUIT SIZE. WPB FBC 107.2.1; NEC 310.15 (FROM FPL
 VAULT TO MAINS NOT SHOWN.)
 91. SHEET E-502, LABEL ALL FEEDERS TO SHOW WIRE AND
 CONDUIT SIZE. WPB FBC 107.2.1; NEC 310.15 (FROM FPL
 VAULT TO MAINS NOT SHOWN. TRANSFORMER SCHEDULE PASTED
 OVER RISER AND IS DIFFICULT TO READ.)
 94. PROVIDE DETAILS OF ARC FLASH MITIGATION FOR ALL
 MAINS PER CODE. NEC 240.87 (ARC FAULT MITIGATION IS NOT
 RELIANT ON THE AIC CALCULATION. SEE CODE SECTION FOR
 METHODS OF COMPLIANCE.)
 95. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR
 EACH PANEL INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE
 SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE.
 NEC 110.9, 110.10 (NOT PROVIDED, NOTED THAT THE
 APPLICANT IS WAITING ON FPL. THIS CAN BE A DEFERRED
 SUBMITTAL IF YOU CHOOSE. BE AWARE THAT APPLICANT WOULD
 BE PROCEEDING AT YOUR OWN RISK UNTIL THIS INFORMATION
 IS OBTAINED. IF SO DESIRED, PROVIDE NOTE ON PLAN TO
 THAT EFFECT.)
 96. ON RISER DIAGRAM PANEL EQPH IS SHOWN AS A 100 AMP
 PANEL. IN THE PANEL SCHEDULE FOR THIS PANEL, IT IS
 SHOWN AS AN 800 AMP PANEL. PROVIDE CORRECTION. WPB FBC
 107.2.1 (IT SEEMS WE DID NOT RECEIVE THE CORRECTED
 PANEL SCHEDULE SHEET, THIS INFORMATION IS STILL SHOWN.)
 97. ON RISER DIAGRAM PANEL EQEH IS SHOWN AS A 1200 AMP
 PANEL. IN THE PANEL SCHEDULE FOR THIS PANEL, IT IS
 SHOWN AS AN 800 AMP PANEL. PROVIDE CORRECTION. WPB FBC
 107.2.1 (IT SEEMS WE DID NOT RECEIVE THE CORRECTED
 PANEL SCHEDULE SHEET, THIS INFORMATION IS STILL SHOWN.)
 98. ON RISER DIAGRAM PANEL EDPH IS SHOWN AS A 600 AMP
 PANEL. IN THE PANEL SCHEDULE FOR THIS PANEL, IT IS
 SHOWN AS AN 1200 AMP PANEL. PROVIDE CORRECTION. WPB FBC
 107.2.1 (IT SEEMS WE DID NOT RECEIVE THE CORRECTED
 PANEL SCHEDULE SHEET, THIS INFORMATION IS STILL SHOWN.)
 102. AS ADJUSTMENTS ARE MADE TO DISCREPANCIES IN PLAN,
 PROVIDE UPDATED LOAD CALCULATION FOR EACH PANEL AND
 SERVICE. NEC 220 (IT SEEMS WE DID NOT RECEIVE THE
 CORRECTED SHEET, THIS INFORMATION IS STILL SHOWN.)
 103. SHEET E-601A, LOADS LISTED FOR LOAD CALCULATION
 SHOWN ARE MUCH DIFFERENT THAN THE LOADS SHOWN IN THE
 CORRESPONDING PANEL SCHEDULES. PROVIDE CLARIFICATION
 AND CORRECTION. WPB FBC 107.2.1; NEC 220 (IT SEEMS WE
 DID NOT RECEIVE THE CORRECTED SHEET, THIS INFORMATION
 IS STILL SHOWN.)
 104. WHERE ARE ELEVATORS FED FROM? I COULD NOT FIND
 THIS LOAD INCLUDED IN THE LOAD CALCULATION OR IN ANY
 PANEL SCHEDULES. PROVIDE CORRECTION. WPB FBC 107.2.1;
 NEC 220 (IT SEEMS WE DID NOT RECEIVE THE CORRECTED
 SHEET, THIS INFORMATION IS STILL SHOWN.)
 105. MANY OF THE PANEL SCHEDULES PROVIDED ARE
 INCOMPLETE. HOW CAN AN ACCURATE LOAD CALCULATION BE
 PROVIDED WITH THIS MUCH MISSING INFORMATION. PROVIDE
 CORRECTION. WPB FBC 107.2.1; NEC 220 (IT SEEMS WE DID
 NOT RECEIVE THE CORRECTED SHEET, THIS INFORMATION IS
 STILL SHOWN.)
 106. RISER DIAGRAM STATES THAT MDP1 IS ONE OF THE
 MAINS. THE PANEL SCHEDULE FOR THIS PANEL DOES NOT SHOW
 A MAIN. PROVIDE CORRECTION. WPB FBC 107.2.1; NEC 230.2
 (IT SEEMS WE DID NOT RECEIVE THE CORRECTED SHEET, THIS
 INFORMATION IS STILL SHOWN.)
 107. LOAD FOR PANEL H SHOWN IN PANEL SCHEDULE FOR PANEL
 MDP1 IS MUCH DIFFERENT THAN THE LOAD SHOWN IN THE PANEL
 SCHEDULE FOR PANEL H. PROVIDE CORRECTION. WPB FBC
 107.2.1; NEC 220 (IT SEEMS WE DID NOT RECEIVE THE
 CORRECTED SHEET, THIS INFORMATION IS STILL SHOWN.)
 108. RISER DIAGRAM STATES THAT THE EMERGENCY MAINS ARE
 MAINS 2 AND 3. THE PANEL SCHEDULE FOR THESE PANELS DOES
 NOT SHOW A MAIN. PROVIDE CORRECTION. WPB FBC 107.2.1;
 NEC 230.2 (IT SEEMS WE DID NOT RECEIVE THE CORRECTED
 SHEET, THIS INFORMATION IS STILL SHOWN.)
  
 NEW COMMENTS:
  
 109. PROVIDE LEGIBLE SHEET FOR E-502. THERE ARE
 GENERATOR SPECS PASTED OVER THE DRAWING KEYNOTES,
 MAKING PART OF THIS SHEET ILLEGIBLE. WPB FBC 107.2.1
 110. CORRECT DISCREPANCY FOR 75KVA TRANSFORMER FEEDING
 PANEL RL. RISER SHOWS IT BEING FED FROM PANEL RH. PANEL
 SCHEDULE SHOWS IT BEING FED FROM PANEL RDH. WPB FBC
 107.2.1
 111. PROVIDE PANEL SCHEDULE FOR ALL PANELS. SOME ARE
 MISSING, SUCH AS RDEH AND RH. WPB FBC 107.2.1; NEC
 408.4
 112. SHEET E-701, GENERATOR AND EMERGENCY ROOM ?
 ENLARGED PLAN, IT APPEARS THERE IS A WALL BUILT IN
 FRONT OF PANELS EOPH, EOL, EQEH, EQH, EQL, AND THE TWO
 TRANSFORMERS ON THAT WALL. PROVIDE CLARIFICATION AND/OR
 CORRECTION. NEC 110.26; WPB FBC 107.2.1
 113. BE ADVISED THAT FIRE ALARM, LOW VOLTAGE SYSTEMS,
 DAS, LIGHTNING PROTECTION, GENERATORS, COMMERCIAL HOOD
 SYSTEMS, WALK IN COOLERS, SIGNS, SITE LIGHTING, AND
 SWIMMING POOLS (WHERE APPLICABLE) ARE NOT INCLUDED IN
 THE SCOPE OF THIS PLAN REVIEW. PROVIDE A BLOCK NOTE
 INDICATING THE REQUIRED SEPARATE PERMITS AND PLAN
 SUBMITTALS FOR ANY OF THESE SYSTEMS PRESENT. WPB FBC
 105.1, 107.2.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  
  