2019-03-07 08:37:09REVIEW COMMENTS
  
 2ND REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
 WPB PERMIT: 18081528
 ADD: 1515 S. FLAGLER DRIVE
 CONT:
 TEL:
 EMAIL:
  
 1) ART IN PUBLIC PLACES - APPLICANT IS WORKING TO
 ADDRESS.
  
 2) PARTIAL COMPLIANCE. PLEASE CLARIFY THE COST
 BREAKDOWN THAT WAS PROVIDED FOR THE ITEMS THAT WILL BE
 PERMITED SEPARATELY AND ARE NOT INCLUDED IN THE
 $91,000,000.00 VALUATION FOR THE BUILDING.
 A) IS THE $3,000,000.00 FOR THE FOUNDATION PART OF THE
 $91,000,000.00 FOR THE BUILDING?
 B) DOES THE $ 0.6 MILLION FOR THE POOL INCLUDE THE COST
 OF THE POOL LOCATED ON THE 25TH FLOOR? PLEASE PROVIDE
 THE COSTS FOR EACH POOL.
 C) THE SITE WALL, LANDSCAPE AND IRRIGATION WILL BE
 THREE SEPARATE PERMITS. PLEASE DIVIDE THE $1.5 MILLION
 TO SHOW THE COST OF EACH ONE INDIVIDUALLY.
 D) SPECIFY THE COST OF THE GENERATOR.
  
 3) PARTIAL COMPLIANCE.
 A) SUBMIT A THRESHOLD INSPECTION PLAN. FBC (CITY
 AMENDMENTS)110.8.1 THRESHOLD INSPECTION PLAN. THE
 ENFORCING AGENCY SHALL REQUIRE A SPECIAL INSPECTOR TO
 PERFORM STRUCTURAL INSPECTIONS ON A THRESHOLD BUILDING
 PURSUANT TO A STRUCTURAL INSPECTION PLAN PREPARED BY
 THE ENGINEER OF RECORD. THE STRUCTURAL INSPECTION PLAN
 MUST BE SUBMITTED TO THE ENFORCING AGENCY PRIOR TO THE
 ISSUANCE OF A BUILDING PERMIT FOR THE CONSTRUCTION OF A
 THRESHOLD BUILDING. THE PURPOSE OF THE STRUCTURAL
 INSPECTION PLAN IS TO PROVIDE SPECIFIC INSPECTION
 PROCEDURES AND SCHEDULES SO THAT THE BUILDING CAN BE
 ADEQUATELY INSPECTED FOR COMPLIANCE WITH THE PERMITTED
 DOCUMENTS. THE SPECIAL INSPECTOR MAY NOT SERVE AS A
 SURROGATE IN CARRYING OUT THE RESPONSIBILITIES OF THE
 BUILDING OFFICIAL, THE ARCHITECT OR THE ENGINEER OF
 RECORD. THE CONTRACTOR'S CONTRACTUAL OR STATUTORY
 OBLIGATIONS ARE NOT RELIEVED BY ANY ACTION OF THE
 SPECIAL INSPECTOR.
  
 B) COMPLIED.
  
 C) COMPLIED.
  
 D) COMPLIED.
  
 E) COMPLIED.
  
 F) NOTE: FOR DIGITAL PLANS, AFTER PERMIT ISSUANCE,
 PLEASE E-MAIL THE PERMIT LIBRARIAN OF THE PERMIT BEING
 ISSUED, THE PERMIT LIBRARIAN WILL THEN E-MAIL YOU THE
 APPROVED AND BATCH STAMPED PLANS SO YOU MAY PRINT YOUR
 PLANS.
  
 G) WILL COMPLY.
  
 H) WILL COMPLY.
  
 I) COMPLIED.
  
 J) COMPLIED.
  
 4) COMPLIED.
  
 5) COMPLIED.
  
 6) COMPLIED.
  
 7) NOT COMPLIED. SOME OF THE PLANS HAVE A STATEMENT
 THAT SAYS "PRELIMINARY NOT FOR CONSTRUCTION". SEE
 SHEETS A111 THRU A115 & SHEETS 000.1 THRU 000.4. THE
 SITE PLANS ARE REQUIRED MARKED FOR REFERENCE ONLY. ALL
 PLANS AND CONSTRUCTION DOCUMENTS THAT ARE SUBMITTED FOR
 PERMIT ARE REQUIRED TO BE SIGNED AND SEALED BY THE
 ENGINEER OR ARCHITECT THAT PREPARED THEM. FS 471 & 481
  
 8) COMPLIED.
  
 9) NOT COMPLIED. THERE ARE PLAN SHEETS LISTED IN THE
 DRAWING INDEX THAT ARE NOT PROVIDED. COORDINATE THE
 DRAWING INDEX ON SHEET G-1 WITH THE PLAN SHEETS THAT
 ARE BEING UPLOADED. STRIKE OUT THE SHEETS THAT ARE NOT
 UPLOADED. FBC 107.2.1
  
 10) COMPLIED.
  
 11) COMPLIED.
  
 12) COMPLIED.
  
 13) COMPLIED.
  
 14) COMPLIED..
  
 15) COMPLIED.
  
 16) COMPLIED.
  
 17) COMPLIED.
  
 18) COMPLIED.
  
 19) COMPLIED.
  
 20) COMPLIED.
  
 21) COMPLIED.
  
 22) NOT COMPLIED. THIS DOOR IS SPECIFIED AS A 45 MIN.
 FIRE RATED DOOR ON LS-5, HOWEVER, THE WALL IN WHICH IT
 IS LOCATED IS SPECIFIED AS HAVING A TWO HOUR FIRE
 RATING REQUIRING A 90 MIN FIRE RATED DOOR. ON SHEET
 LS-5 THE FIRE RATING OF THE DOOR TO THE TRASH ROOM IS
 NOT SPECIFIED.FBC 716.5.3
  
 23) COMPLIED.
  
 24) COMPLIED.
  
 25) PARTIALLY COMPLIED. THE DOORS TO ROOMS 305 AND 307
 ON SHEET LS-4 ARE SPECIFIED AS 45 MIN. FIRE RATED,
 HOWEVER, THE WALLS THEY ARE LOCATED IN ARE SHOWN AS 2
 HOUR FIRE RATED (WHICH REQUIRE 90 MIN. FIRE RATED
 DOORS). ALSO SEE SHEETS LS-5, LS-7, LS-8, LS-9. THE
 FIRE RATING OF THE DOORS TO THE STORAGE ROOM AND THE
 TRASH ROOM IN THE 2 HOUR FIRE RATED WALLS ARE NOT
 SPECIFIED. FBC 107.2.1
  
 26) COMPLIED.
  
 27) NOT COMPLIED. THIS DOOR IS LISTED AS A 45 MIN. FIRE
 RATED DOOR IN THE DOOR SCHEDULE. THE WALL THAT IT IS IN
 IS SHOWN AS A 2 HR. FIRE RATED WALL, WHICH REQUIRES A
 90 MIN. FIRE RATED DOOR. SHOULD THIS WALL HAVE A 1 HR
 FIRE RATING? DOOR 2504A IN THE 2 HOUR FIRE RATED WALL
 AND IS REQUIRED TO BE 90 MINUTE FIRE RATES IS NOT
 LISTED IN THE DOOR SCHEDULE. FBC 107.2.1
  
 28) COMPLIED.
  
 29) COMPLIED.
  
 30) COMPLIED.
  
 31) COMPLIED.
  
 32) COMPLIED.
  
 33) COMPLIED.
  
 34) COMPLIED.
  
 35) COMPLIED.
  
 36) COMPLIED.
  
 37) COMPLIED.
  
 38) COMPLIED.
  
 39)COMPLIED.
  
 40) NOT COMPLIED. PROVIDE A LIST OF THE ITEMS THAT WILL
 BE DEFERRED ON THE PLANS. FBC 107.3.4.1 DEFERRED
 SUBMITTALS. FOR THE PURPOSES OF THIS SECTION, DEFERRED
 SUBMITTALS ARE DEFINED AS THOSE PORTIONS OF THE DESIGN
 THAT ARE NOT SUBMITTED AT THE TIME OF THE APPLICATION
 AND THAT ARE TO BE SUBMITTED TO THE BUILDING OFFICIAL
 WITHIN A SPECIFIED PERIOD. DEFERRAL OF ANY SUBMITTAL
 ITEMS SHALL HAVE THE PRIOR APPROVAL OF THE BUILDING
 OFFICIAL. THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE SHALL LIST THE DEFERRED SUBMITTALS
 ON THE CONSTRUCTION DOCUMENTS FOR REVIEW BY THE
 BUILDING OFFICIAL.
  
 41) W. P. B. 107.3.4.1 PRODUCT APPROVALS. THOSE
 PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03
 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE
 ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING
 ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC.
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 42) PARTIAL COMPLIANCE. REVISE THE NOTE ON THE PLAN TO
 INCLUDE ASTM E 492. SHOW COMPLIANCE WITH FBC 1207.2 FOR
 AIR-BORNE SOUND TRANSMISSION AND FBC 1207.3 FOR
 STRUCTURE BORNE SOUND INSULATION.
  
 43) NEW COMMENT. ON SHEET A-107 THE UNIT H BALCONY
 APPEARS TO SLOPE TOWARDS THE BUILDING. FBC 107.2.1
  
 44) NEW COMMENT. ON SHEET A-901, PARTITION TYPE P/8 HAS
 2 LAYERS OF 5/8" TYPE X GWB ON EACH SIDE OF THE 6"
 METAL FRAME WALL. THIS WALL WILL HAVE A 2 HR FIRE
 RATING AND THE DETAIL SPECIFIES IT AS 1 HR. FBC 107.2.1
  
 FYI - THE NUMBERING OF THE ITEMS ON YOUR RESPONSE
 LETTER ARE INCORRECT. THERE ARE TWO ITEM NUMBER 2S
 WHICH CAUSED ALL COMMENTS AFTER NUMBER 2 TO BE
 MISNUMBERED.
 NOTE: ADDITIONAL COMMENTS MAY RESULT FROM THE RESPONSES
 TO THESE COMMENTS. WHEN RESUBMITTING, IT IS HELPFUL TO
 PROVIDE A RESPONSE LETTER ADDRESSING EACH ITEM ALONG
 WITH THE CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE
 INSERT CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  