| 2019-03-07 08:37:09 | REVIEW COMMENTS |
| | |
| | 2ND REVIEW: FBC SIXTH EDITION (2017) |
| | ROBERT MCDOUGAL, CBO |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561) 805-6714 |
| | [email protected] |
| | WPB PERMIT: 18081528 |
| | ADD: 1515 S. FLAGLER DRIVE |
| | CONT: |
| | TEL: |
| | EMAIL: |
| | |
| | 1) ART IN PUBLIC PLACES - APPLICANT IS WORKING TO |
| | ADDRESS. |
| | |
| | 2) PARTIAL COMPLIANCE. PLEASE CLARIFY THE COST |
| | BREAKDOWN THAT WAS PROVIDED FOR THE ITEMS THAT WILL BE |
| | PERMITED SEPARATELY AND ARE NOT INCLUDED IN THE |
| | $91,000,000.00 VALUATION FOR THE BUILDING. |
| | A) IS THE $3,000,000.00 FOR THE FOUNDATION PART OF THE |
| | $91,000,000.00 FOR THE BUILDING? |
| | B) DOES THE $ 0.6 MILLION FOR THE POOL INCLUDE THE COST |
| | OF THE POOL LOCATED ON THE 25TH FLOOR? PLEASE PROVIDE |
| | THE COSTS FOR EACH POOL. |
| | C) THE SITE WALL, LANDSCAPE AND IRRIGATION WILL BE |
| | THREE SEPARATE PERMITS. PLEASE DIVIDE THE $1.5 MILLION |
| | TO SHOW THE COST OF EACH ONE INDIVIDUALLY. |
| | D) SPECIFY THE COST OF THE GENERATOR. |
| | |
| | 3) PARTIAL COMPLIANCE. |
| | A) SUBMIT A THRESHOLD INSPECTION PLAN. FBC (CITY |
| | AMENDMENTS)110.8.1 THRESHOLD INSPECTION PLAN. THE |
| | ENFORCING AGENCY SHALL REQUIRE A SPECIAL INSPECTOR TO |
| | PERFORM STRUCTURAL INSPECTIONS ON A THRESHOLD BUILDING |
| | PURSUANT TO A STRUCTURAL INSPECTION PLAN PREPARED BY |
| | THE ENGINEER OF RECORD. THE STRUCTURAL INSPECTION PLAN |
| | MUST BE SUBMITTED TO THE ENFORCING AGENCY PRIOR TO THE |
| | ISSUANCE OF A BUILDING PERMIT FOR THE CONSTRUCTION OF A |
| | THRESHOLD BUILDING. THE PURPOSE OF THE STRUCTURAL |
| | INSPECTION PLAN IS TO PROVIDE SPECIFIC INSPECTION |
| | PROCEDURES AND SCHEDULES SO THAT THE BUILDING CAN BE |
| | ADEQUATELY INSPECTED FOR COMPLIANCE WITH THE PERMITTED |
| | DOCUMENTS. THE SPECIAL INSPECTOR MAY NOT SERVE AS A |
| | SURROGATE IN CARRYING OUT THE RESPONSIBILITIES OF THE |
| | BUILDING OFFICIAL, THE ARCHITECT OR THE ENGINEER OF |
| | RECORD. THE CONTRACTOR'S CONTRACTUAL OR STATUTORY |
| | OBLIGATIONS ARE NOT RELIEVED BY ANY ACTION OF THE |
| | SPECIAL INSPECTOR. |
| | |
| | B) COMPLIED. |
| | |
| | C) COMPLIED. |
| | |
| | D) COMPLIED. |
| | |
| | E) COMPLIED. |
| | |
| | F) NOTE: FOR DIGITAL PLANS, AFTER PERMIT ISSUANCE, |
| | PLEASE E-MAIL THE PERMIT LIBRARIAN OF THE PERMIT BEING |
| | ISSUED, THE PERMIT LIBRARIAN WILL THEN E-MAIL YOU THE |
| | APPROVED AND BATCH STAMPED PLANS SO YOU MAY PRINT YOUR |
| | PLANS. |
| | |
| | G) WILL COMPLY. |
| | |
| | H) WILL COMPLY. |
| | |
| | I) COMPLIED. |
| | |
| | J) COMPLIED. |
| | |
| | 4) COMPLIED. |
| | |
| | 5) COMPLIED. |
| | |
| | 6) COMPLIED. |
| | |
| | 7) NOT COMPLIED. SOME OF THE PLANS HAVE A STATEMENT |
| | THAT SAYS "PRELIMINARY NOT FOR CONSTRUCTION". SEE |
| | SHEETS A111 THRU A115 & SHEETS 000.1 THRU 000.4. THE |
| | SITE PLANS ARE REQUIRED MARKED FOR REFERENCE ONLY. ALL |
| | PLANS AND CONSTRUCTION DOCUMENTS THAT ARE SUBMITTED FOR |
| | PERMIT ARE REQUIRED TO BE SIGNED AND SEALED BY THE |
| | ENGINEER OR ARCHITECT THAT PREPARED THEM. FS 471 & 481 |
| | |
| | 8) COMPLIED. |
| | |
| | 9) NOT COMPLIED. THERE ARE PLAN SHEETS LISTED IN THE |
| | DRAWING INDEX THAT ARE NOT PROVIDED. COORDINATE THE |
| | DRAWING INDEX ON SHEET G-1 WITH THE PLAN SHEETS THAT |
| | ARE BEING UPLOADED. STRIKE OUT THE SHEETS THAT ARE NOT |
| | UPLOADED. FBC 107.2.1 |
| | |
| | 10) COMPLIED. |
| | |
| | 11) COMPLIED. |
| | |
| | 12) COMPLIED. |
| | |
| | 13) COMPLIED. |
| | |
| | 14) COMPLIED.. |
| | |
| | 15) COMPLIED. |
| | |
| | 16) COMPLIED. |
| | |
| | 17) COMPLIED. |
| | |
| | 18) COMPLIED. |
| | |
| | 19) COMPLIED. |
| | |
| | 20) COMPLIED. |
| | |
| | 21) COMPLIED. |
| | |
| | 22) NOT COMPLIED. THIS DOOR IS SPECIFIED AS A 45 MIN. |
| | FIRE RATED DOOR ON LS-5, HOWEVER, THE WALL IN WHICH IT |
| | IS LOCATED IS SPECIFIED AS HAVING A TWO HOUR FIRE |
| | RATING REQUIRING A 90 MIN FIRE RATED DOOR. ON SHEET |
| | LS-5 THE FIRE RATING OF THE DOOR TO THE TRASH ROOM IS |
| | NOT SPECIFIED.FBC 716.5.3 |
| | |
| | 23) COMPLIED. |
| | |
| | 24) COMPLIED. |
| | |
| | 25) PARTIALLY COMPLIED. THE DOORS TO ROOMS 305 AND 307 |
| | ON SHEET LS-4 ARE SPECIFIED AS 45 MIN. FIRE RATED, |
| | HOWEVER, THE WALLS THEY ARE LOCATED IN ARE SHOWN AS 2 |
| | HOUR FIRE RATED (WHICH REQUIRE 90 MIN. FIRE RATED |
| | DOORS). ALSO SEE SHEETS LS-5, LS-7, LS-8, LS-9. THE |
| | FIRE RATING OF THE DOORS TO THE STORAGE ROOM AND THE |
| | TRASH ROOM IN THE 2 HOUR FIRE RATED WALLS ARE NOT |
| | SPECIFIED. FBC 107.2.1 |
| | |
| | 26) COMPLIED. |
| | |
| | 27) NOT COMPLIED. THIS DOOR IS LISTED AS A 45 MIN. FIRE |
| | RATED DOOR IN THE DOOR SCHEDULE. THE WALL THAT IT IS IN |
| | IS SHOWN AS A 2 HR. FIRE RATED WALL, WHICH REQUIRES A |
| | 90 MIN. FIRE RATED DOOR. SHOULD THIS WALL HAVE A 1 HR |
| | FIRE RATING? DOOR 2504A IN THE 2 HOUR FIRE RATED WALL |
| | AND IS REQUIRED TO BE 90 MINUTE FIRE RATES IS NOT |
| | LISTED IN THE DOOR SCHEDULE. FBC 107.2.1 |
| | |
| | 28) COMPLIED. |
| | |
| | 29) COMPLIED. |
| | |
| | 30) COMPLIED. |
| | |
| | 31) COMPLIED. |
| | |
| | 32) COMPLIED. |
| | |
| | 33) COMPLIED. |
| | |
| | 34) COMPLIED. |
| | |
| | 35) COMPLIED. |
| | |
| | 36) COMPLIED. |
| | |
| | 37) COMPLIED. |
| | |
| | 38) COMPLIED. |
| | |
| | 39)COMPLIED. |
| | |
| | 40) NOT COMPLIED. PROVIDE A LIST OF THE ITEMS THAT WILL |
| | BE DEFERRED ON THE PLANS. FBC 107.3.4.1 DEFERRED |
| | SUBMITTALS. FOR THE PURPOSES OF THIS SECTION, DEFERRED |
| | SUBMITTALS ARE DEFINED AS THOSE PORTIONS OF THE DESIGN |
| | THAT ARE NOT SUBMITTED AT THE TIME OF THE APPLICATION |
| | AND THAT ARE TO BE SUBMITTED TO THE BUILDING OFFICIAL |
| | WITHIN A SPECIFIED PERIOD. DEFERRAL OF ANY SUBMITTAL |
| | ITEMS SHALL HAVE THE PRIOR APPROVAL OF THE BUILDING |
| | OFFICIAL. THE REGISTERED DESIGN PROFESSIONAL IN |
| | RESPONSIBLE CHARGE SHALL LIST THE DEFERRED SUBMITTALS |
| | ON THE CONSTRUCTION DOCUMENTS FOR REVIEW BY THE |
| | BUILDING OFFICIAL. |
| | |
| | 41) W. P. B. 107.3.4.1 PRODUCT APPROVALS. THOSE |
| | PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03 |
| | SHALL BE REVIEWED AND APPROVED IN WRITING BY THE |
| | DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| | JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE |
| | ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING |
| | ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC. |
| | DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE |
| | SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN |
| | RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD |
| | THEM TO THE BUILDING OFFICIAL WITH A NOTATION |
| | INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE |
| | BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO |
| | THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL |
| | ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED |
| | SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING |
| | OFFICIAL. |
| | |
| | 42) PARTIAL COMPLIANCE. REVISE THE NOTE ON THE PLAN TO |
| | INCLUDE ASTM E 492. SHOW COMPLIANCE WITH FBC 1207.2 FOR |
| | AIR-BORNE SOUND TRANSMISSION AND FBC 1207.3 FOR |
| | STRUCTURE BORNE SOUND INSULATION. |
| | |
| | 43) NEW COMMENT. ON SHEET A-107 THE UNIT H BALCONY |
| | APPEARS TO SLOPE TOWARDS THE BUILDING. FBC 107.2.1 |
| | |
| | 44) NEW COMMENT. ON SHEET A-901, PARTITION TYPE P/8 HAS |
| | 2 LAYERS OF 5/8" TYPE X GWB ON EACH SIDE OF THE 6" |
| | METAL FRAME WALL. THIS WALL WILL HAVE A 2 HR FIRE |
| | RATING AND THE DETAIL SPECIFIES IT AS 1 HR. FBC 107.2.1 |
| | |
| | FYI - THE NUMBERING OF THE ITEMS ON YOUR RESPONSE |
| | LETTER ARE INCORRECT. THERE ARE TWO ITEM NUMBER 2S |
| | WHICH CAUSED ALL COMMENTS AFTER NUMBER 2 TO BE |
| | MISNUMBERED. |
| | NOTE: ADDITIONAL COMMENTS MAY RESULT FROM THE RESPONSES |
| | TO THESE COMMENTS. WHEN RESUBMITTING, IT IS HELPFUL TO |
| | PROVIDE A RESPONSE LETTER ADDRESSING EACH ITEM ALONG |
| | WITH THE CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE |
| | INSERT CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS. |
| | |