| 2018-12-19 12:32:38 | FAILED |
| | |
| | PROVIDE WRITTEN RESPONSES TO COMMENTS. |
| | |
| | 1) SHEET A114 IS NOT THE LATEST PLAN APPROVED AS PART |
| | OF THE MINOR PD AMENDMENT. |
| | |
| | 2) SHEET G-3 SHOWS INCORRECT STRIPING. |
| | |
| | 3) SHEET G-7 SHOWS INCORRECT DATA. |
| | |
| | 4) THESE ARE NOT THE LATEST CIVIL PLANS APPROVED AS |
| | PART OF THE MINOR PD AMENDMENT. |
| | |
| | 5) SHEET A-101 IS NOT THE LATEST PLAN APPROVED AS PART |
| | OF THE MINOR PD AMENDMENT ? PARKING COUNT AND BICYCLE |
| | RACKS. |
| | |
| | 6) SHEETS A-101A, A-102 AND A-102A SHOW A RETAINING |
| | WALL BLOCKING THE WESTERN PERIMETER SIDEWALK. |
| | |
| | 5) SHEET A-101B IS NOT THE LATEST PLAN APPROVED AS PART |
| | OF THE MINOR PD AMENDMENT ? BICYCLE RACKS. |
| | |
| | 6) ROOF SLAB ON SHEET A-110 SHOWS THE HEIGHT AT 302 |
| | FEET 4 INCHES AS OPPOSED TO THE MINOR AMENDMENT |
| | APPROVED ROOF HEIGHT OF 301 FEET 10 INCHES AND THE |
| | HEIGHT SHOWN ON THE ELEVATION DRAWINGS SHEETS A-400 |
| | THROUGH A-402 AND THE SECTION DRAWINGS. STAIR SECTION 3 |
| | ON SHEET A-601 AND SECTION 2 ON SHEET A-609 ALSO SHOW |
| | ROOF HIGHER THAN 301 FEET 10 INCHES. SHEET A-610 SHOWS |
| | THE ELEVATOR CORE EXCEEDING THE 301 FEET 10 INCH |
| | HEIGHT. THE TRASH CUTES ON SHEET A-620 EXCEED THE 301 |
| | FEET 10 INCH HEIGHT. |
| | |
| | 7) THE NORTH ELEVATION ON THE PERMIT SET SHOWS THE |
| | MIDDLE OF THE BUILDING AS "STUCCO/PTD W/ SCORE LINES" |
| | WHILE THE APPROVED MINOR PD AMENDMENT PLANS SHOW THIS |
| | AREA AS ?MATTE ALUMINUM CLADDING?. |
| | |
| | 8) THE EAST ELEVATION ON THE PERMIT SET SHOWS A |
| | "CONCRETE WALL" WHILE THE APPROVED PLANS SHOW THIS AREA |
| | AS "BEAUVAL FRENCH LIMESTONE". |
| | |
| | 9) SHEET A-502, BUILDING SECTION, SHOWS A PORTION OF |
| | THE BUILDING EXTENDING ABOVE THE 307 FOOT MAXIMUM |
| | HEIGHT. |
| | |
| | 10) SHEET A-801 DOES NOT SHOW THE FULL HEIGHT OF THE |
| | COOLING TOWERS SCREENED AS REQUIRED BY THE RPD |
| | REGULATIONS. |
| | |
| | 11) SHEET M-101A SHOWS THE GARAGE VENTING/GENERATOR |
| | VENTING TOWARD THE RESIDENTIAL BUILDING TO THE SOUTH OF |
| | THE SITE. THIS IS NOT PERMITTED. VENTING MAY NOT BE |
| | DIRECTED TOWARD THE ADJACENT RESIDENTIAL PROPERTIES. |
| | |
| | 12) SHOW A SECTION DRAWING TO VERIFY THAT THE ROOFTOP |
| | MECHANICAL EQUIPMENT DOES NOT EXCEED THE HEIGHT OF THE |
| | PARAPET. |
| | |
| | 13) THE ABOVE GRADE PHOTOMETRIC PLANS NEED TO BE SHOWN |
| | TO THE PROPERTY LINE IN ACCORDANCE WITH THE CONDITIONS |
| | FROM THE APPROVED MINOR PD AMENDMENTS. |
| | |
| | 14) PROVIDE VERIFICATION THAT THE GLASS AND STEEL ON |
| | ALL BUILDING FACADES IS TREATED IN SUCH A WAY TO |
| | MINIMIZE GLARE AND REFLECTION OF HIGH INTENSITY |
| | SUNLIGHT ONTO SURROUNDING PROPERTIES. |
| | |