Plan Review Notes
Plan Review Notes For Permit 18081528
Permit Number 18081528
Review Stop Z
Sequence Number 1
Notes
Date Text
2018-12-19 12:32:38FAILED
  
 PROVIDE WRITTEN RESPONSES TO COMMENTS.
  
 1) SHEET A114 IS NOT THE LATEST PLAN APPROVED AS PART
 OF THE MINOR PD AMENDMENT.
  
 2) SHEET G-3 SHOWS INCORRECT STRIPING.
  
 3) SHEET G-7 SHOWS INCORRECT DATA.
  
 4) THESE ARE NOT THE LATEST CIVIL PLANS APPROVED AS
 PART OF THE MINOR PD AMENDMENT.
  
 5) SHEET A-101 IS NOT THE LATEST PLAN APPROVED AS PART
 OF THE MINOR PD AMENDMENT ? PARKING COUNT AND BICYCLE
 RACKS.
  
 6) SHEETS A-101A, A-102 AND A-102A SHOW A RETAINING
 WALL BLOCKING THE WESTERN PERIMETER SIDEWALK.
  
 5) SHEET A-101B IS NOT THE LATEST PLAN APPROVED AS PART
 OF THE MINOR PD AMENDMENT ? BICYCLE RACKS.
  
 6) ROOF SLAB ON SHEET A-110 SHOWS THE HEIGHT AT 302
 FEET 4 INCHES AS OPPOSED TO THE MINOR AMENDMENT
 APPROVED ROOF HEIGHT OF 301 FEET 10 INCHES AND THE
 HEIGHT SHOWN ON THE ELEVATION DRAWINGS SHEETS A-400
 THROUGH A-402 AND THE SECTION DRAWINGS. STAIR SECTION 3
 ON SHEET A-601 AND SECTION 2 ON SHEET A-609 ALSO SHOW
 ROOF HIGHER THAN 301 FEET 10 INCHES. SHEET A-610 SHOWS
 THE ELEVATOR CORE EXCEEDING THE 301 FEET 10 INCH
 HEIGHT. THE TRASH CUTES ON SHEET A-620 EXCEED THE 301
 FEET 10 INCH HEIGHT.
  
 7) THE NORTH ELEVATION ON THE PERMIT SET SHOWS THE
 MIDDLE OF THE BUILDING AS "STUCCO/PTD W/ SCORE LINES"
 WHILE THE APPROVED MINOR PD AMENDMENT PLANS SHOW THIS
 AREA AS ?MATTE ALUMINUM CLADDING?.
  
 8) THE EAST ELEVATION ON THE PERMIT SET SHOWS A
 "CONCRETE WALL" WHILE THE APPROVED PLANS SHOW THIS AREA
 AS "BEAUVAL FRENCH LIMESTONE".
  
 9) SHEET A-502, BUILDING SECTION, SHOWS A PORTION OF
 THE BUILDING EXTENDING ABOVE THE 307 FOOT MAXIMUM
 HEIGHT.
  
 10) SHEET A-801 DOES NOT SHOW THE FULL HEIGHT OF THE
 COOLING TOWERS SCREENED AS REQUIRED BY THE RPD
 REGULATIONS.
  
 11) SHEET M-101A SHOWS THE GARAGE VENTING/GENERATOR
 VENTING TOWARD THE RESIDENTIAL BUILDING TO THE SOUTH OF
 THE SITE. THIS IS NOT PERMITTED. VENTING MAY NOT BE
 DIRECTED TOWARD THE ADJACENT RESIDENTIAL PROPERTIES.
  
 12) SHOW A SECTION DRAWING TO VERIFY THAT THE ROOFTOP
 MECHANICAL EQUIPMENT DOES NOT EXCEED THE HEIGHT OF THE
 PARAPET.
  
 13) THE ABOVE GRADE PHOTOMETRIC PLANS NEED TO BE SHOWN
 TO THE PROPERTY LINE IN ACCORDANCE WITH THE CONDITIONS
 FROM THE APPROVED MINOR PD AMENDMENTS.
  
 14) PROVIDE VERIFICATION THAT THE GLASS AND STEEL ON
 ALL BUILDING FACADES IS TREATED IN SUCH A WAY TO
 MINIMIZE GLARE AND REFLECTION OF HIGH INTENSITY
 SUNLIGHT ONTO SURROUNDING PROPERTIES.
  