Plan Review Notes
Plan Review Notes For Permit 18081528
Permit Number 18081528
Review Stop E
Sequence Number 1
Notes
Date Text
2018-10-18 08:58:07CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 BE ADVISED THAT THERE IS SO MUCH CONFLICTING AND
 INCOMPLETE INFORMATION ON THIS SUBMISSION THAT A FULL
 REVIEW WILL BE REQUIRED FOR THE SECOND REVIEW, LIKELY
 RESULTING IN FURTHER COMMENTS.
  
 1. SHEET E-001, PLAN STATES THAT IT IS NOT FOR
 CONSTRUCTION OR PERMIT PURPOSES. REMOVE STATEMENT AND
 PROVIDE COMPLETED PERMIT SET FOR REVIEW. WPB FBC
 107.2.1
 2. SHEET E-001, NOTE 4, THE NEC AND FBC SPECIFIED FOR
 DESIGN IS NOT THE CURRENT CODE. PROVIDE CORRECTION. FBC
 PREFACE (ALSO SEE CURRENT CODES ABOVE)
 3. SHEET E-001, NOTE 63, AFCI PROTECTION SHOWN IN NOT
 CODE COMPLIANT. ALL BRANCH CIRCUITS THAT SUPPLY
 120-VOLT, SINGLE-PHASE, 15- AND 20-AMPERE OUTLETS
 INSTALLED IN KITCHENS, FAMILY ROOMS, DINING ROOMS,
 LIVING ROOMS, PARLORS, LIBRARIES, DENS, BEDROOMS,
 SUN-ROOMS, RECREATIONS ROOMS, CLOSETS, HALLWAYS,
 LAUNDRY AREAS AND SIMILAR ROOMS OR AREAS SHALL BE AFCI
 PROTECTED. THIS INCLUDES LIGHTING AND POWER OUTLETS AND
 RECEPTACLES. SOME AREAS REQUIRE BOTH AFCI AND GFCI
 PROTECTION. PROVIDE CORRECTION. NEC 210.8, 210.12
 4. SHEET E-001, NOTE 68, STATES THAT RECEPTACLES SHALL
 BE TAMPER RESISTANT PER NEC 406.11. THIS CODE SECTION
 DOES NOT APPLY TO TAMPER RESISTANT RECEPTACLES. PROVIDE
 CORRECTION. NEC 406.12
 5. SHEET E-001, NOTE 79, REFERS TO THE 2010 FBC FOR
 STAIRS. PROVIDE CLARIFICATION FOR PERTINENCE TO
 ELECTRICAL REVIEW. PROVIDE CORRECT CODE FOR DESIGN. WPB
 FBC 107.2.1; FBC PREFACE (ALSO SEE CURRENT CODES ABOVE)
 6. SHEET E-001, NOTE 80, THE NEC AND FBC SPECIFIED FOR
 DESIGN IS NOT THE CURRENT CODE. PROVIDE CORRECTION. FBC
 PREFACE (ALSO SEE CURRENT CODES ABOVE)
 7. SHEET E-101, PROVIDE GFCI PROTECTION FOR ALL
 RECEPTACLE OUTLETS IN GARAGE. NEC 210.8(B)(8)
 8. SHEET E-101, DETAILS ARE SPECIFIED TO BE ON SHEET
 E-701WHICH WAS NOT PROVIDED IN SUBMISSION. PROVIDE
 CORRECTION. WPB FBC 107.2.1
 9. SHEET E-101, DETAILS ARE SPECIFIED TO BE ON SHEET
 E-702 WHICH WAS NOT PROVIDED IN SUBMISSION. PROVIDE
 CORRECTION. WPB FBC 107.2.1
 10. SHEET E-101, DETAIL 1 FOR MAIN ELECTRICAL ROOM IS
 MISSING. PROVIDE CORRECTION. WPB FBC 107.2.1
 11. SHEET E-101A, PROVIDE GFCI PROTECTED RECEPTACLE
 OUTLET FOR SERVICING OF A/C EQUIPMENT WITHIN 25 FEET OF
 THE EQUIPMENT PER CODE. NEC 210.63
 12. SHEET E-101A, PROVIDE THE REQUIRED SERVICE AREA
 RECEPTACLE PER CODE. NEC 210.64
 13. SHEET E-101B, PROVIDE GFCI PROTECTION FOR ALL
 RECEPTACLE OUTLETS IN GARAGE. NEC 210.8(B)(8)
 14. SHEET E-102B, CIRCUIT AL-17 IS SHOWN FEEDING THE
 TRATAM ROOM. WHAT IS THIS ROOM USED FOR, IS GFCI
 PROTECTION REQUIRED. PROVIDE CLARIFICATION AND/OR
 CORRECTION. NEC 210.8; WPB FBC 107.2.1
 15. SHEET E-102B, CIRCUIT AL-1, 3, 5 IS SHOWN FEEDING
 HP-2L-2, BUT THE PANEL SCHEDULE SHOWS CIRCUIT 1 AND 3
 FEEDING POOL RECEPTACLES. PROVIDE CORRECTION. WPB FBC
 107.2.1
 16. SHEET E-103, ALL RECEPTACLE OUTLETS IN CATERING
 KITCHEN AND PERFORMANCE KITCHEN REQUIRE GFCI
 PROTECTION. PROVIDE CORRECTION. NEC 210.8(B)(2)
 17. SHEET E-104, DETAIL 3 IS SPECIFIED TO BE ON SHEET
 E-701WHICH WAS NOT PROVIDED IN SUBMISSION. PROVIDE
 CORRECTION. WPB FBC 107.2.1
 18. SHEET E-104, CORRIDOR RECEPTACLE OUTLETS ARE MARKED
 AS EITHER ?CC? OR ?CC1?. WHAT DOES THIS DESIGNATION
 MEAN? PROVIDE CLARIFICATION. WPB FBC 107.2.1
 19. SHEET E-106, DETAIL 5 IS SPECIFIED TO BE ON SHEET
 E-701WHICH WAS NOT PROVIDED IN SUBMISSION. PROVIDE
 CORRECTION. WPB FBC 107.2.1
 20. SHEET E-106, CORRIDOR RECEPTACLE OUTLETS ARE MARKED
 AS EITHER ?CC? OR ?CC1?. WHAT DOES THIS DESIGNATION
 MEAN? PROVIDE CLARIFICATION. WPB FBC 107.2.1
 21. SHEET E-107, DETAIL 4 IS SPECIFIED TO BE ON SHEET
 E-701WHICH WAS NOT PROVIDED IN SUBMISSION. PROVIDE
 CORRECTION. WPB FBC 107.2.1
 22. SHEET E-108, DETAIL 1 IS SPECIFIED TO BE ON SHEET
 E-702 WHICH WAS NOT PROVIDED IN SUBMISSION. PROVIDE
 CORRECTION. WPB FBC 107.2.1
 23. SHEET E-220, KEYNOTE 1 SPECIFIES THE 2008 NEC AS
 BASIS FOR DESIGN. PROVIDE CORRECTION. FBC PREFACE
 24. SHEET E-220, PANEL SCHEDULE PROVIDED DOES NOT SHOW
 AFCI PROTECTION PER CODE. SEE COMMENT NUMBER 3. PROVIDE
 CORRECTION. NEC 210.12
 25. SHEET E-220, PROVIDE GFCI PROTECTION FOR
 DISHWASHER. NEC 210.8(D)
 26. SHEET E-220, LABEL ROOMS TO FACILITATE CODE
 COMPLIANCE. WPB FBC 107.2.1
 27. SHEET E-220, PANEL IS SHOWN AS 120/240 VOLT SINGLE
 PHASE. ACCORDING TO THE RISER DIAGRAM, PANELS WILL BE
 120/208 VOLT SINGLE PHASE. PROVIDE CORRECTION. WPB FBC
 107.2.1
 28. SHEET E-220, PROVIDE GFCI RECEPTACLE ON EACH
 BALCONY ACCESSIBLE FROM UNIT. NEC 210.52(E)(3)
 29. SHEET E-221, KEYNOTE 1 SPECIFIES THE 2008 NEC AS
 BASIS FOR DESIGN. PROVIDE CORRECTION. FBC PREFACE
 30. SHEET E-221, PANEL SCHEDULE PROVIDED DOES NOT SHOW
 AFCI PROTECTION PER CODE. SEE COMMENT NUMBER 3. PROVIDE
 CORRECTION. NEC 210.12
 31. SHEET E-221, PROVIDE GFCI PROTECTION FOR
 DISHWASHER. NEC 210.8(D)
 32. SHEET E-221, LABEL ROOMS TO FACILITATE CODE
 COMPLIANCE. WPB FBC 107.2.1
 33. SHEET E-221, PANEL IS SHOWN AS 120/240 VOLT SINGLE
 PHASE. ACCORDING TO THE RISER DIAGRAM, PANELS WILL BE
 120/208 VOLT SINGLE PHASE. PROVIDE CORRECTION. WPB FBC
 107.2.1
 34. SHEET E-221, A GFCI PROTECTED RECEPTACLE OUTLET ON
 A 20 AMP CIRCUIT IS REQUIRED WITHIN 3 FEET OF EACH
 BASIN. PROVIDE CORRECTION. NEC 210.11(C)(3), 210.52(D)
 35. SHEET E-222, KEYNOTE 1 SPECIFIES THE 2008 NEC AS
 BASIS FOR DESIGN. PROVIDE CORRECTION. FBC PREFACE
 36. SHEET E-222, PANEL SCHEDULE PROVIDED DOES NOT SHOW
 AFCI PROTECTION PER CODE. SEE COMMENT NUMBER 3. PROVIDE
 CORRECTION. NEC 210.12
 37. SHEET E-222, PROVIDE GFCI PROTECTION FOR
 DISHWASHER. NEC 210.8(D)
 38. SHEET E-222, LABEL ROOMS TO FACILITATE CODE
 COMPLIANCE. WPB FBC 107.2.1
 39. SHEET E-222, PANEL IS SHOWN AS 120/240 VOLT SINGLE
 PHASE. ACCORDING TO THE RISER DIAGRAM, PANELS WILL BE
 120/208 VOLT SINGLE PHASE. PROVIDE CORRECTION. WPB FBC
 107.2.1
 40. SHEET E-223, KEYNOTE 1 SPECIFIES THE 2008 NEC AS
 BASIS FOR DESIGN. PROVIDE CORRECTION. FBC PREFACE
 41. SHEET E-223, PANEL SCHEDULE PROVIDED DOES NOT SHOW
 AFCI PROTECTION PER CODE. SEE COMMENT NUMBER 3. PROVIDE
 CORRECTION. NEC 210.12
 42. SHEET E-223, PROVIDE GFCI PROTECTION FOR
 DISHWASHER. NEC 210.8(D)
 43. SHEET E-223, LABEL ROOMS TO FACILITATE CODE
 COMPLIANCE. WPB FBC 107.2.1
 44. SHEET E-224, PANEL IS SHOWN AS 120/240 VOLT SINGLE
 PHASE. ACCORDING TO THE RISER DIAGRAM, PANELS WILL BE
 120/208 VOLT SINGLE PHASE. PROVIDE CORRECTION. WPB FBC
 107.2.1
 45. SHEET E-223, PROVIDE GFCI RECEPTACLE ON EACH
 BALCONY ACCESSIBLE FROM UNIT. NEC 210.52(E)(3)
 46. SHEET E-224, KEYNOTE 1 SPECIFIES THE 2008 NEC AS
 BASIS FOR DESIGN. PROVIDE CORRECTION. FBC PREFACE
 47. SHEET E-224, PANEL SCHEDULE PROVIDED DOES NOT SHOW
 AFCI PROTECTION PER CODE. SEE COMMENT NUMBER 3. PROVIDE
 CORRECTION. NEC 210.12
 48. SHEET E-224, PROVIDE GFCI PROTECTION FOR
 DISHWASHER. NEC 210.8(D)
 49. SHEET E-224, LABEL ROOMS TO FACILITATE CODE
 COMPLIANCE. WPB FBC 107.2.1
 50. SHEET E-224, PANEL IS SHOWN AS 120/240 VOLT SINGLE
 PHASE. ACCORDING TO THE RISER DIAGRAM, PANELS WILL BE
 120/208 VOLT SINGLE PHASE. PROVIDE CORRECTION. WPB FBC
 107.2.1
 51. SHEET E-225, KEYNOTE 1 SPECIFIES THE 2008 NEC AS
 BASIS FOR DESIGN. PROVIDE CORRECTION. FBC PREFACE
 52. SHEET E-225, PANEL SCHEDULE PROVIDED DOES NOT SHOW
 AFCI PROTECTION PER CODE. SEE COMMENT NUMBER 3. PROVIDE
 CORRECTION. NEC 210.12
 53. SHEET E-225, PROVIDE GFCI PROTECTION FOR
 DISHWASHER. NEC 210.8(D)
 54. SHEET E-225, LABEL ROOMS TO FACILITATE CODE
 COMPLIANCE. WPB FBC 107.2.1
 55. SHEET E-225, PANEL IS SHOWN AS 120/240 VOLT SINGLE
 PHASE. ACCORDING TO THE RISER DIAGRAM, PANELS WILL BE
 120/208 VOLT SINGLE PHASE. PROVIDE CORRECTION. WPB FBC
 107.2.1
 56. SHEET E-225, COMPLETE PLAN FOR UNIT F IS NOT ON
 PLAN SHEET, IT APPEARS TO HAVE BEEN CUT OFF. PROVIDE
 COMPLETE FLOOR PLAN FOR UNIT F ON PLAN SHEET. WPB FBC
 107.2.1
 57. SHEET E-226, KEYNOTE 1 SPECIFIES THE 2008 NEC AS
 BASIS FOR DESIGN. PROVIDE CORRECTION. FBC PREFACE
 58. SHEET E-226, PANEL SCHEDULE PROVIDED DOES NOT SHOW
 AFCI PROTECTION PER CODE. SEE COMMENT NUMBER 3. PROVIDE
 CORRECTION. NEC 210.12
 59. SHEET E-226, PROVIDE GFCI PROTECTION FOR
 DISHWASHER. NEC 210.8(D)
 60. SHEET E-226, LABEL ROOMS TO FACILITATE CODE
 COMPLIANCE. WPB FBC 107.2.1
 61. SHEET E-226, PANEL IS SHOWN AS 120/240 VOLT SINGLE
 PHASE. ACCORDING TO THE RISER DIAGRAM, PANELS WILL BE
 120/208 VOLT SINGLE PHASE. PROVIDE CORRECTION. WPB FBC
 107.2.1
 62. SHEET E-227, KEYNOTE 1 SPECIFIES THE 2008 NEC AS
 BASIS FOR DESIGN. PROVIDE CORRECTION. FBC PREFACE
 63. SHEET E-227, PANEL SCHEDULE PROVIDED DOES NOT SHOW
 AFCI PROTECTION PER CODE. SEE COMMENT NUMBER 3. PROVIDE
 CORRECTION. NEC 210.12
 64. SHEET E-227, PROVIDE GFCI PROTECTION FOR
 DISHWASHER. NEC 210.8(D)
 65. SHEET E-227, LABEL ROOMS TO FACILITATE CODE
 COMPLIANCE. WPB FBC 107.2.1
 66. SHEET E-227, PANEL IS SHOWN AS 120/240 VOLT SINGLE
 PHASE. ACCORDING TO THE RISER DIAGRAM, PANELS WILL BE
 120/208 VOLT SINGLE PHASE. PROVIDE CORRECTION. WPB FBC
 107.2.1
 67. SHEET E-227, RECEPTACLE OUTLETS INSTALLED IN
 LAUNDRY AREAS SHALL HAVE GFCI PROTECTION. PROVIDE
 CORRECTION. NEC 210.8(A)(9)
 68. SHEET E-228, KEYNOTE 1 SPECIFIES THE 2008 NEC AS
 BASIS FOR DESIGN. PROVIDE CORRECTION. FBC PREFACE
 69. SHEET E-228, PANEL SCHEDULE PROVIDED DOES NOT SHOW
 AFCI PROTECTION PER CODE. SEE COMMENT NUMBER 3. PROVIDE
 CORRECTION. NEC 210.12
 70. SHEET E-228, PROVIDE GFCI PROTECTION FOR
 DISHWASHER. NEC 210.8(D)
 71. SHEET E-228, LABEL ROOMS TO FACILITATE CODE
 COMPLIANCE. WPB FBC 107.2.1
 72. SHEET E-228, PANEL IS SHOWN AS 120/240 VOLT SINGLE
 PHASE. ACCORDING TO THE RISER DIAGRAM, PANELS WILL BE
 120/208 VOLT SINGLE PHASE. PROVIDE CORRECTION. WPB FBC
 107.2.1
 73. SHEET E-229, KEYNOTE 1 SPECIFIES THE 2008 NEC AS
 BASIS FOR DESIGN. PROVIDE CORRECTION. FBC PREFACE
 74. SHEET E-229, PANEL SCHEDULE PROVIDED DOES NOT SHOW
 AFCI PROTECTION PER CODE. SEE COMMENT NUMBER 3. PROVIDE
 CORRECTION. NEC 210.12
 75. SHEET E-229, PROVIDE GFCI PROTECTION FOR
 DISHWASHER. NEC 210.8(D)
 76. SHEET E-229, LABEL ROOMS TO FACILITATE CODE
 COMPLIANCE. WPB FBC 107.2.1
 77. SHEET E-229, PANEL IS SHOWN AS 120/240 VOLT SINGLE
 PHASE. ACCORDING TO THE RISER DIAGRAM, PANELS WILL BE
 120/208 VOLT SINGLE PHASE. PROVIDE CORRECTION. WPB FBC
 107.2.1
 78. SHEET E-229, A GFCI PROTECTED RECEPTACLE OUTLET ON
 A 20 AMP CIRCUIT IS REQUIRED WITHIN 3 FEET OF EACH
 BASIN. PROVIDE CORRECTION. NEC 210.11(C)(3), 210.52(D)
 79. SHEET E-230, KEYNOTE 1 SPECIFIES THE 2008 NEC AS
 BASIS FOR DESIGN. PROVIDE CORRECTION. FBC PREFACE
 80. SHEET E-230, PANEL SCHEDULE PROVIDED DOES NOT SHOW
 AFCI PROTECTION PER CODE. SEE COMMENT NUMBER 3. PROVIDE
 CORRECTION. NEC 210.12
 81. SHEET E-230, PROVIDE GFCI PROTECTION FOR
 DISHWASHER. NEC 210.8(D)
 82. SHEET E-230, LABEL ROOMS TO FACILITATE CODE
 COMPLIANCE. WPB FBC 107.2.1
 83. SHEET E-230, PANEL IS SHOWN AS 120/240 VOLT SINGLE
 PHASE. ACCORDING TO THE RISER DIAGRAM, PANELS WILL BE
 120/208 VOLT SINGLE PHASE. PROVIDE CORRECTION. WPB FBC
 107.2.1
 84. LIGHTING SHEETS (ALL) DO NOT SHOW THE AUTOMATIC
 CONTROL REQUIRED. PROVIDE THE ADDITIONAL AUTOMATIC
 LIGHTING CONTROLS STIPULATED IN THE FBC ENERGY CODE.
 FBC EC C405.2
 85. PROVIDE GRAPH/CALCULATION OF EXTERIOR LIGHTING
 POWER ALLOWANCES PER THE FBC ENERGY CONSERVATION IN
 RELATION TO THE CONNECTED EXTERIOR LIGHTING PROPOSED TO
 COMPLY WITH CODE. FBC EC C405.5.1
 86. SHEET E-501, NOTE 4 SPECS A 2500 KW GENERATOR.
 SHEET E-502, THE RISER DIAGRAM SHOWS A 1000 KW
 GENERATOR. PROVIDE CLARIFICATION AND CORRECTION. WPB
 FBC 107.2.1
 87. SHEET E-501, LABEL ALL FEEDERS TO SHOW WIRE AND
 CONDUIT SIZE. WPB FBC 107.2.1; NEC 310.15
 88. SHEET E-502, PLAN STATES THAT IT IS NOT FOR
 CONSTRUCTION OR PERMIT PURPOSES. REMOVE STATEMENT AND
 PROVIDE COMPLETED PERMIT SET FOR REVIEW. WPB FBC
 107.2.1
 89. SHEET E-502 IS LABELED AS THE RESIDENTIAL RISER
 DIAGRAM, WHICH IS ALSO WHAT E-501 IS LABELED. PROVIDE
 CORRECTION. WPB FBC 107.2.1
 90. SHEET E-502 STATES THAT THERE WILL BE A 125
 HORSEPOWER FIRE PUMP. SHEET E-601A STATES THAT THE FIRE
 PUMP WILL BE 200 HORSEPOWER. CORRECT DISCREPANCY.
 CORRECT LOAD CALCULATION AND WIRE SIZE AS NEEDED FOR
 FIRE PUMP FEED. NEC 695.6; WPB FBC 107.2.1
 91. SHEET E-502, LABEL ALL FEEDERS TO SHOW WIRE AND
 CONDUIT SIZE. WPB FBC 107.2.1; NEC 310.15
 92. SHEET E-502, THE SIZE OF THE MAINS IS NOT SHOWN ON
 PLAN. PROVIDE CORRECTION. WPB FBC 107.2.1
 93. PROVIDE GROUND FAULT PROTECTION FOR MAINS AS PER
 CODE. NEC 230.95
 94. PROVIDE DETAILS OF ARC FLASH MITIGATION FOR ALL
 MAINS PER CODE. NEC 240.87
 95. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR
 EACH PANEL INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE
 SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE.
 NEC 110.9, 110.10
 96. ON RISER DIAGRAM PANEL EQPH IS SHOWN AS A 100 AMP
 PANEL. IN THE PANEL SCHEDULE FOR THIS PANEL, IT IS
 SHOWN AS AN 800 AMP PANEL. PROVIDE CORRECTION. WPB FBC
 107.2.1
 97. ON RISER DIAGRAM PANEL EQEH IS SHOWN AS A 1200 AMP
 PANEL. IN THE PANEL SCHEDULE FOR THIS PANEL, IT IS
 SHOWN AS AN 800 AMP PANEL. PROVIDE CORRECTION. WPB FBC
 107.2.1
 98. ON RISER DIAGRAM PANEL EDPH IS SHOWN AS A 600 AMP
 PANEL. IN THE PANEL SCHEDULE FOR THIS PANEL, IT IS
 SHOWN AS AN 1200 AMP PANEL. PROVIDE CORRECTION. WPB FBC
 107.2.1
 99. IN REFERENCE TO COMMENTS 96, 97, AND 98, CORRECT
 THE SIZING OF TRANSFER SWITCHES 1, 2, AND 3 TO
 CORRESPOND TO THE PANELS THAT THEY FEED. WPB FBC
 107.2.1
 100. GENERATOR SHOWN ON RISER DIAGRAM APPEARS TO FEED
 SOME SORT OF PANEL AND THEN BRANCHES OUT TO THE
 TRANSFER SWITCHES. PROVIDE CLARIFICATION. PROVIDE PANEL
 SCHEDULE IS THIS IS A PANEL. WPB FBC 107.2.1; NEC
 408.4, 408.30, 408.36
 101. SHEET E-602, PANEL EM AND PANEL GMP ARE SHOWN
 FEEDING THE SAME LOADS. PROVIDE CLARIFICATION AND
 CORRECTION. WPB FBC 107.2.1
 102. AS ADJUSTMENTS ARE MADE TO DISCREPANCIES IN PLAN,
 PROVIDE UPDATED LOAD CALCULATION FOR EACH PANEL AND
 SERVICE. NEC 220
 103. SHEET E-601A, LOADS LISTED FOR LOAD CALCULATION
 SHOWN ARE MUCH DIFFERENT THAN THE LOADS SHOWN IN THE
 CORRESPONDING PANEL SCHEDULES. PROVIDE CLARIFICATION
 AND CORRECTION. WPB FBC 107.2.1; NEC 220
 104. WHERE ARE ELEVATORS FED FROM? I COULD NOT FIND
 THIS LOAD INCLUDED IN THE LOAD CALCULATION OR IN ANY
 PANEL SCHEDULES. PROVIDE CORRECTION. WPB FBC 107.2.1;
 NEC 220
 105. MANY OF THE PANEL SCHEDULES PROVIDED ARE
 INCOMPLETE. HOW CAN AN ACCURATE LOAD CALCULATION BE
 PROVIDED WITH THIS MUCH MISSING INFORMATION. PROVIDE
 CORRECTION. WPB FBC 107.2.1; NEC 220
 106. RISER DIAGRAM STATES THAT MDP1 IS ONE OF THE
 MAINS. THE PANEL SCHEDULE FOR THIS PANEL DOES NOT SHOW
 A MAIN. PROVIDE CORRECTION. WPB FBC 107.2.1; NEC 230.2
 107. LOAD FOR PANEL H SHOWN IN PANEL SCHEDULE FOR PANEL
 MDP1 IS MUCH DIFFERENT THAN THE LOAD SHOWN IN THE PANEL
 SCHEDULE FOR PANEL H. PROVIDE CORRECTION. WPB FBC
 107.2.1; NEC 220
 108. RISER DIAGRAM STATES THAT THE EMERGENCY MAINS ARE
 MAINS 2 AND 3. THE PANEL SCHEDULE FOR THESE PANELS DOES
 NOT SHOW A MAIN. PROVIDE CORRECTION. WPB FBC 107.2.1;
 NEC 230.2
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  
  