| 2018-10-18 08:58:07 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | BE ADVISED THAT THERE IS SO MUCH CONFLICTING AND |
| | INCOMPLETE INFORMATION ON THIS SUBMISSION THAT A FULL |
| | REVIEW WILL BE REQUIRED FOR THE SECOND REVIEW, LIKELY |
| | RESULTING IN FURTHER COMMENTS. |
| | |
| | 1. SHEET E-001, PLAN STATES THAT IT IS NOT FOR |
| | CONSTRUCTION OR PERMIT PURPOSES. REMOVE STATEMENT AND |
| | PROVIDE COMPLETED PERMIT SET FOR REVIEW. WPB FBC |
| | 107.2.1 |
| | 2. SHEET E-001, NOTE 4, THE NEC AND FBC SPECIFIED FOR |
| | DESIGN IS NOT THE CURRENT CODE. PROVIDE CORRECTION. FBC |
| | PREFACE (ALSO SEE CURRENT CODES ABOVE) |
| | 3. SHEET E-001, NOTE 63, AFCI PROTECTION SHOWN IN NOT |
| | CODE COMPLIANT. ALL BRANCH CIRCUITS THAT SUPPLY |
| | 120-VOLT, SINGLE-PHASE, 15- AND 20-AMPERE OUTLETS |
| | INSTALLED IN KITCHENS, FAMILY ROOMS, DINING ROOMS, |
| | LIVING ROOMS, PARLORS, LIBRARIES, DENS, BEDROOMS, |
| | SUN-ROOMS, RECREATIONS ROOMS, CLOSETS, HALLWAYS, |
| | LAUNDRY AREAS AND SIMILAR ROOMS OR AREAS SHALL BE AFCI |
| | PROTECTED. THIS INCLUDES LIGHTING AND POWER OUTLETS AND |
| | RECEPTACLES. SOME AREAS REQUIRE BOTH AFCI AND GFCI |
| | PROTECTION. PROVIDE CORRECTION. NEC 210.8, 210.12 |
| | 4. SHEET E-001, NOTE 68, STATES THAT RECEPTACLES SHALL |
| | BE TAMPER RESISTANT PER NEC 406.11. THIS CODE SECTION |
| | DOES NOT APPLY TO TAMPER RESISTANT RECEPTACLES. PROVIDE |
| | CORRECTION. NEC 406.12 |
| | 5. SHEET E-001, NOTE 79, REFERS TO THE 2010 FBC FOR |
| | STAIRS. PROVIDE CLARIFICATION FOR PERTINENCE TO |
| | ELECTRICAL REVIEW. PROVIDE CORRECT CODE FOR DESIGN. WPB |
| | FBC 107.2.1; FBC PREFACE (ALSO SEE CURRENT CODES ABOVE) |
| | 6. SHEET E-001, NOTE 80, THE NEC AND FBC SPECIFIED FOR |
| | DESIGN IS NOT THE CURRENT CODE. PROVIDE CORRECTION. FBC |
| | PREFACE (ALSO SEE CURRENT CODES ABOVE) |
| | 7. SHEET E-101, PROVIDE GFCI PROTECTION FOR ALL |
| | RECEPTACLE OUTLETS IN GARAGE. NEC 210.8(B)(8) |
| | 8. SHEET E-101, DETAILS ARE SPECIFIED TO BE ON SHEET |
| | E-701WHICH WAS NOT PROVIDED IN SUBMISSION. PROVIDE |
| | CORRECTION. WPB FBC 107.2.1 |
| | 9. SHEET E-101, DETAILS ARE SPECIFIED TO BE ON SHEET |
| | E-702 WHICH WAS NOT PROVIDED IN SUBMISSION. PROVIDE |
| | CORRECTION. WPB FBC 107.2.1 |
| | 10. SHEET E-101, DETAIL 1 FOR MAIN ELECTRICAL ROOM IS |
| | MISSING. PROVIDE CORRECTION. WPB FBC 107.2.1 |
| | 11. SHEET E-101A, PROVIDE GFCI PROTECTED RECEPTACLE |
| | OUTLET FOR SERVICING OF A/C EQUIPMENT WITHIN 25 FEET OF |
| | THE EQUIPMENT PER CODE. NEC 210.63 |
| | 12. SHEET E-101A, PROVIDE THE REQUIRED SERVICE AREA |
| | RECEPTACLE PER CODE. NEC 210.64 |
| | 13. SHEET E-101B, PROVIDE GFCI PROTECTION FOR ALL |
| | RECEPTACLE OUTLETS IN GARAGE. NEC 210.8(B)(8) |
| | 14. SHEET E-102B, CIRCUIT AL-17 IS SHOWN FEEDING THE |
| | TRATAM ROOM. WHAT IS THIS ROOM USED FOR, IS GFCI |
| | PROTECTION REQUIRED. PROVIDE CLARIFICATION AND/OR |
| | CORRECTION. NEC 210.8; WPB FBC 107.2.1 |
| | 15. SHEET E-102B, CIRCUIT AL-1, 3, 5 IS SHOWN FEEDING |
| | HP-2L-2, BUT THE PANEL SCHEDULE SHOWS CIRCUIT 1 AND 3 |
| | FEEDING POOL RECEPTACLES. PROVIDE CORRECTION. WPB FBC |
| | 107.2.1 |
| | 16. SHEET E-103, ALL RECEPTACLE OUTLETS IN CATERING |
| | KITCHEN AND PERFORMANCE KITCHEN REQUIRE GFCI |
| | PROTECTION. PROVIDE CORRECTION. NEC 210.8(B)(2) |
| | 17. SHEET E-104, DETAIL 3 IS SPECIFIED TO BE ON SHEET |
| | E-701WHICH WAS NOT PROVIDED IN SUBMISSION. PROVIDE |
| | CORRECTION. WPB FBC 107.2.1 |
| | 18. SHEET E-104, CORRIDOR RECEPTACLE OUTLETS ARE MARKED |
| | AS EITHER ?CC? OR ?CC1?. WHAT DOES THIS DESIGNATION |
| | MEAN? PROVIDE CLARIFICATION. WPB FBC 107.2.1 |
| | 19. SHEET E-106, DETAIL 5 IS SPECIFIED TO BE ON SHEET |
| | E-701WHICH WAS NOT PROVIDED IN SUBMISSION. PROVIDE |
| | CORRECTION. WPB FBC 107.2.1 |
| | 20. SHEET E-106, CORRIDOR RECEPTACLE OUTLETS ARE MARKED |
| | AS EITHER ?CC? OR ?CC1?. WHAT DOES THIS DESIGNATION |
| | MEAN? PROVIDE CLARIFICATION. WPB FBC 107.2.1 |
| | 21. SHEET E-107, DETAIL 4 IS SPECIFIED TO BE ON SHEET |
| | E-701WHICH WAS NOT PROVIDED IN SUBMISSION. PROVIDE |
| | CORRECTION. WPB FBC 107.2.1 |
| | 22. SHEET E-108, DETAIL 1 IS SPECIFIED TO BE ON SHEET |
| | E-702 WHICH WAS NOT PROVIDED IN SUBMISSION. PROVIDE |
| | CORRECTION. WPB FBC 107.2.1 |
| | 23. SHEET E-220, KEYNOTE 1 SPECIFIES THE 2008 NEC AS |
| | BASIS FOR DESIGN. PROVIDE CORRECTION. FBC PREFACE |
| | 24. SHEET E-220, PANEL SCHEDULE PROVIDED DOES NOT SHOW |
| | AFCI PROTECTION PER CODE. SEE COMMENT NUMBER 3. PROVIDE |
| | CORRECTION. NEC 210.12 |
| | 25. SHEET E-220, PROVIDE GFCI PROTECTION FOR |
| | DISHWASHER. NEC 210.8(D) |
| | 26. SHEET E-220, LABEL ROOMS TO FACILITATE CODE |
| | COMPLIANCE. WPB FBC 107.2.1 |
| | 27. SHEET E-220, PANEL IS SHOWN AS 120/240 VOLT SINGLE |
| | PHASE. ACCORDING TO THE RISER DIAGRAM, PANELS WILL BE |
| | 120/208 VOLT SINGLE PHASE. PROVIDE CORRECTION. WPB FBC |
| | 107.2.1 |
| | 28. SHEET E-220, PROVIDE GFCI RECEPTACLE ON EACH |
| | BALCONY ACCESSIBLE FROM UNIT. NEC 210.52(E)(3) |
| | 29. SHEET E-221, KEYNOTE 1 SPECIFIES THE 2008 NEC AS |
| | BASIS FOR DESIGN. PROVIDE CORRECTION. FBC PREFACE |
| | 30. SHEET E-221, PANEL SCHEDULE PROVIDED DOES NOT SHOW |
| | AFCI PROTECTION PER CODE. SEE COMMENT NUMBER 3. PROVIDE |
| | CORRECTION. NEC 210.12 |
| | 31. SHEET E-221, PROVIDE GFCI PROTECTION FOR |
| | DISHWASHER. NEC 210.8(D) |
| | 32. SHEET E-221, LABEL ROOMS TO FACILITATE CODE |
| | COMPLIANCE. WPB FBC 107.2.1 |
| | 33. SHEET E-221, PANEL IS SHOWN AS 120/240 VOLT SINGLE |
| | PHASE. ACCORDING TO THE RISER DIAGRAM, PANELS WILL BE |
| | 120/208 VOLT SINGLE PHASE. PROVIDE CORRECTION. WPB FBC |
| | 107.2.1 |
| | 34. SHEET E-221, A GFCI PROTECTED RECEPTACLE OUTLET ON |
| | A 20 AMP CIRCUIT IS REQUIRED WITHIN 3 FEET OF EACH |
| | BASIN. PROVIDE CORRECTION. NEC 210.11(C)(3), 210.52(D) |
| | 35. SHEET E-222, KEYNOTE 1 SPECIFIES THE 2008 NEC AS |
| | BASIS FOR DESIGN. PROVIDE CORRECTION. FBC PREFACE |
| | 36. SHEET E-222, PANEL SCHEDULE PROVIDED DOES NOT SHOW |
| | AFCI PROTECTION PER CODE. SEE COMMENT NUMBER 3. PROVIDE |
| | CORRECTION. NEC 210.12 |
| | 37. SHEET E-222, PROVIDE GFCI PROTECTION FOR |
| | DISHWASHER. NEC 210.8(D) |
| | 38. SHEET E-222, LABEL ROOMS TO FACILITATE CODE |
| | COMPLIANCE. WPB FBC 107.2.1 |
| | 39. SHEET E-222, PANEL IS SHOWN AS 120/240 VOLT SINGLE |
| | PHASE. ACCORDING TO THE RISER DIAGRAM, PANELS WILL BE |
| | 120/208 VOLT SINGLE PHASE. PROVIDE CORRECTION. WPB FBC |
| | 107.2.1 |
| | 40. SHEET E-223, KEYNOTE 1 SPECIFIES THE 2008 NEC AS |
| | BASIS FOR DESIGN. PROVIDE CORRECTION. FBC PREFACE |
| | 41. SHEET E-223, PANEL SCHEDULE PROVIDED DOES NOT SHOW |
| | AFCI PROTECTION PER CODE. SEE COMMENT NUMBER 3. PROVIDE |
| | CORRECTION. NEC 210.12 |
| | 42. SHEET E-223, PROVIDE GFCI PROTECTION FOR |
| | DISHWASHER. NEC 210.8(D) |
| | 43. SHEET E-223, LABEL ROOMS TO FACILITATE CODE |
| | COMPLIANCE. WPB FBC 107.2.1 |
| | 44. SHEET E-224, PANEL IS SHOWN AS 120/240 VOLT SINGLE |
| | PHASE. ACCORDING TO THE RISER DIAGRAM, PANELS WILL BE |
| | 120/208 VOLT SINGLE PHASE. PROVIDE CORRECTION. WPB FBC |
| | 107.2.1 |
| | 45. SHEET E-223, PROVIDE GFCI RECEPTACLE ON EACH |
| | BALCONY ACCESSIBLE FROM UNIT. NEC 210.52(E)(3) |
| | 46. SHEET E-224, KEYNOTE 1 SPECIFIES THE 2008 NEC AS |
| | BASIS FOR DESIGN. PROVIDE CORRECTION. FBC PREFACE |
| | 47. SHEET E-224, PANEL SCHEDULE PROVIDED DOES NOT SHOW |
| | AFCI PROTECTION PER CODE. SEE COMMENT NUMBER 3. PROVIDE |
| | CORRECTION. NEC 210.12 |
| | 48. SHEET E-224, PROVIDE GFCI PROTECTION FOR |
| | DISHWASHER. NEC 210.8(D) |
| | 49. SHEET E-224, LABEL ROOMS TO FACILITATE CODE |
| | COMPLIANCE. WPB FBC 107.2.1 |
| | 50. SHEET E-224, PANEL IS SHOWN AS 120/240 VOLT SINGLE |
| | PHASE. ACCORDING TO THE RISER DIAGRAM, PANELS WILL BE |
| | 120/208 VOLT SINGLE PHASE. PROVIDE CORRECTION. WPB FBC |
| | 107.2.1 |
| | 51. SHEET E-225, KEYNOTE 1 SPECIFIES THE 2008 NEC AS |
| | BASIS FOR DESIGN. PROVIDE CORRECTION. FBC PREFACE |
| | 52. SHEET E-225, PANEL SCHEDULE PROVIDED DOES NOT SHOW |
| | AFCI PROTECTION PER CODE. SEE COMMENT NUMBER 3. PROVIDE |
| | CORRECTION. NEC 210.12 |
| | 53. SHEET E-225, PROVIDE GFCI PROTECTION FOR |
| | DISHWASHER. NEC 210.8(D) |
| | 54. SHEET E-225, LABEL ROOMS TO FACILITATE CODE |
| | COMPLIANCE. WPB FBC 107.2.1 |
| | 55. SHEET E-225, PANEL IS SHOWN AS 120/240 VOLT SINGLE |
| | PHASE. ACCORDING TO THE RISER DIAGRAM, PANELS WILL BE |
| | 120/208 VOLT SINGLE PHASE. PROVIDE CORRECTION. WPB FBC |
| | 107.2.1 |
| | 56. SHEET E-225, COMPLETE PLAN FOR UNIT F IS NOT ON |
| | PLAN SHEET, IT APPEARS TO HAVE BEEN CUT OFF. PROVIDE |
| | COMPLETE FLOOR PLAN FOR UNIT F ON PLAN SHEET. WPB FBC |
| | 107.2.1 |
| | 57. SHEET E-226, KEYNOTE 1 SPECIFIES THE 2008 NEC AS |
| | BASIS FOR DESIGN. PROVIDE CORRECTION. FBC PREFACE |
| | 58. SHEET E-226, PANEL SCHEDULE PROVIDED DOES NOT SHOW |
| | AFCI PROTECTION PER CODE. SEE COMMENT NUMBER 3. PROVIDE |
| | CORRECTION. NEC 210.12 |
| | 59. SHEET E-226, PROVIDE GFCI PROTECTION FOR |
| | DISHWASHER. NEC 210.8(D) |
| | 60. SHEET E-226, LABEL ROOMS TO FACILITATE CODE |
| | COMPLIANCE. WPB FBC 107.2.1 |
| | 61. SHEET E-226, PANEL IS SHOWN AS 120/240 VOLT SINGLE |
| | PHASE. ACCORDING TO THE RISER DIAGRAM, PANELS WILL BE |
| | 120/208 VOLT SINGLE PHASE. PROVIDE CORRECTION. WPB FBC |
| | 107.2.1 |
| | 62. SHEET E-227, KEYNOTE 1 SPECIFIES THE 2008 NEC AS |
| | BASIS FOR DESIGN. PROVIDE CORRECTION. FBC PREFACE |
| | 63. SHEET E-227, PANEL SCHEDULE PROVIDED DOES NOT SHOW |
| | AFCI PROTECTION PER CODE. SEE COMMENT NUMBER 3. PROVIDE |
| | CORRECTION. NEC 210.12 |
| | 64. SHEET E-227, PROVIDE GFCI PROTECTION FOR |
| | DISHWASHER. NEC 210.8(D) |
| | 65. SHEET E-227, LABEL ROOMS TO FACILITATE CODE |
| | COMPLIANCE. WPB FBC 107.2.1 |
| | 66. SHEET E-227, PANEL IS SHOWN AS 120/240 VOLT SINGLE |
| | PHASE. ACCORDING TO THE RISER DIAGRAM, PANELS WILL BE |
| | 120/208 VOLT SINGLE PHASE. PROVIDE CORRECTION. WPB FBC |
| | 107.2.1 |
| | 67. SHEET E-227, RECEPTACLE OUTLETS INSTALLED IN |
| | LAUNDRY AREAS SHALL HAVE GFCI PROTECTION. PROVIDE |
| | CORRECTION. NEC 210.8(A)(9) |
| | 68. SHEET E-228, KEYNOTE 1 SPECIFIES THE 2008 NEC AS |
| | BASIS FOR DESIGN. PROVIDE CORRECTION. FBC PREFACE |
| | 69. SHEET E-228, PANEL SCHEDULE PROVIDED DOES NOT SHOW |
| | AFCI PROTECTION PER CODE. SEE COMMENT NUMBER 3. PROVIDE |
| | CORRECTION. NEC 210.12 |
| | 70. SHEET E-228, PROVIDE GFCI PROTECTION FOR |
| | DISHWASHER. NEC 210.8(D) |
| | 71. SHEET E-228, LABEL ROOMS TO FACILITATE CODE |
| | COMPLIANCE. WPB FBC 107.2.1 |
| | 72. SHEET E-228, PANEL IS SHOWN AS 120/240 VOLT SINGLE |
| | PHASE. ACCORDING TO THE RISER DIAGRAM, PANELS WILL BE |
| | 120/208 VOLT SINGLE PHASE. PROVIDE CORRECTION. WPB FBC |
| | 107.2.1 |
| | 73. SHEET E-229, KEYNOTE 1 SPECIFIES THE 2008 NEC AS |
| | BASIS FOR DESIGN. PROVIDE CORRECTION. FBC PREFACE |
| | 74. SHEET E-229, PANEL SCHEDULE PROVIDED DOES NOT SHOW |
| | AFCI PROTECTION PER CODE. SEE COMMENT NUMBER 3. PROVIDE |
| | CORRECTION. NEC 210.12 |
| | 75. SHEET E-229, PROVIDE GFCI PROTECTION FOR |
| | DISHWASHER. NEC 210.8(D) |
| | 76. SHEET E-229, LABEL ROOMS TO FACILITATE CODE |
| | COMPLIANCE. WPB FBC 107.2.1 |
| | 77. SHEET E-229, PANEL IS SHOWN AS 120/240 VOLT SINGLE |
| | PHASE. ACCORDING TO THE RISER DIAGRAM, PANELS WILL BE |
| | 120/208 VOLT SINGLE PHASE. PROVIDE CORRECTION. WPB FBC |
| | 107.2.1 |
| | 78. SHEET E-229, A GFCI PROTECTED RECEPTACLE OUTLET ON |
| | A 20 AMP CIRCUIT IS REQUIRED WITHIN 3 FEET OF EACH |
| | BASIN. PROVIDE CORRECTION. NEC 210.11(C)(3), 210.52(D) |
| | 79. SHEET E-230, KEYNOTE 1 SPECIFIES THE 2008 NEC AS |
| | BASIS FOR DESIGN. PROVIDE CORRECTION. FBC PREFACE |
| | 80. SHEET E-230, PANEL SCHEDULE PROVIDED DOES NOT SHOW |
| | AFCI PROTECTION PER CODE. SEE COMMENT NUMBER 3. PROVIDE |
| | CORRECTION. NEC 210.12 |
| | 81. SHEET E-230, PROVIDE GFCI PROTECTION FOR |
| | DISHWASHER. NEC 210.8(D) |
| | 82. SHEET E-230, LABEL ROOMS TO FACILITATE CODE |
| | COMPLIANCE. WPB FBC 107.2.1 |
| | 83. SHEET E-230, PANEL IS SHOWN AS 120/240 VOLT SINGLE |
| | PHASE. ACCORDING TO THE RISER DIAGRAM, PANELS WILL BE |
| | 120/208 VOLT SINGLE PHASE. PROVIDE CORRECTION. WPB FBC |
| | 107.2.1 |
| | 84. LIGHTING SHEETS (ALL) DO NOT SHOW THE AUTOMATIC |
| | CONTROL REQUIRED. PROVIDE THE ADDITIONAL AUTOMATIC |
| | LIGHTING CONTROLS STIPULATED IN THE FBC ENERGY CODE. |
| | FBC EC C405.2 |
| | 85. PROVIDE GRAPH/CALCULATION OF EXTERIOR LIGHTING |
| | POWER ALLOWANCES PER THE FBC ENERGY CONSERVATION IN |
| | RELATION TO THE CONNECTED EXTERIOR LIGHTING PROPOSED TO |
| | COMPLY WITH CODE. FBC EC C405.5.1 |
| | 86. SHEET E-501, NOTE 4 SPECS A 2500 KW GENERATOR. |
| | SHEET E-502, THE RISER DIAGRAM SHOWS A 1000 KW |
| | GENERATOR. PROVIDE CLARIFICATION AND CORRECTION. WPB |
| | FBC 107.2.1 |
| | 87. SHEET E-501, LABEL ALL FEEDERS TO SHOW WIRE AND |
| | CONDUIT SIZE. WPB FBC 107.2.1; NEC 310.15 |
| | 88. SHEET E-502, PLAN STATES THAT IT IS NOT FOR |
| | CONSTRUCTION OR PERMIT PURPOSES. REMOVE STATEMENT AND |
| | PROVIDE COMPLETED PERMIT SET FOR REVIEW. WPB FBC |
| | 107.2.1 |
| | 89. SHEET E-502 IS LABELED AS THE RESIDENTIAL RISER |
| | DIAGRAM, WHICH IS ALSO WHAT E-501 IS LABELED. PROVIDE |
| | CORRECTION. WPB FBC 107.2.1 |
| | 90. SHEET E-502 STATES THAT THERE WILL BE A 125 |
| | HORSEPOWER FIRE PUMP. SHEET E-601A STATES THAT THE FIRE |
| | PUMP WILL BE 200 HORSEPOWER. CORRECT DISCREPANCY. |
| | CORRECT LOAD CALCULATION AND WIRE SIZE AS NEEDED FOR |
| | FIRE PUMP FEED. NEC 695.6; WPB FBC 107.2.1 |
| | 91. SHEET E-502, LABEL ALL FEEDERS TO SHOW WIRE AND |
| | CONDUIT SIZE. WPB FBC 107.2.1; NEC 310.15 |
| | 92. SHEET E-502, THE SIZE OF THE MAINS IS NOT SHOWN ON |
| | PLAN. PROVIDE CORRECTION. WPB FBC 107.2.1 |
| | 93. PROVIDE GROUND FAULT PROTECTION FOR MAINS AS PER |
| | CODE. NEC 230.95 |
| | 94. PROVIDE DETAILS OF ARC FLASH MITIGATION FOR ALL |
| | MAINS PER CODE. NEC 240.87 |
| | 95. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR |
| | EACH PANEL INCLUDING INFORMATION FROM THE POWER COMPANY |
| | STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR |
| | THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE |
| | SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE. |
| | NEC 110.9, 110.10 |
| | 96. ON RISER DIAGRAM PANEL EQPH IS SHOWN AS A 100 AMP |
| | PANEL. IN THE PANEL SCHEDULE FOR THIS PANEL, IT IS |
| | SHOWN AS AN 800 AMP PANEL. PROVIDE CORRECTION. WPB FBC |
| | 107.2.1 |
| | 97. ON RISER DIAGRAM PANEL EQEH IS SHOWN AS A 1200 AMP |
| | PANEL. IN THE PANEL SCHEDULE FOR THIS PANEL, IT IS |
| | SHOWN AS AN 800 AMP PANEL. PROVIDE CORRECTION. WPB FBC |
| | 107.2.1 |
| | 98. ON RISER DIAGRAM PANEL EDPH IS SHOWN AS A 600 AMP |
| | PANEL. IN THE PANEL SCHEDULE FOR THIS PANEL, IT IS |
| | SHOWN AS AN 1200 AMP PANEL. PROVIDE CORRECTION. WPB FBC |
| | 107.2.1 |
| | 99. IN REFERENCE TO COMMENTS 96, 97, AND 98, CORRECT |
| | THE SIZING OF TRANSFER SWITCHES 1, 2, AND 3 TO |
| | CORRESPOND TO THE PANELS THAT THEY FEED. WPB FBC |
| | 107.2.1 |
| | 100. GENERATOR SHOWN ON RISER DIAGRAM APPEARS TO FEED |
| | SOME SORT OF PANEL AND THEN BRANCHES OUT TO THE |
| | TRANSFER SWITCHES. PROVIDE CLARIFICATION. PROVIDE PANEL |
| | SCHEDULE IS THIS IS A PANEL. WPB FBC 107.2.1; NEC |
| | 408.4, 408.30, 408.36 |
| | 101. SHEET E-602, PANEL EM AND PANEL GMP ARE SHOWN |
| | FEEDING THE SAME LOADS. PROVIDE CLARIFICATION AND |
| | CORRECTION. WPB FBC 107.2.1 |
| | 102. AS ADJUSTMENTS ARE MADE TO DISCREPANCIES IN PLAN, |
| | PROVIDE UPDATED LOAD CALCULATION FOR EACH PANEL AND |
| | SERVICE. NEC 220 |
| | 103. SHEET E-601A, LOADS LISTED FOR LOAD CALCULATION |
| | SHOWN ARE MUCH DIFFERENT THAN THE LOADS SHOWN IN THE |
| | CORRESPONDING PANEL SCHEDULES. PROVIDE CLARIFICATION |
| | AND CORRECTION. WPB FBC 107.2.1; NEC 220 |
| | 104. WHERE ARE ELEVATORS FED FROM? I COULD NOT FIND |
| | THIS LOAD INCLUDED IN THE LOAD CALCULATION OR IN ANY |
| | PANEL SCHEDULES. PROVIDE CORRECTION. WPB FBC 107.2.1; |
| | NEC 220 |
| | 105. MANY OF THE PANEL SCHEDULES PROVIDED ARE |
| | INCOMPLETE. HOW CAN AN ACCURATE LOAD CALCULATION BE |
| | PROVIDED WITH THIS MUCH MISSING INFORMATION. PROVIDE |
| | CORRECTION. WPB FBC 107.2.1; NEC 220 |
| | 106. RISER DIAGRAM STATES THAT MDP1 IS ONE OF THE |
| | MAINS. THE PANEL SCHEDULE FOR THIS PANEL DOES NOT SHOW |
| | A MAIN. PROVIDE CORRECTION. WPB FBC 107.2.1; NEC 230.2 |
| | 107. LOAD FOR PANEL H SHOWN IN PANEL SCHEDULE FOR PANEL |
| | MDP1 IS MUCH DIFFERENT THAN THE LOAD SHOWN IN THE PANEL |
| | SCHEDULE FOR PANEL H. PROVIDE CORRECTION. WPB FBC |
| | 107.2.1; NEC 220 |
| | 108. RISER DIAGRAM STATES THAT THE EMERGENCY MAINS ARE |
| | MAINS 2 AND 3. THE PANEL SCHEDULE FOR THESE PANELS DOES |
| | NOT SHOW A MAIN. PROVIDE CORRECTION. WPB FBC 107.2.1; |
| | NEC 230.2 |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY |
| | REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED |
| | SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD |
| | SHEETS. |
| | |