2018-11-15 17:45:15REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
 WPB PERMIT: 18081528
 ADD: 1515 S. FLAGLER DRIVE
 CONT:
 TEL:
 EMAIL:
  
 1) ART IN PUBLIC PLACES
 THE CITY OF WEST PALM BEACH ART IN PUBLIC PLACES
 ORDINANCE REQUIREMENT THAT APPLIES TO ANY REMODEL OR
 NEW CONSTRUCTION PROJECT FOR WHICH THE PERMIT
 APPLICATION WAS SUBMITTED AFTER 6/29/14, AND THE TOTAL
 PROJECT CONSTRUCTION COSTS ARE EQUAL TO OR GREATER THAN
 $750,000 WILL NEED TO COMPLY WITH THIS ORDINANCE.
 PER CITY OF WEST PALM BEACH ORDINANCE NO. 4504-14, AND
 CITY OF WEST PALM BEACH CODE OF ORDINANCES, ARTICLE V,
 ART IN PUBLIC PLACES, SECTION 78-123(A) AND SECTION
 78-126(A), THE ART ASSESSMENT IS 1% OF THE TOTAL
 PROJECT CONSTRUCTION COST.
 PER CITY OF WEST PALM BEACH CODE OF ORDINANCES, ARTICLE
 V, ART IN PUBLIC PLACES, SECTION 78-122, RENOVATION AND
 NEW CONSTRUCTION PROJECTS ARE ASSESSED CUMULATIVELY, SO
 THE ART ASSESSMENT WILL BE APPLICABLE TO ALL FUTURE
 PROJECTS.
 SEC. 78-129. - PUBLIC ART ASSESSMENT FOR PRIVATE
 DEVELOPMENT.
 (A) APPLICABILITY. THE PROVISIONS OF THIS ARTICLE AND
 THE PUBLIC ART ASSESSMENT SECTION SHALL APPLY TO ALL
 PRIVATE DEVELOPMENT PROJECTS, INCLUDING NEW
 CONSTRUCTION, OR THE RENOVATION OR IMPROVEMENT OF AN
 EXISTING BUILDING, WHERE TOTAL CONSTRUCTION COSTS ARE
 EQUAL TO OR GREATER THAN $750,000.00. ALL BUILDINGS
 WITHIN NEW PLANNED DEVELOPMENTS SHALL BE ASSESSED
 CUMULATIVELY TOWARDS THIS ART IN PUBLIC PLACES
 REQUIREMENT, EVEN IF THE BUILDINGS ARE PERMITTED
 SEPARATELY OR DEVELOPED IN PHASES. THE PROVISIONS OF
 THIS SECTION APPLY TO NEW DEVELOPMENT OR NEW
 CONSTRUCTION WITHIN EXISTING PLANNED DEVELOPMENTS.
 FOR CONTACT INFORMATION PLEASE CONTACT:
 MS. SYBILLE WELTER ART IN PUBLIC PLACES COORDINATOR
 822-1515 E-MAIL: [email protected]
  
 2) 109.3 BUILDING PERMIT VALUATION.
 IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE
 CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE,
 ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS
 APPEARS TO BE UNDER ESTIMATED ON THE APPLICATION, THE
 PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES,
 VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL
 REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND
 SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE
 STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR
 FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR
 BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING
 COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC.) WITH REGIONAL ADJUSTMENTS
 FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE
 CONGRESS.
 THIS MAIN BUILDING PERMIT WILL INCLUDE THE FEES FOR THE
 MECHANICAL, ELECTRICAL, PLUMBING & ROOFING PERMITS.
 WHEN THE GENERAL CONTRACTOR COMES IN FOR A BUILDING
 PERMIT WITH THE SIGNED PERMIT APPLICATION FORM BY THE
 QUALIFIER AND OWNER AND BRINGS IN THE LISTED
 SUB-PERMITS M-E-P & ROOFING PERMITS SIGNED BY THE
 QUALIFIER OF EACH COMPANY, THEIR INSURANCES AND
 LICENSURE UP TO DATE, THE M-E-P AND ROOFING PERMITS ARE
 FREE OF CHARGE. IF THE M-E-P & ROOFING PERMITS COME IN
 LATER THERE WILL BE AN $80.00 ADMINISTRATIVE FEE FOR
 EACH PERMIT.
 ALL OTHER PERMITS FIRE SPRINKLER, FIRE ALARM, RACK
 STORAGE, EXHAUST HOODS, ANSUL SYSTEMS OR ALTERNATIVE
 AUTOMATIC FIRE-EXTINGUISHING SYSTEMS, WALK IN COOLERS &
 FREEZERS, ALL LOW VOLTAGE PERMITS, GENERATORS & FUEL
 TANKS, GAS PERMIT, POOL, JACUZZI AND ASSOCIATED
 SUB-PERMITS, AWNING, SCREEN ENCLOSURES, CANOPY, FENCE,
 LANDSCAPE, IRRIGATION, AUGER CAST PILE AND OR
 FOUNDATION OR STRUCTURE ONLY PERMIT WILL BE SEPARATE
 REVIEWS AND ASSOCIATED FEES WITH EACH PERMIT.
 PLEASE PROVIDE AN ITEMIZED LIST AND SUBTRACT THESE LINE
 ITEMS AND THEIR VALUE FROM THE OVERALL BUILDING VALUE
 STATED ON THE PERMIT APPLICATION FOR THIS PROJECT. THE
 REMAINING BALANCE WILL BE AFFECTIVELY THE VALUE OF THE
 BUILDING YOU WILL BE PAYING FOR THIS PERMIT. THE
 BUILDING DEPARTMENT DOES NOT WANT TO COLLECT TWICE FOR
 THE VALUE OF THESE SUB-PERMITS NOT COVERED UNDER THE
 PRIME OR MASTER PERMIT.
  
 3) THIS PROJECT IS A THRESHOLD BUILDING / FL S. S.
 553.71(7) "THRESHOLD BUILDING" MEANING ANY BUILDING
 WHICH IS GREATER THAN (3) STORIES OR 50 FT. IN HEIGHT,
 OR WHICH HAS AN ASSEMBLY OCCUPANCY CLASSIFICATION AS
 DENIED IN THE FLORIDA BUILDING CODE WHICH EXCEEDS 5,000
 SQ. FT. IN AREA AND AN OCCUPANT CONTENT OF GREATER THAN
 500 PERSONS.
  
 A) FBC (CITY AMENDMENTS)110.8.1 THRESHOLD INSPECTION
 PLAN. THE ENFORCING AGENCY SHALL REQUIRE A SPECIAL
 INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON A
 THRESHOLD BUILDING PURSUANT TO A STRUCTURAL INSPECTION
 PLAN PREPARED BY THE ENGINEER OF RECORD. THE STRUCTURAL
 INSPECTION PLAN MUST BE SUBMITTED TO THE ENFORCING
 AGENCY PRIOR TO THE ISSUANCE OF A BUILDING PERMIT FOR
 THE CONSTRUCTION OF A THRESHOLD BUILDING. THE PURPOSE
 OF THE STRUCTURAL INSPECTION PLAN IS TO PROVIDE
 SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO THAT
 THE BUILDING CAN BE ADEQUATELY INSPECTED FOR COMPLIANCE
 WITH THE PERMITTED DOCUMENTS. THE SPECIAL INSPECTOR MAY
 NOT SERVE AS A SURROGATE IN CARRYING OUT THE
 RESPONSIBILITIES OF THE BUILDING OFFICIAL, THE
 ARCHITECT OR THE ENGINEER OF RECORD. THE CONTRACTOR'S
 CONTRACTUAL OR STATUTORY OBLIGATIONS ARE NOT RELIEVED
 BY ANY ACTION OF THE SPECIAL INSPECTOR.
  
 B) THRESHOLD INSPECTOR: WPB AMENDMENT 110.8.1 W.P.B.
 CONSTRUCTION SERVICES DEPARTMENT REQUEST FOR THRESHOLD
 BUILDINGS A SPECIAL INSPECTOR AS REQUIRED BY 553.79(5)
 FLORIDA STATUTES TO THE MINIMUM INSPECTIONS REQUIRED BY
 THIS CODE. THE THRESHOLD INSPECTION FORMS ARE REQUIRED
 TO BE FILED OUT BY ALL PARTIES WITH INTEREST, NOTARIZED
 AND RETURNED TO THIS OFFICE, AND REVIEWED AND APPROVED
 BEFORE PERMIT ISSUANCE WILL TAKE PLACE.
  
 C) THRESHOLD BLDG. REQUIRED STATEMENT: W.P.B. AMENDMENT
 110.8.4.4 ALL PLANS FOR THE BUILDING WHICH ARE REQUIRED
 TO BE SIGNED AND SEALED BY THE ARCHITECT OR ENGINEER OF
 RECORD CONTAIN A STATEMENT THAT, TO THE BEST OF THE
 ARCHITECT'S OR ENGINEER'S KNOWLEDGE, THE PLANS AND
 SPECIFICATIONS COMPLY WITH THE APPLICABLE MINIMUM
 BUILDING CODES AND THE APPLICABLE FIRE-SAFETY STANDARDS
 AS DETERMINED BY THE LOCAL AUTHORITY IN ACCORDANCE WITH
 THIS SECTION AND CHAPTER 633 FLORIDA STATUTES.
  
 D) FOR THE SPECIAL INSPECTOR PLEASE PROVIDE A RESUME OF
 INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE RESUME
 MUST BE ACCOMPANIED BY ALL CERTIFICATES AS SPECIFIED
 HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE WILL
 REVIEW THE RESUME. AFTER THE RESUME IS REVIEWED, AN
 INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES
 WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST
 MEETING THE ABOVE CRITERIA.
  
 E) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR HISTORY
 FOR THIS TYPE OF CONSTRUCTION.
  
 F) NOTE: FOR DIGITAL PLANS, AFTER PERMIT ISSUANCE,
 PLEASE E-MAIL THE PERMIT LIBRARIAN OF THE PERMIT BEING
 ISSUED, THE PERMIT LIBRARIAN WILL THEN E-MAIL YOU THE
 APPROVED AND BATCH STAMPED PLANS SO YOU MAY PRINT YOUR
 PLANS, TWO SETS OF PLANS WILL NEED TO BE PRINTED IN
 COLOR, (1) FOR THE THRESHOLD INSPECTOR, THE OTHER FOR
 THE MEP INSPECTORS OTHER PLANS YOU WISH TO PRINT MAYBE
 IN BLACK & WHITE.
  
 G) 110.8.4.3 ALL SHORING AND RESHORING PROCEDURES,
 PLANS AND DETAILS SHALL BE SUBMITTED TO THE ENFORCEMENT
 AGENCY FOR RECORDKEEPING. EACH SHORING AND RESHORING
 INSTALLATION SHALL BE SUPERVISED, INSPECTED AND
 CERTIFIED TO BE IN COMPLIANCE WITH THE SHORING
 DOCUMENTS BY THE CONTRACTOR.
  
 H) PLEASE CALL THE CITY OF WEST PALM BEACH'S AUTOMATED
 TELEPHONE INSPECTIONS LINE (561) 805-6700 FOR ALL
 BUILDING INSPECTIONS FOR AUDITING OF JOBSITE
 INSPECTIONS WITHOUT THIS THE PERMIT EXPIRES IN 6
 MONTHS, ABANDONMENT OF JOB, NO INSPECTION ACTIVITY.
  
 I) 110.8 THRESHOLD BUILDINGS, OPERATING GUIDELINES FOR
 THRESHOLD INSPECTORS #25. ASSURE THAT THE DESIGNER HAS
 REQUIRED ON THE PLANS OR SPECIFICATIONS ONE MATERIAL,
 APPROVED FOR FIRE STOPPING PENETRATIONS, FOR WALLS AND
 CEILINGS.
  
 J) PLEASE CONTACT ME WITH AN EMAIL ADDRESS AND I WILL
 BE HAPPY TO SEND YOU A COPY OF THE OCTOBER 2018
 GUIDELINES AND POLICIES FOR PROJECTS CONCERNING
 THRESHOLD/SPECIAL INSPECTORS AND RESIDENT INSPECTORS.
  
 4) THIS PROJECT ISLOCATED IN A SPECIAL FLOOD HAZARD
 AREA (AE). SUBMIT A COPY OF THE LOMR FROM FEMA THAT IS
 MENTIONED IN YOUR RESPONSE. RESIDENTIAL BUILDINGS
 LOCATED IN A SPECIAL FLOOD HAZARD AREA ARE NOT ALLOWED
 TO HAVE BASEMENTS BELOW THE BFE. THE PROPOSED STRUCTURE
 IS LOCATED IN FLOOD ZONE AE WITH BASE FLOOD ELEVATIONS
 6 AND 7 NAVD 88. ACCORDING TO CITY ORDINANCE 4729-17
 SEC. 18-34 THE FINISH FLOOR ELEVATION NEEDS TO BE TWO
 FEET (FREEBOARD) ABOVE THE BASE FLOOD ELEVATION.
 BASEMENT FLOOR NEEDS TO BE RAISED.
 NOTE: ELEVATION CERTIFICATES ARE REQUIRED. INCLUDING
 CONSTRUCTION DRAWINGS, DURING CONSTRUCTION AND FINAL.
  
 5) THE CURRENT FLOOD MAPS WERE ADOPTED BY THE CITY OF
 WEST PALM BEACH ON OCTOBER 5, 2017. THE ELEVATIONS ON
 THE ADOPTED MAPS ARE IN NAVD 88. TO AVOID CONFUSION
 PLEASE SPECIFY ALL ELEVATIONS ON THE PLANS USING NAVD
 88. FBC 107.2.1
  
 6) CLARIFY THE FLOOD PANELS AT THE SERVICE WING THAT
 ARE SHOWN ON SHEET A-803A. DRY FLOOD PROOFING IS NOT
 ALLOWED BY FEMA FOR RESIDENTIAL OCCUPANCIES.
  
 7) THE SITE PLANS ARE REQUIRED MARKED FOR REFERENCE
 ONLY. ALL PLANS AND CONSTRUCTION DOCUMENTS THAT ARE
 SUBMITTED FOR PERMIT ARE REQUIRED TO BE SIGNED AND
 SEALED BY THE ENGINEER OR ARCHITECT THAT PREPARED THEM.
 FS 471 & 481
  
 8)FBC 110.8.4.4 REQUIRES ALL PLANS FOR THRESHOLD
 BUILDINGS WHICH ARE REQUIRED TO BE SIGNED AND SEALED BY
 THE ARCHITECT OR ENGINEER OF RECORD CONTAIN A STATEMENT
 THAT, TO THE BEST OF THE
 ARCHITECT'S OR ENGINEER'S KNOWLEDGE, THE PLANS AND
 SPECIFICATIONS COMPLY WITH THE APPLICABLE MINIMUM
 BUILDING CODES AND THE APPLICABLE FIRE-SAFETY STANDARDS
 AS DETERMINED BY THE LOCAL AUTHORITY IN ACCORDANCE WITH
 THIS SECTION AND CHAPTER 633 FLORIDA STATUTES. THE
 STRUCTURAL PLANS STATE THIS IN THE TITLE BLOCK. I DID
 NOT SEE IT ON THE ARCHITECTURAL PLANS.
  
 9) COORDINATE THE DRAWING INDEX ON SHEET G-1 WITH THE
 PLAN SHEETS THAT ARE BEING UPLOADED. STRIKE OUT THE
 SHEETS THAT ARE NOT UPLOADED. FBC 107.2.1 SOME OF THE
 SHEETS ARE MISSING AND OTHERS SUCH AS A-110 AND A-125
 ARE DUPLICATED.
  
 10) SOME OF THE CODE SECTIONS THAT ARE SPECIFIED UNDER
 CODE NOTES ON SHEET G-2 ARE INCORRECT. PLEASE REVIEW
 AND CORRECT THEM. FBC 107.2.1
  
 11) CODE NOTE #26 ON SHEET G-2 SPECIFIES THE FLORIDA
 ASSEMBLY CODE 2012. IS THIS MEANT TO BE THE FLORIDA
 ACCESSIBILTY CODE? IF SO IT WILL BE THE 2017 EDITION.
  
 12) PLEASE CLARIFY WHICH AREAS OF THIS BUILDING WILL BE
 SUBJECT TO THE FLORIDA ACCESSIBILITY CODE AND WHAT
 AREAS ARE REQUIRED TO COMPLY WITH THE FEDERAL FAIR
 HOUSING ACT. FBC 107.2.1
  
 13) PLEASE PROVIDE ADDITIONAL ELEVATIONS FOR THE AREAS
 AROUND THE AMENITY LEVEL POOL AND SHOW THE ACCESIBLE
 ROUTES TO AND AROUND THE POOL. SHOW COMPLIANT RAMPS,
 LIFTS, ETC. 2017 FBC ACCESSIBILITY 402 / FAIR HOUSING
 GUIDELINES REQUIREMENT 2.
  
 14) THE ENTRY LOBBY RAMP DETAILS 1A AND 1B ON SHEET
 A-606 IS MISSING THE INFORMATION REQUIRED TO SHOW
 COMPLIANCE WITH FBC 1012 OR FBC ACCESSIBILITY 405.
  
 15) THE ENTRY LOBBY STAIR PLANS AND SECTIONS ON A-606
 ARE NOT CLEAR, ARE MISSING INFORMATION SUCH AS THE
 NUMBER OF RISERS AND RISER HEIGHT. CLARIFY THE CURVED
 HANDRAIL AND RADIUS.
  
 16) SPECIFY THE LOCATION OF THE PENTHOUSE POOL
 EQUIPMENT AND INDICATE HOW IT WILL BE ACCESSED. FBC
 107.2.1
  
 17) THE POOL EQUIPMENT ROOM 117, ON THE GROUND LEVEL IS
 SPECIFIED WITH A 2 HOUR FIRE RATED WALL, HOWEVER, IT
 DOES NOT HAVE AN ID TAG TIED TO A SPECIFIC WALL TYPE.
 FBC 107.2.1
  
 18) THE DOOR TO POOL EQUIPMENT ROOM 117 IS LOCATED IN A
 2 HOUR FIRE RATED WALL AND IS REQUIRED TO HAVE A 90
 MINUTE FIRE RATING. THIS IS NOT SPECIFIED. FBC 716.5.3
  
 19) ON SHEET LS-1 THE FSA ELEVATOR LOBBY HAS A 1 HOUR
 FIRE RATED WALL WITH A 60 MINUTE FIRE RATED DOUBLE DOOR
 AND THE DOOR FROM THE LOBBY TO THE 2 HOUR FIRE RATED
 EXIT ACCESS PASSAGE WAY DOES NOT HAVE A RATING
 SPECIFIED. EITHER THIS DOOR HAS TO HAVE A 90 MINUTE
 FIRE RATING OR THE DOUBLE DOOR HAS TO BE FIRE RATED FOR
 90 MIN. AND BE IN A TWO HOUR FIRE RATED WALL. FBC FBC
 TABLE 716.5
  
 20) ON SHEET LS-1 THE FIRE RATING OF THE DOOR FROM THE
 PARKING GARAGE TO THE 2 HOUR FIRE RATED PASSAGE WAY IS
 NOT SPECIFIED. FBC 716.5.3
  
 21) ON SHEET LS-1 THE FIRE RATING OF THE DOORS FROM THE
 PARKING GARAGE TO EXIT STAIR 3 ARE NOT SPECIFIED. FBC
 716.5.3
  
 22) ON SHEET LS-5 THE FIRE RATING OF THE DOOR TO THE
 TRASH ROOM IS NOT SPECIFIED.FBC 716.5.3
  
 23) THE DOOR TO THE STAFF ROOM ON LEVEL 3 IS NOT TAGGED
 OR IDENTIFIED ON THE LIFE SAFTEY OR ARCHITECTURAL PLAN
 SHEETS. FBC 107.2.1
  
 24) SHEET 151. A-103 MULTIPURPOSE ROOM 327 HAS DOORS IN
 THE 1 HOUR RATED CORRIDOR WALLS THAT ARE NOT IDENTIFIED
 ON THE LIFE SAFTEY OR ARCHITECTURAL PLAN SHEETS. FBC
 107.2.1
  
 25) THE FIRE RATING OF THE DOORS TO THE STORAGE ROOM
 AND THE TRASH ROOM IN THE 2 HOUR FIRE RATED WALLS ARE
 NOT SPECIFIED. FBC 107.2.1
  
 26) DOORS 2503 AND 2504 ARE LOCATED IN 2 HOUR FIRE
 RATED WALLS AND ARE SPECIFIED ON THE SCHEDULE AS 45
 MINUTE RATHER THAN 90 MINUTE FIRE RATED DOORS. FBC
 716.5.3
  
 27) DOOR 2504A IN THE 2 HOUR FIRE RATED WALL AND IS
 REQUIRED TO BE 90 MINUTE FIRE RATES IS NOT LISTED IN
 THE DOOR SCHEDULE. FBC 107.2.1
  
 28) ON SHEET LS-4 FOR LEVEL 3 THE IDENTIFICATION LINE
 FOR THE 1 HOUR FIRE RATED WALL IS SHOWN CROSSING THE
 OPENING TO THE LOUNGE/BAR AREA. IT APPEARS THAT A ONE
 HOUR FIRE RATED WALL AND 45 MINUTE RATED DOOR IS
 REQUIRED HERE. FBC TABLE 716.5
  
 29) THE CORRIDOR WALL TYPES ARE NOT IDENTIFIED WITH A
 CORRESPONDING TAG ON THE PLANS. FBC 107.2.1
  
 30) THE 2 HOUR FIRE RATED WALL TYPE IS NOT IDENTIFIED
 FOR THE WALLS AT THE FACE OF THE ELEVATORS. FBC 107.2.1
  
 31) THE 2 HOUR FIRE WALL IDENTIFICATION LINES ARE OUT
 OF PLACE AT THE ELEVATOR LOBBY ON SHEET LS-9. FBC
 107.2.1
  
 32) ON SHEET LS-6 THE 1 HOUR WALL IDENTIFICATION LINE
 IS MISTAKENLY INDICATED IN SIDE OF UNIT F. FBC 107.2.1
  
 33) ON SHEET A-901 DETAIL P/11 FOR THE 2 HOUR CMU WALL
 IN ORDER TO ACHIEVE A 2 HOUR FIRE RATING CLASSIFICATION
 D-2 CONCRETE BLOCK IS REQUIRED. FBC TABLE 721.1(2)
  
 34) SHOW COMPLIANCE WITH FBC ACCESSIBILITY CODE 209.2.1
 PASSENGER LOADING ZONES.PASSENGER LOADING ZONES, EXCEPT
 THOSE REQUIRED TO COMPLY WITH 209.2.2 AND 209.2.3,
 SHALL PROVIDE AT LEAST ONE PASSENGER LOADING ZONE
 COMPLYING WITH 503 IN EVERY CONTINUOUS 100 LINEAR FEET
 (30 M) OF LOADING ZONE SPACE, OR FRACTION THEREOF.
  
 35) SHOW COMPLIANCE WITH FBC ACCESSIBILITY CODE 209.4
 VALET PARKING.PARKING FACILITIES THAT PROVIDE VALET
 PARKING SERVICES SHALL PROVIDE AT LEAST ONE PASSENGER
 LOADING ZONE COMPLYING WITH 503.
  
 36) THE GRAB BAR REINFORCING AT THE BACK OF THE TOILET
 IS REQUIRED TO BE A MINIMUM OF 12" (1 FOOT) ON EACH
 SIDE OF THE TOILET CENTER LINE PER FAIR HOUSING
 GUIDELINES REQUIREMENT 6. PLEASE REVISE THE DETAIL ON
 SHEET G-5.
  
 37) IDENTIFY THE TWO REQUIRED FIRE SERVICE ACCESS
 ELEVATORS ON THE PLANS AND SHOW THAT THEY COMPLY WITH
 THE REQUIREMENTS OF FBC 403.6.1 AND 3007.1.
  
 38) SHOW COMPLIANCE WITH FBC 3007.3 WATER PROTECTION.
 AN APPROVED METHOD TO PREVENT WATER FROM INFILTRATING
 INTO THE HOISTWAY ENCLOSURE FROM THE OPERATION OF THE
 AUTOMATIC SPRINKLER SYSTEM OUTSIDE THE ENCLOSED FIRE
 SERVICE ACCESS ELEVATOR LOBBY SHALL BE PROVIDED.
  
 39) IDENTIFY THE REQUIRED ELEVATOR CAR TO ACCOMMODATE
 AMBULANCE STRETCHER AND SHOW THAT IT COMPLIES WITH FBC
 3002.4. ANY BUILDING THAT IS MORE THAN THREE STORIES
 HIGH OR IN WHICH THE VERTICAL DISTANCE BETWEEN THE
 BOTTOM TERMINAL LANDING AND THE TOP TERMINAL LANDING
 EXCEEDS 25 FEET (7620 MM), MUST BE CONSTRUCTED TO
 CONTAIN AT LEAST ONE PASSENGER ELEVATOR THAT IS
 OPERATIONAL FOR BUILDING OCCUPANTS AND FIRE DEPARTMENT
 EMERGENCY ACCESS TO ALL FLOORS. THE ELEVATOR CAR SHALL
 BE OF SUCH A SIZE AND ARRANGEMENT TO ACCOMMODATE AN
 AMBULANCE STRETCHER 24 INCHES BY 76 INCHES (610 MM BY
 1950 MM) WITH NOT LESS THAN 5-INCH (127 MM) RADIUS
 CORNERS, IN THE HORIZONTAL, OPEN POSITION AND SHALL BE
 IDENTIFIED BY THE INTERNATIONAL SYMBOL FOR EMERGENCY
 MEDICAL SERVICES (STAR OF LIFE). THE SYMBOL SHALL BE
 NOT LESS THAN 3 INCHES (76 MM) IN HEIGHT AND SHALL BE
 PLACED INSIDE ON BOTH SIDES OF THE HOISTWAY DOOR FRAME.
  
 40) FBC 107.3.4.1 DEFERRED SUBMITTALS. FOR THE PURPOSES
 OF THIS SECTION, DEFERRED SUBMITTALS ARE DEFINED AS
 THOSE PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT
 THE TIME OF THE APPLICATION AND THAT ARE TO BE
 SUBMITTED TO THE BUILDING OFFICIAL WITHIN A SPECIFIED
 PERIOD. DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE
 PRIOR APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST
 THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS
 FOR REVIEW BY THE BUILDING OFFICIAL.
  
 41) W. P. B. 107.3.4.1 PRODUCT APPROVALS. THOSE
 PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03
 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE
 ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING
 ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC..
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 42) SHOW COMPLIANCE WITH FBC 1207.2 FOR AIR-BORNE SOUND
 TRANSMISSION AND FBC 1207.3 FOR STRUCTURE BORNE SOUND
 INSULATION.
  
 NOTE: ADDITIONAL COMMENTS MAY RESULT FROM THE RESPONSES
 TO THESE COMMENTS. WHEN RESUBMITTING, IT IS HELPFUL TO
 PROVIDE A RESPONSE LETTER ADDRESSING EACH ITEM ALONG
 WITH THE CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE
 INSERT CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
  
  
  
  
  
  