| 2018-11-15 17:45:15 | REVIEW COMMENTS |
| | |
| | 1ST REVIEW: FBC SIXTH EDITION (2017) |
| | ROBERT MCDOUGAL, CBO |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561) 805-6714 |
| | [email protected] |
| | WPB PERMIT: 18081528 |
| | ADD: 1515 S. FLAGLER DRIVE |
| | CONT: |
| | TEL: |
| | EMAIL: |
| | |
| | 1) ART IN PUBLIC PLACES |
| | THE CITY OF WEST PALM BEACH ART IN PUBLIC PLACES |
| | ORDINANCE REQUIREMENT THAT APPLIES TO ANY REMODEL OR |
| | NEW CONSTRUCTION PROJECT FOR WHICH THE PERMIT |
| | APPLICATION WAS SUBMITTED AFTER 6/29/14, AND THE TOTAL |
| | PROJECT CONSTRUCTION COSTS ARE EQUAL TO OR GREATER THAN |
| | $750,000 WILL NEED TO COMPLY WITH THIS ORDINANCE. |
| | PER CITY OF WEST PALM BEACH ORDINANCE NO. 4504-14, AND |
| | CITY OF WEST PALM BEACH CODE OF ORDINANCES, ARTICLE V, |
| | ART IN PUBLIC PLACES, SECTION 78-123(A) AND SECTION |
| | 78-126(A), THE ART ASSESSMENT IS 1% OF THE TOTAL |
| | PROJECT CONSTRUCTION COST. |
| | PER CITY OF WEST PALM BEACH CODE OF ORDINANCES, ARTICLE |
| | V, ART IN PUBLIC PLACES, SECTION 78-122, RENOVATION AND |
| | NEW CONSTRUCTION PROJECTS ARE ASSESSED CUMULATIVELY, SO |
| | THE ART ASSESSMENT WILL BE APPLICABLE TO ALL FUTURE |
| | PROJECTS. |
| | SEC. 78-129. - PUBLIC ART ASSESSMENT FOR PRIVATE |
| | DEVELOPMENT. |
| | (A) APPLICABILITY. THE PROVISIONS OF THIS ARTICLE AND |
| | THE PUBLIC ART ASSESSMENT SECTION SHALL APPLY TO ALL |
| | PRIVATE DEVELOPMENT PROJECTS, INCLUDING NEW |
| | CONSTRUCTION, OR THE RENOVATION OR IMPROVEMENT OF AN |
| | EXISTING BUILDING, WHERE TOTAL CONSTRUCTION COSTS ARE |
| | EQUAL TO OR GREATER THAN $750,000.00. ALL BUILDINGS |
| | WITHIN NEW PLANNED DEVELOPMENTS SHALL BE ASSESSED |
| | CUMULATIVELY TOWARDS THIS ART IN PUBLIC PLACES |
| | REQUIREMENT, EVEN IF THE BUILDINGS ARE PERMITTED |
| | SEPARATELY OR DEVELOPED IN PHASES. THE PROVISIONS OF |
| | THIS SECTION APPLY TO NEW DEVELOPMENT OR NEW |
| | CONSTRUCTION WITHIN EXISTING PLANNED DEVELOPMENTS. |
| | FOR CONTACT INFORMATION PLEASE CONTACT: |
| | MS. SYBILLE WELTER ART IN PUBLIC PLACES COORDINATOR |
| | 822-1515 E-MAIL: [email protected] |
| | |
| | 2) 109.3 BUILDING PERMIT VALUATION. |
| | IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE |
| | CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE, |
| | ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS |
| | APPEARS TO BE UNDER ESTIMATED ON THE APPLICATION, THE |
| | PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES, |
| | VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL |
| | REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND |
| | SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE |
| | STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR |
| | FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR |
| | BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING |
| | COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE. |
| | VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED |
| | DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES |
| | (MARSHALL-SWIFT, MEANS, ETC.) WITH REGIONAL ADJUSTMENTS |
| | FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE |
| | CONGRESS. |
| | THIS MAIN BUILDING PERMIT WILL INCLUDE THE FEES FOR THE |
| | MECHANICAL, ELECTRICAL, PLUMBING & ROOFING PERMITS. |
| | WHEN THE GENERAL CONTRACTOR COMES IN FOR A BUILDING |
| | PERMIT WITH THE SIGNED PERMIT APPLICATION FORM BY THE |
| | QUALIFIER AND OWNER AND BRINGS IN THE LISTED |
| | SUB-PERMITS M-E-P & ROOFING PERMITS SIGNED BY THE |
| | QUALIFIER OF EACH COMPANY, THEIR INSURANCES AND |
| | LICENSURE UP TO DATE, THE M-E-P AND ROOFING PERMITS ARE |
| | FREE OF CHARGE. IF THE M-E-P & ROOFING PERMITS COME IN |
| | LATER THERE WILL BE AN $80.00 ADMINISTRATIVE FEE FOR |
| | EACH PERMIT. |
| | ALL OTHER PERMITS FIRE SPRINKLER, FIRE ALARM, RACK |
| | STORAGE, EXHAUST HOODS, ANSUL SYSTEMS OR ALTERNATIVE |
| | AUTOMATIC FIRE-EXTINGUISHING SYSTEMS, WALK IN COOLERS & |
| | FREEZERS, ALL LOW VOLTAGE PERMITS, GENERATORS & FUEL |
| | TANKS, GAS PERMIT, POOL, JACUZZI AND ASSOCIATED |
| | SUB-PERMITS, AWNING, SCREEN ENCLOSURES, CANOPY, FENCE, |
| | LANDSCAPE, IRRIGATION, AUGER CAST PILE AND OR |
| | FOUNDATION OR STRUCTURE ONLY PERMIT WILL BE SEPARATE |
| | REVIEWS AND ASSOCIATED FEES WITH EACH PERMIT. |
| | PLEASE PROVIDE AN ITEMIZED LIST AND SUBTRACT THESE LINE |
| | ITEMS AND THEIR VALUE FROM THE OVERALL BUILDING VALUE |
| | STATED ON THE PERMIT APPLICATION FOR THIS PROJECT. THE |
| | REMAINING BALANCE WILL BE AFFECTIVELY THE VALUE OF THE |
| | BUILDING YOU WILL BE PAYING FOR THIS PERMIT. THE |
| | BUILDING DEPARTMENT DOES NOT WANT TO COLLECT TWICE FOR |
| | THE VALUE OF THESE SUB-PERMITS NOT COVERED UNDER THE |
| | PRIME OR MASTER PERMIT. |
| | |
| | 3) THIS PROJECT IS A THRESHOLD BUILDING / FL S. S. |
| | 553.71(7) "THRESHOLD BUILDING" MEANING ANY BUILDING |
| | WHICH IS GREATER THAN (3) STORIES OR 50 FT. IN HEIGHT, |
| | OR WHICH HAS AN ASSEMBLY OCCUPANCY CLASSIFICATION AS |
| | DENIED IN THE FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 |
| | SQ. FT. IN AREA AND AN OCCUPANT CONTENT OF GREATER THAN |
| | 500 PERSONS. |
| | |
| | A) FBC (CITY AMENDMENTS)110.8.1 THRESHOLD INSPECTION |
| | PLAN. THE ENFORCING AGENCY SHALL REQUIRE A SPECIAL |
| | INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON A |
| | THRESHOLD BUILDING PURSUANT TO A STRUCTURAL INSPECTION |
| | PLAN PREPARED BY THE ENGINEER OF RECORD. THE STRUCTURAL |
| | INSPECTION PLAN MUST BE SUBMITTED TO THE ENFORCING |
| | AGENCY PRIOR TO THE ISSUANCE OF A BUILDING PERMIT FOR |
| | THE CONSTRUCTION OF A THRESHOLD BUILDING. THE PURPOSE |
| | OF THE STRUCTURAL INSPECTION PLAN IS TO PROVIDE |
| | SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO THAT |
| | THE BUILDING CAN BE ADEQUATELY INSPECTED FOR COMPLIANCE |
| | WITH THE PERMITTED DOCUMENTS. THE SPECIAL INSPECTOR MAY |
| | NOT SERVE AS A SURROGATE IN CARRYING OUT THE |
| | RESPONSIBILITIES OF THE BUILDING OFFICIAL, THE |
| | ARCHITECT OR THE ENGINEER OF RECORD. THE CONTRACTOR'S |
| | CONTRACTUAL OR STATUTORY OBLIGATIONS ARE NOT RELIEVED |
| | BY ANY ACTION OF THE SPECIAL INSPECTOR. |
| | |
| | B) THRESHOLD INSPECTOR: WPB AMENDMENT 110.8.1 W.P.B. |
| | CONSTRUCTION SERVICES DEPARTMENT REQUEST FOR THRESHOLD |
| | BUILDINGS A SPECIAL INSPECTOR AS REQUIRED BY 553.79(5) |
| | FLORIDA STATUTES TO THE MINIMUM INSPECTIONS REQUIRED BY |
| | THIS CODE. THE THRESHOLD INSPECTION FORMS ARE REQUIRED |
| | TO BE FILED OUT BY ALL PARTIES WITH INTEREST, NOTARIZED |
| | AND RETURNED TO THIS OFFICE, AND REVIEWED AND APPROVED |
| | BEFORE PERMIT ISSUANCE WILL TAKE PLACE. |
| | |
| | C) THRESHOLD BLDG. REQUIRED STATEMENT: W.P.B. AMENDMENT |
| | 110.8.4.4 ALL PLANS FOR THE BUILDING WHICH ARE REQUIRED |
| | TO BE SIGNED AND SEALED BY THE ARCHITECT OR ENGINEER OF |
| | RECORD CONTAIN A STATEMENT THAT, TO THE BEST OF THE |
| | ARCHITECT'S OR ENGINEER'S KNOWLEDGE, THE PLANS AND |
| | SPECIFICATIONS COMPLY WITH THE APPLICABLE MINIMUM |
| | BUILDING CODES AND THE APPLICABLE FIRE-SAFETY STANDARDS |
| | AS DETERMINED BY THE LOCAL AUTHORITY IN ACCORDANCE WITH |
| | THIS SECTION AND CHAPTER 633 FLORIDA STATUTES. |
| | |
| | D) FOR THE SPECIAL INSPECTOR PLEASE PROVIDE A RESUME OF |
| | INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE RESUME |
| | MUST BE ACCOMPANIED BY ALL CERTIFICATES AS SPECIFIED |
| | HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE WILL |
| | REVIEW THE RESUME. AFTER THE RESUME IS REVIEWED, AN |
| | INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES |
| | WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST |
| | MEETING THE ABOVE CRITERIA. |
| | |
| | E) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR HISTORY |
| | FOR THIS TYPE OF CONSTRUCTION. |
| | |
| | F) NOTE: FOR DIGITAL PLANS, AFTER PERMIT ISSUANCE, |
| | PLEASE E-MAIL THE PERMIT LIBRARIAN OF THE PERMIT BEING |
| | ISSUED, THE PERMIT LIBRARIAN WILL THEN E-MAIL YOU THE |
| | APPROVED AND BATCH STAMPED PLANS SO YOU MAY PRINT YOUR |
| | PLANS, TWO SETS OF PLANS WILL NEED TO BE PRINTED IN |
| | COLOR, (1) FOR THE THRESHOLD INSPECTOR, THE OTHER FOR |
| | THE MEP INSPECTORS OTHER PLANS YOU WISH TO PRINT MAYBE |
| | IN BLACK & WHITE. |
| | |
| | G) 110.8.4.3 ALL SHORING AND RESHORING PROCEDURES, |
| | PLANS AND DETAILS SHALL BE SUBMITTED TO THE ENFORCEMENT |
| | AGENCY FOR RECORDKEEPING. EACH SHORING AND RESHORING |
| | INSTALLATION SHALL BE SUPERVISED, INSPECTED AND |
| | CERTIFIED TO BE IN COMPLIANCE WITH THE SHORING |
| | DOCUMENTS BY THE CONTRACTOR. |
| | |
| | H) PLEASE CALL THE CITY OF WEST PALM BEACH'S AUTOMATED |
| | TELEPHONE INSPECTIONS LINE (561) 805-6700 FOR ALL |
| | BUILDING INSPECTIONS FOR AUDITING OF JOBSITE |
| | INSPECTIONS WITHOUT THIS THE PERMIT EXPIRES IN 6 |
| | MONTHS, ABANDONMENT OF JOB, NO INSPECTION ACTIVITY. |
| | |
| | I) 110.8 THRESHOLD BUILDINGS, OPERATING GUIDELINES FOR |
| | THRESHOLD INSPECTORS #25. ASSURE THAT THE DESIGNER HAS |
| | REQUIRED ON THE PLANS OR SPECIFICATIONS ONE MATERIAL, |
| | APPROVED FOR FIRE STOPPING PENETRATIONS, FOR WALLS AND |
| | CEILINGS. |
| | |
| | J) PLEASE CONTACT ME WITH AN EMAIL ADDRESS AND I WILL |
| | BE HAPPY TO SEND YOU A COPY OF THE OCTOBER 2018 |
| | GUIDELINES AND POLICIES FOR PROJECTS CONCERNING |
| | THRESHOLD/SPECIAL INSPECTORS AND RESIDENT INSPECTORS. |
| | |
| | 4) THIS PROJECT ISLOCATED IN A SPECIAL FLOOD HAZARD |
| | AREA (AE). SUBMIT A COPY OF THE LOMR FROM FEMA THAT IS |
| | MENTIONED IN YOUR RESPONSE. RESIDENTIAL BUILDINGS |
| | LOCATED IN A SPECIAL FLOOD HAZARD AREA ARE NOT ALLOWED |
| | TO HAVE BASEMENTS BELOW THE BFE. THE PROPOSED STRUCTURE |
| | IS LOCATED IN FLOOD ZONE AE WITH BASE FLOOD ELEVATIONS |
| | 6 AND 7 NAVD 88. ACCORDING TO CITY ORDINANCE 4729-17 |
| | SEC. 18-34 THE FINISH FLOOR ELEVATION NEEDS TO BE TWO |
| | FEET (FREEBOARD) ABOVE THE BASE FLOOD ELEVATION. |
| | BASEMENT FLOOR NEEDS TO BE RAISED. |
| | NOTE: ELEVATION CERTIFICATES ARE REQUIRED. INCLUDING |
| | CONSTRUCTION DRAWINGS, DURING CONSTRUCTION AND FINAL. |
| | |
| | 5) THE CURRENT FLOOD MAPS WERE ADOPTED BY THE CITY OF |
| | WEST PALM BEACH ON OCTOBER 5, 2017. THE ELEVATIONS ON |
| | THE ADOPTED MAPS ARE IN NAVD 88. TO AVOID CONFUSION |
| | PLEASE SPECIFY ALL ELEVATIONS ON THE PLANS USING NAVD |
| | 88. FBC 107.2.1 |
| | |
| | 6) CLARIFY THE FLOOD PANELS AT THE SERVICE WING THAT |
| | ARE SHOWN ON SHEET A-803A. DRY FLOOD PROOFING IS NOT |
| | ALLOWED BY FEMA FOR RESIDENTIAL OCCUPANCIES. |
| | |
| | 7) THE SITE PLANS ARE REQUIRED MARKED FOR REFERENCE |
| | ONLY. ALL PLANS AND CONSTRUCTION DOCUMENTS THAT ARE |
| | SUBMITTED FOR PERMIT ARE REQUIRED TO BE SIGNED AND |
| | SEALED BY THE ENGINEER OR ARCHITECT THAT PREPARED THEM. |
| | FS 471 & 481 |
| | |
| | 8)FBC 110.8.4.4 REQUIRES ALL PLANS FOR THRESHOLD |
| | BUILDINGS WHICH ARE REQUIRED TO BE SIGNED AND SEALED BY |
| | THE ARCHITECT OR ENGINEER OF RECORD CONTAIN A STATEMENT |
| | THAT, TO THE BEST OF THE |
| | ARCHITECT'S OR ENGINEER'S KNOWLEDGE, THE PLANS AND |
| | SPECIFICATIONS COMPLY WITH THE APPLICABLE MINIMUM |
| | BUILDING CODES AND THE APPLICABLE FIRE-SAFETY STANDARDS |
| | AS DETERMINED BY THE LOCAL AUTHORITY IN ACCORDANCE WITH |
| | THIS SECTION AND CHAPTER 633 FLORIDA STATUTES. THE |
| | STRUCTURAL PLANS STATE THIS IN THE TITLE BLOCK. I DID |
| | NOT SEE IT ON THE ARCHITECTURAL PLANS. |
| | |
| | 9) COORDINATE THE DRAWING INDEX ON SHEET G-1 WITH THE |
| | PLAN SHEETS THAT ARE BEING UPLOADED. STRIKE OUT THE |
| | SHEETS THAT ARE NOT UPLOADED. FBC 107.2.1 SOME OF THE |
| | SHEETS ARE MISSING AND OTHERS SUCH AS A-110 AND A-125 |
| | ARE DUPLICATED. |
| | |
| | 10) SOME OF THE CODE SECTIONS THAT ARE SPECIFIED UNDER |
| | CODE NOTES ON SHEET G-2 ARE INCORRECT. PLEASE REVIEW |
| | AND CORRECT THEM. FBC 107.2.1 |
| | |
| | 11) CODE NOTE #26 ON SHEET G-2 SPECIFIES THE FLORIDA |
| | ASSEMBLY CODE 2012. IS THIS MEANT TO BE THE FLORIDA |
| | ACCESSIBILTY CODE? IF SO IT WILL BE THE 2017 EDITION. |
| | |
| | 12) PLEASE CLARIFY WHICH AREAS OF THIS BUILDING WILL BE |
| | SUBJECT TO THE FLORIDA ACCESSIBILITY CODE AND WHAT |
| | AREAS ARE REQUIRED TO COMPLY WITH THE FEDERAL FAIR |
| | HOUSING ACT. FBC 107.2.1 |
| | |
| | 13) PLEASE PROVIDE ADDITIONAL ELEVATIONS FOR THE AREAS |
| | AROUND THE AMENITY LEVEL POOL AND SHOW THE ACCESIBLE |
| | ROUTES TO AND AROUND THE POOL. SHOW COMPLIANT RAMPS, |
| | LIFTS, ETC. 2017 FBC ACCESSIBILITY 402 / FAIR HOUSING |
| | GUIDELINES REQUIREMENT 2. |
| | |
| | 14) THE ENTRY LOBBY RAMP DETAILS 1A AND 1B ON SHEET |
| | A-606 IS MISSING THE INFORMATION REQUIRED TO SHOW |
| | COMPLIANCE WITH FBC 1012 OR FBC ACCESSIBILITY 405. |
| | |
| | 15) THE ENTRY LOBBY STAIR PLANS AND SECTIONS ON A-606 |
| | ARE NOT CLEAR, ARE MISSING INFORMATION SUCH AS THE |
| | NUMBER OF RISERS AND RISER HEIGHT. CLARIFY THE CURVED |
| | HANDRAIL AND RADIUS. |
| | |
| | 16) SPECIFY THE LOCATION OF THE PENTHOUSE POOL |
| | EQUIPMENT AND INDICATE HOW IT WILL BE ACCESSED. FBC |
| | 107.2.1 |
| | |
| | 17) THE POOL EQUIPMENT ROOM 117, ON THE GROUND LEVEL IS |
| | SPECIFIED WITH A 2 HOUR FIRE RATED WALL, HOWEVER, IT |
| | DOES NOT HAVE AN ID TAG TIED TO A SPECIFIC WALL TYPE. |
| | FBC 107.2.1 |
| | |
| | 18) THE DOOR TO POOL EQUIPMENT ROOM 117 IS LOCATED IN A |
| | 2 HOUR FIRE RATED WALL AND IS REQUIRED TO HAVE A 90 |
| | MINUTE FIRE RATING. THIS IS NOT SPECIFIED. FBC 716.5.3 |
| | |
| | 19) ON SHEET LS-1 THE FSA ELEVATOR LOBBY HAS A 1 HOUR |
| | FIRE RATED WALL WITH A 60 MINUTE FIRE RATED DOUBLE DOOR |
| | AND THE DOOR FROM THE LOBBY TO THE 2 HOUR FIRE RATED |
| | EXIT ACCESS PASSAGE WAY DOES NOT HAVE A RATING |
| | SPECIFIED. EITHER THIS DOOR HAS TO HAVE A 90 MINUTE |
| | FIRE RATING OR THE DOUBLE DOOR HAS TO BE FIRE RATED FOR |
| | 90 MIN. AND BE IN A TWO HOUR FIRE RATED WALL. FBC FBC |
| | TABLE 716.5 |
| | |
| | 20) ON SHEET LS-1 THE FIRE RATING OF THE DOOR FROM THE |
| | PARKING GARAGE TO THE 2 HOUR FIRE RATED PASSAGE WAY IS |
| | NOT SPECIFIED. FBC 716.5.3 |
| | |
| | 21) ON SHEET LS-1 THE FIRE RATING OF THE DOORS FROM THE |
| | PARKING GARAGE TO EXIT STAIR 3 ARE NOT SPECIFIED. FBC |
| | 716.5.3 |
| | |
| | 22) ON SHEET LS-5 THE FIRE RATING OF THE DOOR TO THE |
| | TRASH ROOM IS NOT SPECIFIED.FBC 716.5.3 |
| | |
| | 23) THE DOOR TO THE STAFF ROOM ON LEVEL 3 IS NOT TAGGED |
| | OR IDENTIFIED ON THE LIFE SAFTEY OR ARCHITECTURAL PLAN |
| | SHEETS. FBC 107.2.1 |
| | |
| | 24) SHEET 151. A-103 MULTIPURPOSE ROOM 327 HAS DOORS IN |
| | THE 1 HOUR RATED CORRIDOR WALLS THAT ARE NOT IDENTIFIED |
| | ON THE LIFE SAFTEY OR ARCHITECTURAL PLAN SHEETS. FBC |
| | 107.2.1 |
| | |
| | 25) THE FIRE RATING OF THE DOORS TO THE STORAGE ROOM |
| | AND THE TRASH ROOM IN THE 2 HOUR FIRE RATED WALLS ARE |
| | NOT SPECIFIED. FBC 107.2.1 |
| | |
| | 26) DOORS 2503 AND 2504 ARE LOCATED IN 2 HOUR FIRE |
| | RATED WALLS AND ARE SPECIFIED ON THE SCHEDULE AS 45 |
| | MINUTE RATHER THAN 90 MINUTE FIRE RATED DOORS. FBC |
| | 716.5.3 |
| | |
| | 27) DOOR 2504A IN THE 2 HOUR FIRE RATED WALL AND IS |
| | REQUIRED TO BE 90 MINUTE FIRE RATES IS NOT LISTED IN |
| | THE DOOR SCHEDULE. FBC 107.2.1 |
| | |
| | 28) ON SHEET LS-4 FOR LEVEL 3 THE IDENTIFICATION LINE |
| | FOR THE 1 HOUR FIRE RATED WALL IS SHOWN CROSSING THE |
| | OPENING TO THE LOUNGE/BAR AREA. IT APPEARS THAT A ONE |
| | HOUR FIRE RATED WALL AND 45 MINUTE RATED DOOR IS |
| | REQUIRED HERE. FBC TABLE 716.5 |
| | |
| | 29) THE CORRIDOR WALL TYPES ARE NOT IDENTIFIED WITH A |
| | CORRESPONDING TAG ON THE PLANS. FBC 107.2.1 |
| | |
| | 30) THE 2 HOUR FIRE RATED WALL TYPE IS NOT IDENTIFIED |
| | FOR THE WALLS AT THE FACE OF THE ELEVATORS. FBC 107.2.1 |
| | |
| | 31) THE 2 HOUR FIRE WALL IDENTIFICATION LINES ARE OUT |
| | OF PLACE AT THE ELEVATOR LOBBY ON SHEET LS-9. FBC |
| | 107.2.1 |
| | |
| | 32) ON SHEET LS-6 THE 1 HOUR WALL IDENTIFICATION LINE |
| | IS MISTAKENLY INDICATED IN SIDE OF UNIT F. FBC 107.2.1 |
| | |
| | 33) ON SHEET A-901 DETAIL P/11 FOR THE 2 HOUR CMU WALL |
| | IN ORDER TO ACHIEVE A 2 HOUR FIRE RATING CLASSIFICATION |
| | D-2 CONCRETE BLOCK IS REQUIRED. FBC TABLE 721.1(2) |
| | |
| | 34) SHOW COMPLIANCE WITH FBC ACCESSIBILITY CODE 209.2.1 |
| | PASSENGER LOADING ZONES.PASSENGER LOADING ZONES, EXCEPT |
| | THOSE REQUIRED TO COMPLY WITH 209.2.2 AND 209.2.3, |
| | SHALL PROVIDE AT LEAST ONE PASSENGER LOADING ZONE |
| | COMPLYING WITH 503 IN EVERY CONTINUOUS 100 LINEAR FEET |
| | (30 M) OF LOADING ZONE SPACE, OR FRACTION THEREOF. |
| | |
| | 35) SHOW COMPLIANCE WITH FBC ACCESSIBILITY CODE 209.4 |
| | VALET PARKING.PARKING FACILITIES THAT PROVIDE VALET |
| | PARKING SERVICES SHALL PROVIDE AT LEAST ONE PASSENGER |
| | LOADING ZONE COMPLYING WITH 503. |
| | |
| | 36) THE GRAB BAR REINFORCING AT THE BACK OF THE TOILET |
| | IS REQUIRED TO BE A MINIMUM OF 12" (1 FOOT) ON EACH |
| | SIDE OF THE TOILET CENTER LINE PER FAIR HOUSING |
| | GUIDELINES REQUIREMENT 6. PLEASE REVISE THE DETAIL ON |
| | SHEET G-5. |
| | |
| | 37) IDENTIFY THE TWO REQUIRED FIRE SERVICE ACCESS |
| | ELEVATORS ON THE PLANS AND SHOW THAT THEY COMPLY WITH |
| | THE REQUIREMENTS OF FBC 403.6.1 AND 3007.1. |
| | |
| | 38) SHOW COMPLIANCE WITH FBC 3007.3 WATER PROTECTION. |
| | AN APPROVED METHOD TO PREVENT WATER FROM INFILTRATING |
| | INTO THE HOISTWAY ENCLOSURE FROM THE OPERATION OF THE |
| | AUTOMATIC SPRINKLER SYSTEM OUTSIDE THE ENCLOSED FIRE |
| | SERVICE ACCESS ELEVATOR LOBBY SHALL BE PROVIDED. |
| | |
| | 39) IDENTIFY THE REQUIRED ELEVATOR CAR TO ACCOMMODATE |
| | AMBULANCE STRETCHER AND SHOW THAT IT COMPLIES WITH FBC |
| | 3002.4. ANY BUILDING THAT IS MORE THAN THREE STORIES |
| | HIGH OR IN WHICH THE VERTICAL DISTANCE BETWEEN THE |
| | BOTTOM TERMINAL LANDING AND THE TOP TERMINAL LANDING |
| | EXCEEDS 25 FEET (7620 MM), MUST BE CONSTRUCTED TO |
| | CONTAIN AT LEAST ONE PASSENGER ELEVATOR THAT IS |
| | OPERATIONAL FOR BUILDING OCCUPANTS AND FIRE DEPARTMENT |
| | EMERGENCY ACCESS TO ALL FLOORS. THE ELEVATOR CAR SHALL |
| | BE OF SUCH A SIZE AND ARRANGEMENT TO ACCOMMODATE AN |
| | AMBULANCE STRETCHER 24 INCHES BY 76 INCHES (610 MM BY |
| | 1950 MM) WITH NOT LESS THAN 5-INCH (127 MM) RADIUS |
| | CORNERS, IN THE HORIZONTAL, OPEN POSITION AND SHALL BE |
| | IDENTIFIED BY THE INTERNATIONAL SYMBOL FOR EMERGENCY |
| | MEDICAL SERVICES (STAR OF LIFE). THE SYMBOL SHALL BE |
| | NOT LESS THAN 3 INCHES (76 MM) IN HEIGHT AND SHALL BE |
| | PLACED INSIDE ON BOTH SIDES OF THE HOISTWAY DOOR FRAME. |
| | |
| | 40) FBC 107.3.4.1 DEFERRED SUBMITTALS. FOR THE PURPOSES |
| | OF THIS SECTION, DEFERRED SUBMITTALS ARE DEFINED AS |
| | THOSE PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT |
| | THE TIME OF THE APPLICATION AND THAT ARE TO BE |
| | SUBMITTED TO THE BUILDING OFFICIAL WITHIN A SPECIFIED |
| | PERIOD. DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE |
| | PRIOR APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED |
| | DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST |
| | THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS |
| | FOR REVIEW BY THE BUILDING OFFICIAL. |
| | |
| | 41) W. P. B. 107.3.4.1 PRODUCT APPROVALS. THOSE |
| | PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03 |
| | SHALL BE REVIEWED AND APPROVED IN WRITING BY THE |
| | DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| | JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE |
| | ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING |
| | ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC.. |
| | DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE |
| | SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN |
| | RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD |
| | THEM TO THE BUILDING OFFICIAL WITH A NOTATION |
| | INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE |
| | BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO |
| | THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL |
| | ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED |
| | SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING |
| | OFFICIAL. |
| | |
| | 42) SHOW COMPLIANCE WITH FBC 1207.2 FOR AIR-BORNE SOUND |
| | TRANSMISSION AND FBC 1207.3 FOR STRUCTURE BORNE SOUND |
| | INSULATION. |
| | |
| | NOTE: ADDITIONAL COMMENTS MAY RESULT FROM THE RESPONSES |
| | TO THESE COMMENTS. WHEN RESUBMITTING, IT IS HELPFUL TO |
| | PROVIDE A RESPONSE LETTER ADDRESSING EACH ITEM ALONG |
| | WITH THE CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE |
| | INSERT CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS. |
| | |
| | |
| | |
| | |
| | |
| | |
| | |