| Plan Review Notes For Permit 18081512 |
| Permit Number |
18081512 |
|
| Review Stop |
B |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2019-02-16 12:33:11 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | | | | 1.PROVISO: GENERATOR ATTACHMENT IS DELEGATED | | | ENGINEERING PER SEOR. THIS IS REQUIRED TO BE SUBMITTED | | | AS A REVISION, AND REVIEWED, PRIOR TO FIRST INSPECTION. | | | DELEGATED ENGINEERING TO BE REVIEWED BY SEOR PRIOR TO | | | SUBMITTAL TO THE CITY. | | | | | | 2. FBC 1609.1, SHEET S002 1060 2.3 DECLARES EXPOSURE C; | | | PLEASE PROVIDE JUSTIFICATION FOR C RATHER THAN D IN THE | | | RESPONSE LETTER. | | | | | | 3RD REVIEW; THIS WAS REVIEWED PRELIMINARILY VIA EMAIL. | | | A REQUEST WAS MADE FOR ENGINEER TO EVALUATE THE | | | CONDITION TO THE SOUTHEAST. ONLY THE NORTHEAST WAS | | | ADDRESSED. | | | | | | THIS MAY BE SENT VIA EMAIL IN A DIGITALLY SIGNED | | | LETTER. | | | | | | |
|