| 2018-12-28 12:30:37 | 2ND REVIEW: |
| | 2017 FLORIDA BUILDING CODE 6TH EDITION |
| | 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH |
| | EDITION |
| | 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH |
| | EDITION |
| | 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH |
| | EDITION |
| | |
| | PREVIOUS GAS COMMENTS: NOT COMPLIED 2ND REQUEST. |
| | |
| | 1. PROVIDE MANUFACTURE SPECIFICATION AND INSTALLATION |
| | GUIDES FOR GENERATOR, REGULATORS, SUCTION AND RETURN |
| | PUMPS, THE DUAL WALL PIPING WITH LEAK DETECTION, |
| | GEOFLEX PIPING, AND ANY NEW EQUIPMENT ON THE FUEL TANK |
| | SUCH AS THE ANTI SIPHON VALVE AND FOOT VALVE. PER WPB |
| | AMEND TO FBC 107.2.1 |
| | IN THE RESPONSE LETTER IT STATED THAT MANUFACTURE SPEC |
| | WILL BE SUPPLIED IN SUBMITTAL PHASE THIS REVIEW IS |
| | CONSIDERED THE SUBMITTAL PHASE AND IT WILL BE REQUIRED |
| | TO SUBMIT THE DOCUMENTATION TO VERIFY CODE COMPLIANCE. |
| | |
| | 2. COMPLIED |
| | |
| | 3. ON THE NATURAL GAS RISER PLEASE SHOW THE FOLLOWING: |
| | A) COMPLIED |
| | B) COMPLIED |
| | C) COMPLIED |
| | D) SHOW DISTANCE AND SIZE OF PIPE FROM REGULATOR TO THE |
| | GENERATOR. |
| | E) COMPLIED |
| | PER WPB AMEND TO FBC 107.2.1 |
| | |
| | 4. COMPLIED |
| | |
| | 5. COMPLIED |
| | |
| | NEW COMMENT: |
| | |
| | 1. THE FIRST SECTION OF PIPE AFTER THE METER SHALL BE |
| | 3" TO SUPPLY THE EXISTING LOAD AND THE NEW LOAD |
| | COMBINED. PER FBC FG TABLE 402.4(5) |
| | |
| | 2. PLEASE PLACE NOTE ON PLAN. CITY OF WEST PALM BEACH |
| | GAS PIPING AFFIDAVIT OR MANOMETER TEST DOCUMENT |
| | REQUIRED AT JOBSITE FOR FINAL INSPECTION. |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | |
| | GEORGE JOHNSON |
| | PLUMBING PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | 561-805-6711 |
| | [email protected] |
| | |