| Plan Review Notes For Permit 18081512 |
| Permit Number |
18081512 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2018-12-27 18:36:05 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | | | | 1. PREVIOUS COMMENT LIST REQUESTED GENERATOR ATTACHMENT | | | DETAILS. DETAIL 5 ON SHEET S201 REFERS TO SPACING PER | | | MANUFACTURER SPECS. MANUFACTURER SPECS WERE NOT | | | PROVIDED. | | | | | | PLEASE NOTE THAT IF THE MANUFACTURER SPECS ARE USED TO | | | SHOW RESISTANCE TO WIND LOADS, THEY ARE TO BE PREPARED | | | BY A FLORIDA PE AND BE SIGNED AND SEALED. THIS WOULD BE | | | CONSIDERED DELEGATED ENGINEERING AND AS SUCH SHOULD BE | | | REVIEWED BY SEOR PRIOR TO SUBMITTAL. THE DELEGATED | | | ENGINEERING SHOULD INCLUDE THE SEOR'S WIND DESIGN | | | CRITERIA SO COMPLIANCE IS CLEAR. | | | | | | 2. FBC 1609.1, SHEET S002 1060 2.3 DECLARES EXPOSURE C; | | | PLEASE PROVIDE JUSTIFICATION FOR C RATHER THAN D IN THE | | | RESPONSE LETTER. | | | | | | 3. SHEET S002 REFERS TO AN OUTDATED CODE, 1060 ITEM 1 | | | (FBC 2014). REVISE AND CHECK ALL. | | | | | | |
|