Plan Review Notes
Plan Review Notes For Permit 18081512
Permit Number 18081512
Review Stop G
Sequence Number 1
Notes
Date Text
2018-10-03 17:15:391ST REVIEW:
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
 1. PROVIDE MANUFACTURE SPECIFICATION AND INSTALLATION
 GUIDES FOR GENERATOR, REGULATORS, SUCTION AND RETURN
 PUMPS, THE DUAL WALL PIPING WITH LEAK DETECTION,
 GEOFLEX PIPING, AND ANY NEW EQUIPMENT ON THE FUEL TANK
 SUCH AS THE ANTI SIPHON VALVE AND FOOT VALVE. PER WPB
 AMEND TO FBC 107.2.1
  
 2. PLEASE SHOW THE EXISTING BTU LOAD ON THE EXISTING
 PIPE. PER WPB AMEND TO FBC 107.2.1
  
 3. ON THE NATURAL GAS RISER PLEASE SHOW THE FOLLOWING:
 A) THE FURTHEST DISTANCE FROM THE METER TO THE LAST
 GENERATOR.
 B) SHOW THE BRANCHES FOR ALL 3 GENERATORS.
 C) INDICATE SYSTEM PRESSURE.
 D) SHOW DISTANCE AND SIZE OF PIPE FROM REGULATOR TO THE
 GENERATOR.
 E) INDICATE BTU LOAD ON EACH GENERATOR.
 PER WPB AMEND TO FBC 107.2.1
 4. PLEASE NOTE ON THE PLAN THE SIZING TABLE USED FROM
 FBC FG 402.4
  
 5. EXPOSED PIPING SHALL BE LABELED AS NATURAL GAS OR
 DIESEL.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  