| 2018-09-26 12:42:13 | FLORIDA BUILDING CODE 2017 6TH EDITION |
| | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED |
| | NFPA 70 2014 EDITION |
| | |
| | JAKE LEAHY |
| | ELECTRICAL PLANS EXAMINER II |
| | 561-805-6713 |
| | [email protected] |
| | |
| | PERMIT CAN NOT BE ISSUED TO A CGC WITHOUT AN ELECTRICAL |
| | SUB-PERMIT |
| | |
| | #1 |
| | GSB HAS 1600A BREAKER |
| | ATS-2 HAS A 3000A BREAKER |
| | |
| | 240.87 ARC ENERGY REDUCTION |
| | WHERE THE HIGHEST CONTINUOUS CURRENT TRIP SETTING FOR |
| | WHICH THE |
| | ACTUAL OVERCURRENT DEVICE INSTALLED IN A CIRCUIT |
| | BREAKER IS RATED |
| | OR CAN BE ADJUSTED IS 1200 A OR HIGHER, 240.87(A) AND |
| | (B) SHALL |
| | APPLY. |
| | (A) DOCUMENTATION. DOCUMENTATION SHALL BE AVAILABLE TO |
| | THOSE |
| | AUTHORIZED TO DESIGN, INSTA LL, OPERATE, OR INSPECT THE |
| | INSTALLATION |
| | AS TO THE LOCATION OF THE CIRCUIT BREAKER(S). |
| | |
| | #2 |
| | VALUE TO LOW FOR PROPOSED WORK. |
| | |
| | FBC 109.3 BUILDING PERMIT VALUATION. FOR PERMITTING |
| | PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL BE |
| | TOTAL REPLACEMENT |
| | VALUE TO INCLUDE STRUCTURAL, ELECTRIC, PLUMBING, |
| | MECHANICAL, INTERIOR FINISH, RELATIVE SITE WORK, |
| | ARCHITECTURAL AND DESIGN FEES, |
| | MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY |
| | LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST |
| | PUBLISHED |
| | DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES |
| | (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY |
| | INTERNATIONAL CODE |
| | CONGRESS. FINAL BUILDING PERMIT VALUATION SHALL BE SET |
| | BY THE BUILDING OFFICIAL. |
| | |
| | #3 |
| | SUBMIT CUT SHEETS ON PANEL GSB, ATS #1, #2, MAIN LSI, |
| | EMERGENCY MAIN. GENERATORS. |
| | |
| | #4 |
| | 800A MAIN LSI IS NOT GROUPED WITH ATS-1 MAIN |
| | 200A EMERGENCY MAIN IS NOT GROUPED WITH ATS-2 MAIN. |
| | |
| | #5 |
| | 250.64 GROUNDING ELECTRODE CONDUCTOR INSTALLATION |
| | (A) ALUMINUM OR CO PPER-CLAD ALUMINUM CONDUCTORS. |
| | BARE ALUMINUM OR COPPER-CLAD ALUMINUM GROUNDING |
| | ELECTRODE |
| | CONDUCTORS SHALL NOT BE USED WHERE IN DIRECT CONTACT |
| | WITH MASONRY |
| | OR THE EARTH OR WHERE SUBJECT TO CORROSIVE CONDITIONS. |
| | WHERE |
| | USED OUTSIDE, ALUMINUM OR COPPER-CLAD ALUMINUM |
| | GROUNDING |
| | ELECTRODE CONDUCTORS SHALL NOT BE TERMINATED WITHIN 450 |
| | MM |
| | (18 IN.) OF THE EARTH. |
| | |
| | #6 |
| | WIRE AND CONDUIT SCHEDULE #9 SHOWS A 2/0 WHICH SHOULD |
| | BE 4/0 |
| | |
| | #7 |
| | PROVIDE FPL MAXIMUM DEMAND FOR THE SERVICE RECORDS FOR |
| | THE MAINS LOAD CALCULATION. |
| | |
| | |
| | |
| | |