Plan Review Notes
Plan Review Notes For Permit 18081512
Permit Number 18081512
Review Stop E
Sequence Number 1
Notes
Date Text
2018-09-26 12:42:13FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 PERMIT CAN NOT BE ISSUED TO A CGC WITHOUT AN ELECTRICAL
 SUB-PERMIT
  
 #1
 GSB HAS 1600A BREAKER
 ATS-2 HAS A 3000A BREAKER
  
 240.87 ARC ENERGY REDUCTION
 WHERE THE HIGHEST CONTINUOUS CURRENT TRIP SETTING FOR
 WHICH THE
 ACTUAL OVERCURRENT DEVICE INSTALLED IN A CIRCUIT
 BREAKER IS RATED
 OR CAN BE ADJUSTED IS 1200 A OR HIGHER, 240.87(A) AND
 (B) SHALL
 APPLY.
 (A) DOCUMENTATION. DOCUMENTATION SHALL BE AVAILABLE TO
 THOSE
 AUTHORIZED TO DESIGN, INSTA LL, OPERATE, OR INSPECT THE
 INSTALLATION
 AS TO THE LOCATION OF THE CIRCUIT BREAKER(S).
  
 #2
 VALUE TO LOW FOR PROPOSED WORK.
  
 FBC 109.3 BUILDING PERMIT VALUATION. FOR PERMITTING
 PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL BE
 TOTAL REPLACEMENT
 VALUE TO INCLUDE STRUCTURAL, ELECTRIC, PLUMBING,
 MECHANICAL, INTERIOR FINISH, RELATIVE SITE WORK,
 ARCHITECTURAL AND DESIGN FEES,
 MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY
 LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST
 PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL CODE
 CONGRESS. FINAL BUILDING PERMIT VALUATION SHALL BE SET
 BY THE BUILDING OFFICIAL.
  
 #3
 SUBMIT CUT SHEETS ON PANEL GSB, ATS #1, #2, MAIN LSI,
 EMERGENCY MAIN. GENERATORS.
  
 #4
 800A MAIN LSI IS NOT GROUPED WITH ATS-1 MAIN
 200A EMERGENCY MAIN IS NOT GROUPED WITH ATS-2 MAIN.
  
 #5
 250.64 GROUNDING ELECTRODE CONDUCTOR INSTALLATION
 (A) ALUMINUM OR CO PPER-CLAD ALUMINUM CONDUCTORS.
 BARE ALUMINUM OR COPPER-CLAD ALUMINUM GROUNDING
 ELECTRODE
 CONDUCTORS SHALL NOT BE USED WHERE IN DIRECT CONTACT
 WITH MASONRY
 OR THE EARTH OR WHERE SUBJECT TO CORROSIVE CONDITIONS.
 WHERE
 USED OUTSIDE, ALUMINUM OR COPPER-CLAD ALUMINUM
 GROUNDING
 ELECTRODE CONDUCTORS SHALL NOT BE TERMINATED WITHIN 450
 MM
 (18 IN.) OF THE EARTH.
  
 #6
 WIRE AND CONDUIT SCHEDULE #9 SHOWS A 2/0 WHICH SHOULD
 BE 4/0
  
 #7
 PROVIDE FPL MAXIMUM DEMAND FOR THE SERVICE RECORDS FOR
 THE MAINS LOAD CALCULATION.
  
  
  
  