| 2019-01-15 16:31:46 | 3RD REVIEW FBC-2017 MECHANICAL |
| | PERMIT #18081507 |
| | 11/28/18 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED |
| | |
| | 1) THE PREVIOUS MECHANICAL PLANS SUBMITTEF BY STEVEN J. |
| | BRUH HAVE BEEN REMOVED. THE NEW M-1 PLAN SHEET BEARS |
| | THE TITLE BLOCK OF THE ARCHITECT, HOWEVER THE PLAN DOES |
| | NOT BEAR HIS SIGNATURE AND SEAL WHICH IS REQUIRED BY |
| | FL. STATUTE AND SECTION 61G15-16.003 FAC. IF KYSAR AC, |
| | WHOSE TITLE BLOCK ALSO APPEARS ON THE PLAN, IS THE NEW |
| | MECHANCIAL DESIGNER OF RECORD, HE CANNOT USE THE |
| | ARCHITECT'S PLAN WHICH HAS ARCHITECTURAL AND ELECTRICAL |
| | DETAILS AND NOTES THAT ARE BEYOND HIS SCOPE. KYSAR MUST |
| | PROVIDE A SEPARATE, CLEAR, LEGIBLE PLAN FOR REVIEW THAT |
| | ADDRESSES ALL PREVIOUS REVIEW COMMENTS CONCERNING THE |
| | MECHANICAL ALTERATIONS- SEE COMMENTS BELOW. |
| | |
| | A) REFER TO SECTION 809.2 FBC-17 EXISTING BUILDING CODE |
| | AND PROVIDE MINIMUM VENTILATION CALCULATIONS FOR ALL |
| | ROOMS AND SPACES PER TABLE 403.3.1 FBC-17 MECHANICAL. |
| | PROVIDE A SCHEDULE THAT INDICATES THE REQUIRED AND |
| | PROVIDED CFMS OF OUTDOOR AIR. |
| | |
| | B) PROVIDE A DUCT LAYOUT PLAN SHOWING THE REQUIRED |
| | ALTERATIONS TO THE EXISTING SYSTEMS TO ACCOMODATE THE |
| | NEW ROOMS AND SPACES WITH BALANCED AIR CONDITIONING- |
| | SECTION 603.1 FBC M. |
| | |
| | C) PROVIDE AN AIR DEVICE SCHEDULE. |
| | |
| | 2) THE ARCHITECT OF RECORD STEVEN BRUH HAS ADDRESSED |
| | OTHER COMMENTS FROM THE 1ST REVIEW IN A RESPONSE |
| | NARRATIVE, HOWEVER HIS RESPONSES MUST BE APPLIED TO |
| | SIGNED AND SEALED PLANS THAT WILL BE APPROVED FOR |
| | INSPECTION, AND FOR PUBLIC RECORD- SEE COMMENTS BELOW |
| | |
| | A) EXHAUST VENTILATION CALCULATIONS FOR THE DISPATCH |
| | AND LOADING AREAS. PLEASE REVIEW SECTION 406 AND |
| | IDENTIFY IF THE AREAS IN QUESTION ARE TO BE CLASSIFIED |
| | AS PRIVATE OR PUBLIC GARAGES. IN EITHER CASE EXHAUST |
| | VENTILATION SYSTEMS SIZED AT A RATE OF 0.75 CFMS PER |
| | SF. WILL BE REQUIRED- TABLE 403.3.1.1 FBC M. (SEE SHEET |
| | A-1: THE PLANS SHOW OVERHEAD DOORS AT GRADE LEVEL IN |
| | THESE AREAS WHICH ALLOWS FOR VEHICLES TO DRIVE IN AND |
| | OUT, AND ALSO BE PARKED). |
| | |
| | B) CLARIFY THE USE OF THE CHARGING STATION SHOWN IN THE |
| | WAREHOUSE OF SHEET EP-1. PLEASE NOTE THAT AN EXHAUST |
| | VENTILATION SYSTEM IS REQUIRED FOR BATTERY CHARGING |
| | AREAS PER SECTIONS 502.3- 502.5.3 FBC M. (THE ARCHITECT |
| | HAS INDICATED CELL PHONE CHARGING AND NOT BATTERY |
| | CHARGING FOR FORKLIFTS IN THIS AREA. THE ARCHITECT MUST |
| | INDICATE THAT ON THE PLAN, OTHERWISE PROVIDE THE |
| | REQUIRED EXHAUST VENTILATION IN THIS AREA). |
| | |
| | C) PROVIDE THE LEVEL OF ALTERATION FOR THE PROPOSED |
| | PROJECT- SEE CHAPTER 5 FBC EX AND DETERMINE IF THE |
| | PROJECT IS A LEVEL 1, 2, OR 3 ALTERATION OR A CHANGE OF |
| | OCCUPANCY. |
| | |
| | D) SHOW HOW THE WAREHOUSE IS BEING VENTILATED AND WHAT |
| | MATERIALS ARE BEING STORED THERE- SEE SECTIONS 401.2, |
| | 402.1 AND TABLE 403.3.1.1. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL PLANS EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL 33401 |
| | 561-805-6719 |
| | [email protected] |
| | |