| 2018-11-28 16:05:36 | 2ND REVIEW FBC-2017 MECHANICAL |
| | PERMIT #18081507 |
| | 11/28/18 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED |
| | |
| | SOME OF THE 1ST REVIEW COMMENTS LISTED BELOW HAVE NOT |
| | BEEN ADDRESSED COMPLETELY. PLEASE COMPLY |
| | |
| | 1) REFER TO SECTION 809.2 FBC-17 EXISTING BUILDING CODE |
| | AND PROVIDE MINIMUM VENTILATION CALCULATIONS FOR ALL |
| | ROOMS AND SPACES PER TABLE 403.3.1 FBC-17 MECHANICAL. |
| | PROVIDE A SCHEDULE THAT INDICATES THE REQUIRED AND |
| | PROVIDED CFMS OF OUTDOOR AIR. |
| | |
| | 2) PROVIDE A DUCT LAYOUT PLAN SHOWING THE REQUIRED |
| | ALTERATIONS TO THE EXISTING SYSTEMS TO ACCOMODATE THE |
| | NEW ROOMS AND SPACES WITH BALANCED AIR CONDITIONING- |
| | SECTION 603.1 FBC M. ( SEE SHEET EP-1: SUPPLY AND |
| | RETURN MISSING FROM SOME OF THE NEW ROOMS BEING |
| | CONSTRUCTED). |
| | |
| | 3) EXHAUST VENTILATION CALCULATIONS FOR THE DISPATCH |
| | AND LOADING AREAS. PLEASE REVIEW SECTION 406 AND |
| | IDENTIFY IF THE AREAS IN QUESTION ARE TO BE CLASSIFIED |
| | AS PRIVATE OR PUBLIC GARAGES. IN EITHER CASE EXHAUST |
| | VENTILATION SYSTEMS SIZED AT A RATE OF 0.75 CFMS PER |
| | SF. WILL BE REQUIRED- TABLE 403.3.1.1 FBC M. (SEE SHEET |
| | A-1: THE PLANS SHOW OVERHEAD DOORS AT GRADE LEVEL IN |
| | THESE AREAS WHICH ALLOWS FOR VEHICLES TO DRIVE IN AND |
| | OUT, AND ALSO BE PARKED). |
| | |
| | 4) CLARIFY THE USE OF THE CHARGING STATION SHOWN IN THE |
| | WAREHOUSE OF SHEET EP-1. PLEASE NOTE THAT AN EXHAUST |
| | VENTILATION SYSTEM IS REQUIRED FOR BATTERY CHARGING |
| | AREAS PER SECTIONS 502.3- 502.5.3 FBC M. (THE ARCHITECT |
| | HAS INDICATED CELL PHONE CHARGING AND NOT BATTERY |
| | CHARGING FOR FORKLIFTS IN THIS AREA. THE ARCHITECT MUST |
| | INDICATE THAT ON THE PLAN, OTHERWISE PROVIDE THE |
| | REQUIRED EXHAUST VENTILATION IN THIS AREA). |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL PLANS EXAMINER |