2018-11-28 16:05:362ND REVIEW FBC-2017 MECHANICAL
 PERMIT #18081507
 11/28/18
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED
  
 SOME OF THE 1ST REVIEW COMMENTS LISTED BELOW HAVE NOT
 BEEN ADDRESSED COMPLETELY. PLEASE COMPLY
  
 1) REFER TO SECTION 809.2 FBC-17 EXISTING BUILDING CODE
 AND PROVIDE MINIMUM VENTILATION CALCULATIONS FOR ALL
 ROOMS AND SPACES PER TABLE 403.3.1 FBC-17 MECHANICAL.
 PROVIDE A SCHEDULE THAT INDICATES THE REQUIRED AND
 PROVIDED CFMS OF OUTDOOR AIR.
  
 2) PROVIDE A DUCT LAYOUT PLAN SHOWING THE REQUIRED
 ALTERATIONS TO THE EXISTING SYSTEMS TO ACCOMODATE THE
 NEW ROOMS AND SPACES WITH BALANCED AIR CONDITIONING-
 SECTION 603.1 FBC M. ( SEE SHEET EP-1: SUPPLY AND
 RETURN MISSING FROM SOME OF THE NEW ROOMS BEING
 CONSTRUCTED).
  
 3) EXHAUST VENTILATION CALCULATIONS FOR THE DISPATCH
 AND LOADING AREAS. PLEASE REVIEW SECTION 406 AND
 IDENTIFY IF THE AREAS IN QUESTION ARE TO BE CLASSIFIED
 AS PRIVATE OR PUBLIC GARAGES. IN EITHER CASE EXHAUST
 VENTILATION SYSTEMS SIZED AT A RATE OF 0.75 CFMS PER
 SF. WILL BE REQUIRED- TABLE 403.3.1.1 FBC M. (SEE SHEET
 A-1: THE PLANS SHOW OVERHEAD DOORS AT GRADE LEVEL IN
 THESE AREAS WHICH ALLOWS FOR VEHICLES TO DRIVE IN AND
 OUT, AND ALSO BE PARKED).
  
 4) CLARIFY THE USE OF THE CHARGING STATION SHOWN IN THE
 WAREHOUSE OF SHEET EP-1. PLEASE NOTE THAT AN EXHAUST
 VENTILATION SYSTEM IS REQUIRED FOR BATTERY CHARGING
 AREAS PER SECTIONS 502.3- 502.5.3 FBC M. (THE ARCHITECT
 HAS INDICATED CELL PHONE CHARGING AND NOT BATTERY
 CHARGING FOR FORKLIFTS IN THIS AREA. THE ARCHITECT MUST
 INDICATE THAT ON THE PLAN, OTHERWISE PROVIDE THE
 REQUIRED EXHAUST VENTILATION IN THIS AREA).
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  